40 Chapter 3 Fault Management<br />
Digital Output Module Alarms<br />
Digital output module faults are reported to the control application and can be used to increase<br />
availability during specific multiple-fault conditions. Loss of field power or logic power is<br />
reported to the control application.<br />
The inability of a digital output module to control an output point is reported to the control<br />
application as a Load/Fuse alarm. This condition can result from a loss of field power or a field<br />
short condition. The alarm can be used to modify the control strategy or direct effective<br />
maintenance action.<br />
Pulse Input (PI) Module<br />
The pulse input module points use a combination of comparison and reference diagnostics.<br />
Under system control, each channel is independently compared against the measured value of<br />
all channels. If a mismatch is found, an alarm is set. Each channel’s measured values are also<br />
compared against the channel’s internal references. These diagnostics are executed<br />
independently by each channel, thus assuring nearly 100 percent fault coverage and fail-safe<br />
operation under all single-fault scenarios, and most common multiple-fault scenarios.<br />
Pulse Input Module Alarms<br />
Pulse input module faults are reported to the control application. These alarms can be used to<br />
increase availability during specific multiple-fault conditions. Loss of logic power is reported to<br />
the control application.<br />
Solid-State Relay Output (SRO) Modules<br />
Solid-state relay output module points are not intended <strong>for</strong> safety-critical applications. The<br />
diagnostics used by the solid-state relay output points cannot detect faults in the relay contacts.<br />
Solid-State Relay Output Module Alarms<br />
Solid-state relay output module faults are reported to the control application.<br />
<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Trident</strong> <strong>v2</strong> <strong>Systems</strong>