Re-powering Study for the Northport <strong>and</strong> Port Jefferson Power Stations<br />

<strong>Appendix</strong> II Northport System Descriptions<br />

One instrument air receiver is provided downstream of the dryers to provide surge capacity for the<br />

Instrument Air System.<br />

From the air filtration <strong>and</strong> drying units, instrument air is provided to the various instrument air users<br />

throughout the plant.<br />

2.13 <strong>Plan</strong>t Make<strong>up</strong> Water Treatment<br />

For Northport, raw water (city water) is used for service water, fire protection, <strong>and</strong> demineralized water<br />

system make<strong>up</strong>. Raw water is ultimately used in the steam cycle make <strong>up</strong> after being treated<br />

appropriately.<br />

Untreated water is stored in the raw water tank. The lower portion of the tank is dedicated for the fire<br />

protection system <strong>and</strong> water for the other systems in the <strong>up</strong>per portion. Raw water is drawn from a nozzle<br />

above the fire water storage high level. The <strong>up</strong>per portion of the tank has sufficient storage to meet raw<br />

water dem<strong>and</strong> for a safe shutdown of the plant in the event of a loss of off-site water s<strong>up</strong>ply.<br />

Two 100% capacity service/raw water pumps are provided. The service water system provides a feed to<br />

the water treatment cycle, <strong>and</strong> to miscellaneous plant washdown services.<br />

Refer to PID-09-21A in <strong>Appendix</strong> III.<br />

Two 100% demineralizer feed pumps direct water from the service water tank to a reverse osmosis/EDI<br />

demineralizer system. Pumps are started <strong>and</strong> stopped by the operator from the control room using the<br />

distributed control system (DCS). Demineralized water is directed via demineralizer outlet pumps to the<br />

demineralized water storage tank. Two 100% demineralized water forwarding pumps draw suction from<br />

the tank to distribute water to the condenser for steam cycle make-<strong>up</strong>, combustion turbine generator wash<br />

water skid, combustion turbine evaporative coolers, combustion turbine water injection (when burning<br />

oil) <strong>and</strong> to the phosphate chemical feed skid.<br />

2.14 <strong>Plan</strong>t Waste Water Treatment<br />

Refer to PID-13-19A in <strong>Appendix</strong> III.<br />

All liquid wastes produced within Northport is collected in their designated sumps <strong>and</strong> pumped to the<br />

existing wastewater treatment system. Each sump will have two 100 percent capacity sump pumps<br />

controlled by float-switch actuated mechanical alternator to equalize the wear on pumps. Each sump<br />

pump will be installed according to the manufacturer’s recommendations for the clearance between the<br />

pump casing <strong>and</strong> the floor of the sump. Each sump float-switch actuated mechanical alternator will<br />

provide protection for its pumps by stopping the operating pump at a predetermined low level in the<br />

sump. The pump alternator will also have a high level switch to start the selected pumps <strong>and</strong> a high-high<br />

level switch to start the st<strong>and</strong>by pump <strong>and</strong> alarm. Each sump has its own set of controls <strong>and</strong> manual<br />

valves.<br />

Steam turbine area wastewater is collected in the condensate sump. One of two 100 percent condensate<br />

sump pumps route condensate sump water to the oil/water separator.<br />

Oily runoff <strong>and</strong> drainage from the power block <strong>and</strong> surrounding areas is collected in the oil/water<br />

separator. Water separated from the oil is routed to the wastewater collection sump by one of two 100<br />

percent oil/water separator sump pumps.<br />

March 30, 2009 166