Appendix E-2.c.i Energy Plan 2004-2013 Follow-up Studies and ...

Appendix E-2.c.i Energy Plan 2004-2013 Follow-up Studies and ... Appendix E-2.c.i Energy Plan 2004-2013 Follow-up Studies and ...

23.12.2012 Views

2.1 Main Steam Re-powering Study for the Northport and Port Jefferson Power Stations Appendix II Northport System Descriptions 2 System Descriptions for Backyard Option Refer to PID-03-1A and 03-1B in Appendix III. 2.1.1 Main Flow Path The Main Steam system conveys superheated steam from the HP superheater outlet of each of the three HRSG’s to the steam turbine via the turbine main steam trip and control valves. The three HRSGs supply main steam within the pressure and temperature limits required by the turbine design. Inside each HRSG boundary, the HP superheater contains an attemperator which uses HP feedwater to provide temperature control and maintain the HP superheater outlet temperature. Isolation of each HRSG from the main steam system header, in the Northport 3x3x1 configuration, is provided by a stop-check block valve located near the header. The turbine main steam trip and control valve provides positive isolation of the steam turbine from the main steam system. The Main Steam System also supplies steam to the steam turbine gland seals during startup. A pressure reducing valve and spray desuperheater is provided in the line to this service to lower the steam pressure and temperature to match the ST manufacturers’ requirements. Low point drain pots are located in the system in accordance with ASME TPD, “Recommended Practices for the Prevention of Water Damage to Steam Turbines Used for Electric Power Generation”. Depending on the location, low point drains are directed to either the condenser or the atmospheric blowoff tank associated with each HRSG. 2.1.2 Bypass Flow Path The main steam bypass flow path provides the means to convey main steam from each HRSG to the cold reheat system via a main steam bypass conditioning valve station. During normal load operation, the main steam by-pass valves are shut. The bypass station permits main steam generated in each CT/HRSG set to be removed during normal CT startup, normal shutdown, steam turbine trip, or when the steam turbine is removed from service. The conditioning valve controls main steam pressure by bleeding off main steam, reducing its pressure and temperature to match the operating parameters of the cold reheat steam system. The conditioning valve controls the temperature of the outlet by spraying HP feedwater at a controlled rate to match the cold reheat steam temperature. 2.2 Cold Reheat Refer to PID-03-02A in Appendix III. The Cold Reheat Steam System directs the high pressure steam turbine exhaust to each HRSG reheat inlet header. The cold reheat steam line from the steam turbine joins into a common header, which then splits into branches, one to each HRSG reheater inlet. For The Backyard Option, a non-return valve is provided in the cold reheat line to prevent backflow into the high pressure turbine. This valve protects the turbine when the main steam system is bypassed to the March 30, 2009 156

Re-powering Study for the Northport and Port Jefferson Power Stations Appendix II Northport System Descriptions cold reheat system during turbine start-up, shutdown, and turbine trip events. The valve is controlled through the steam turbine control system to prevent closure whenever the main steam stop/throttle valve is open. Each individual cold reheat line to an HRSG has a motor-operated gate valve and a branch from the main steam bypass valve. Main steam is bypassed around the steam turbine to the cold reheat steam system during plant start-up, shutdown, and when the turbine is out of service. The multiple combustion turbine generators at Northport are assumed to operate at the same load over their range of operation. For this reason, no balancing valves are provided in the cold reheat lines. Within the HRSG scope of supply, IP superheater outlet piping connects to the cold reheat piping prior to the reheat inlet connection. A branch connection from the cold reheat line supplies steam to the auxiliary steam system during normal operation. The branch has a motor operated block valve and a pressure control valve. All portions of the cold reheat pipe, as well as the steam turbine HP casing, require overpressure protection. For Northport Backyard Option, stop valves are located in the cold reheat leads to each HRSG. These intervening stop valves could potentially isolate the relief path from the HP turbine outlet connection to the HRSG reheater safety valves. Therefore, safety valves are required in the cold reheat piping for Northport between the HP turbine outlet connection and the non-return valve. Low point drain pots, equipped with level sensing devices, are in accordance with ASME TPD, "Recommended Practices for the Prevention of Water Damage to Steam Turbines Used for Electric Power Generation". 2.3 Hot Reheat Refer to PID-03-3A and PID-03-03B in Appendix III. The Hot Reheat Steam System directs superheated steam from the Hot Reheat outlet of each HRSG to the IP steam turbine. The reheater outlet temperature is controlled by an attemperator located within the HRSG boundary between the primary and final sections. The attemperator uses IP feedwater to provide temperature control and maintain the hot reheat outlet temperature. The hot reheat steam line from each HRSG contains a flow nozzle, a bypass branch and a motor operated stop-check valve. The HRSG steam leads combine into a common header en route to the steam turbine. At the steam turbine, the header splits into two branches, one to each combined reheat valve. Hot reheat bypass valves provide means to bypass hot reheat steam to the condenser during startup, normal shutdown, steam turbine trips, or when the steam turbine is removed from service while the combustion turbines continue to operate. The hot reheat lead from each HRSG is equipped with a steam conditioning valve (bypass valve) to reduce the hot reheat pressure and temperature to acceptable condenser design levels. Attemperating water for the bypass valves is from the condensate system through temperature control valves. Low point drains are in accordance with ASME TPD, “Recommended Practices for the Prevention of Water Damage to Steam Turbines Used for Electric Power Generation”. March 30, 2009 157

Re-powering Study for the Northport <strong>and</strong> Port Jefferson Power Stations<br />

<strong>Appendix</strong> II Northport System Descriptions<br />

cold reheat system during turbine start-<strong>up</strong>, shutdown, <strong>and</strong> turbine trip events. The valve is controlled<br />

through the steam turbine control system to prevent closure whenever the main steam stop/throttle valve<br />

is open.<br />

Each individual cold reheat line to an HRSG has a motor-operated gate valve <strong>and</strong> a branch from the main<br />

steam bypass valve. Main steam is bypassed around the steam turbine to the cold reheat steam system<br />

during plant start-<strong>up</strong>, shutdown, <strong>and</strong> when the turbine is out of service. The multiple combustion turbine<br />

generators at Northport are assumed to operate at the same load over their range of operation. For this<br />

reason, no balancing valves are provided in the cold reheat lines.<br />

Within the HRSG scope of s<strong>up</strong>ply, IP s<strong>up</strong>erheater outlet piping connects to the cold reheat piping prior to<br />

the reheat inlet connection.<br />

A branch connection from the cold reheat line s<strong>up</strong>plies steam to the auxiliary steam system during normal<br />

operation. The branch has a motor operated block valve <strong>and</strong> a pressure control valve.<br />

All portions of the cold reheat pipe, as well as the steam turbine HP casing, require overpressure<br />

protection. For Northport Backyard Option, stop valves are located in the cold reheat leads to each<br />

HRSG. These intervening stop valves could potentially isolate the relief path from the HP turbine outlet<br />

connection to the HRSG reheater safety valves. Therefore, safety valves are required in the cold reheat<br />

piping for Northport between the HP turbine outlet connection <strong>and</strong> the non-return valve.<br />

Low point drain pots, equipped with level sensing devices, are in accordance with ASME TPD,<br />

"Recommended Practices for the Prevention of Water Damage to Steam Turbines Used for Electric<br />

Power Generation".<br />

2.3 Hot Reheat<br />

Refer to PID-03-3A <strong>and</strong> PID-03-03B in <strong>Appendix</strong> III.<br />

The Hot Reheat Steam System directs s<strong>up</strong>erheated steam from the Hot Reheat outlet of each HRSG to the<br />

IP steam turbine.<br />

The reheater outlet temperature is controlled by an attemperator located within the HRSG boundary<br />

between the primary <strong>and</strong> final sections. The attemperator uses IP feedwater to provide temperature<br />

control <strong>and</strong> maintain the hot reheat outlet temperature.<br />

The hot reheat steam line from each HRSG contains a flow nozzle, a bypass branch <strong>and</strong> a motor operated<br />

stop-check valve. The HRSG steam leads combine into a common header en route to the steam turbine.<br />

At the steam turbine, the header splits into two branches, one to each combined reheat valve.<br />

Hot reheat bypass valves provide means to bypass hot reheat steam to the condenser during start<strong>up</strong>,<br />

normal shutdown, steam turbine trips, or when the steam turbine is removed from service while the<br />

combustion turbines continue to operate. The hot reheat lead from each HRSG is equipped with a steam<br />

conditioning valve (bypass valve) to reduce the hot reheat pressure <strong>and</strong> temperature to acceptable<br />

condenser design levels. Attemperating water for the bypass valves is from the condensate system<br />

through temperature control valves.<br />

Low point drains are in accordance with ASME TPD, “Recommended Practices for the Prevention of<br />

Water Damage to Steam Turbines Used for Electric Power Generation”.<br />

March 30, 2009 157

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!