Sentron 3/6 Bus Plugs<br />

Sentron 3/6 Bus Plugs<br />

Revised on 04/30/18<br />

Technical<br />

Product Overview<br />

The Sentron 3/6 bus plug is designed for light industrial,<br />

commercial, and datacenter applications. Optional factory<br />

installed receptacles range from 10 to 100A per pole, and<br />

the bus plug allows for anywhere between 1 and 6 poles of<br />

distribution (i.e. two 3Ø receptacles per plug). This product<br />

combines plug-and-play capabilities, minimizing installation<br />

time and cost, with the option for preconfigured embedded<br />

branch circuit metering utilizing SEM3.<br />

Product Application<br />

Building your metered network of Sentron 3/6 bus plugs is<br />

easy. There are two variations of metered bus plugs, simple<br />

meter plugs (child) and controller plugs (parent). Each SEM3<br />

controller can monitor 42 bus plug poles. Depending on the<br />

number of metered poles per bus plug, one parent controller<br />

plug can monitor between 6 to 41 bus plugs. An example of<br />

a network of seven 6-pole bus plugs is shown below (in this<br />

case there is one controller and six metered plugs). Outputs<br />

from multiple controller plugs may be consolidated at an<br />

Ethernet switch (shown below) or integrated directly into a<br />

building or site management system.<br />

Metered Bus Plug 1 Metered Bus Plug 2 Metered Bus Plug 3 Controller Bus Plug 1 Metered Bus Plug 4 Metered Bus Plug 5 Metered Bus Plug 6<br />

15<br />

600V Isolated<br />

Siemens Cable<br />

Controller Bus Plug 2<br />

600V Isolated<br />

Siemens Cable<br />

600V Isolated<br />

Siemens Cable<br />

600V Isolated<br />

Siemens Cable<br />

600V Isolated<br />

Siemens Cable<br />

8 Port Ethernet Switch<br />

600V Isolated<br />

Siemens Cable<br />

BUSWAY SYSTEMS<br />

CAT6 Cable<br />

CAT6 Cable<br />

CAT6 Cable<br />

Controller Bus Plug 3<br />

The function of the Ethernet switch is to aggregate signals being<br />

generated by each SEM3 controller. Each SEM3 controller bus plug may<br />

monitor up to 42 poles. Metered bus plugs may have between 1 and 6<br />

metered poles. SEM3 may also be embedded in other electrical<br />

equipment such as switchboards or panels, providing a comprehensive<br />

power monitoring solution.<br />

Power Monitoring System/Building<br />

Management System/SCADA<br />

CAT6 Cable<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 15-59