Sentron Busway Systems<br />

Panelboards and Meter Center Modules<br />

Selection<br />

Meter center modules provide a quick and<br />

convenient method of connecting to metering<br />

devices for both commercial and industrial<br />

applications.<br />

Meter center modules connect at the side of a<br />

busway run to special joint stacks; these special<br />

joints can be added to existing busway to<br />

accommodate meter center module<br />

connections. When using multiple metering<br />

stacks, main disconnects are available if the<br />

system reaches the 6 circuit rule (see metering<br />

bulletin for further information).<br />

15<br />

BUSWAY SYSTEMS<br />

Dimensional Data Required<br />

Dimensions Inches (mm)<br />

“A” Distance between floor and bottom<br />

of meter center as required by the<br />

customer.<br />

“B” Dimension from bottom of meter<br />

center to centerline of meter center<br />

joint connection stack:<br />

100-125A Panel, B = 16.5 (419)<br />

200A Panel, B = 22.0 (559)<br />

“C” Equals “A” plus “B”, Minimum 16.0 (406)<br />

“D” Individual meter center height.<br />

Consult Modular Metering application<br />

information.<br />

15-34<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog