Sentron Busway Systems<br />

Service Heads<br />

Selection<br />

Service Heads are used to connect busway to a service entrance. In the Sentron Busway line, 3 single-phase service heads and<br />

3-phase service head connections are available. The standard service entrance connection is the 3-phase service head which<br />

consists of one service head for all three phases. 3 single-phase service heads consist of three heads – one for each phase and<br />

may be used to meet the requirements of certain applications. To ensure ease of installation of incoming cables, both types of<br />

Sentron service heads are constructed so that the lugs face the Glastic bottom of the box. The Glastic bottom provides<br />

insulation and protection to the incoming cables.<br />

15<br />

BUSWAY SYSTEMS<br />

Single-Phase Service Heads, Dimensions (standard/min.)<br />

Cable Lugs per<br />

Dimensions Inches (mm) Phase and Neutral Ground<br />

Ampere Rating Single-Phase “A” Qty. Size Lugs a<br />

AL L-Rated<br />

225 13 (330) 1 a 1<br />

400 225 13 (330) 1 b 1<br />

600 — 13 (330) 2 b 1<br />

800 400 13 (330) 3 b 1<br />

1000 600 13 (330) 4 b 1<br />

1200 800 18 (457) 4 b 1<br />

1350 1000 18 (457) 4 b 1<br />

1600 1200 18 (457) 5 b 1<br />

2000 1350,1600 20 (508) 6 b 2<br />

2500 2000 27 (686) 8 b 2<br />

3000 2500 29 (737) 9 b 2<br />

3200 2000 29 (737) 9 b 2<br />

4000 3000,3200 29 (737) 12 b 3<br />

CU M-Rated<br />

225 13 (330) 1 a 1<br />

400 13 (330) 1 b 1<br />

600 13 (330) 2 b 1<br />

800 400 13 (330) 3 b 1<br />

1000 — 13 (330) 4 b 1<br />

1200 600 13 (330) 4 b 1<br />

1350 800 13 (330) 4 b 1<br />

1600 1000 18 (457) 5 b 1<br />

2000 1200,1350 20 (508) 6 b 2<br />

— 1600 18 (457) 5 b 1<br />

2500 2000 20 (508) 8 b 2<br />

3000 — 27 (686) 9 b 2<br />

3200 — 27 (686) 9 b 2<br />

4000 2500,3000,3200 27 (686) 12 b 3<br />

5000 4000 29 (737) 15 b 4<br />

Three Single-Phase Service Heads<br />

Suffix V1TX<br />

Three-Phase Service Heads, Dimensions (standard/min.)<br />

Cable Lugs per<br />

Dimensions Inches (mm) Phase and Neutral Ground<br />

Ampere Rating Three-Phase “B” Qty. Size Lugs a<br />

AL L-Rated<br />

225 13 (330) 1 a 1<br />

400 225 13 (330) 1 b 1<br />

600 — 13 (330) 2 b 1<br />

800 400 13 (330) 3 b 1<br />

1000 600 13 (330) 4 b 1<br />

1200 800 18 (457) 4 b 1<br />

1350 1000 18 (457) 4 b 1<br />

1600 1200 18 (457) 5 b 1<br />

2000 1350,1600 18 (457) 6 b 2<br />

2500 2000 27 (686) 8 b 2<br />

3000 2500 27 (686) 9 b 2<br />

3200 2000 27 (686) 9 b 2<br />

4000 3000,3200 29 (737) 12 b 3<br />

CU M-Rated<br />

225 13 (330) 1 a 1<br />

400 13 (330) 1 b 1<br />

600 13 (330) 2 b 1<br />

800 400 13 (330) 3 b 1<br />

1000 — 13 (330) 4 b 1<br />

1200 600 13 (330) 4 b 1<br />

1350 800 13 (330) 4 b 1<br />

1600 1000 18 (457) 5 b 1<br />

2000 1200,1350 18 (457) 6 b 2<br />

— 1600 18 (457) 5 b 1<br />

2500 2000 18 (457) 8 b 2<br />

3000 — 27 (686) 9 b 2<br />

3200 — 27 (686) 9 b 2<br />

4000 2500,3000,3200 27 (686) 12 b 3<br />

5000 4000 29 (737) 15 b 4<br />

Three-Phase Service Head<br />

Suffix V3TX<br />

a #6 AWG - 350 kcmil, Cu / Al.<br />

b #4 AWG - 600 kcmil, Cu / Al.<br />

15-24<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog