Sentron Busway Systems<br />

Expansion Fittings<br />

Revised on 06/30/18<br />

Selection<br />

15<br />

BUSWAY SYSTEMS<br />

Expansion Fittings, Dimensions (standard/min.)<br />

Dimensions Inches (mm)<br />

Ampere Rating<br />

“A”<br />

AL L-Rated<br />

225 — 13 (330)<br />

400 — 13 (330)<br />

600 — 13 (330)<br />

800 400 13 (330)<br />

1000 600 13 (330)<br />

1200 800 18 (457)<br />

1350 1000 18 (457)<br />

1600 1200 18 (457)<br />

2000 1350,1600 18 (457)<br />

2500 2000 23 (584)<br />

3000 2500 23 (584)<br />

3200 2000 25 (635)<br />

4000 3000,3200 25 (635)<br />

CU M-Rated<br />

225 — 13 (330)<br />

400 — 13 (330)<br />

600 — 13 (330)<br />

800 400 13 (330)<br />

1000 — 13 (330)<br />

1200 600 13 (330)<br />

1350 800 13 (330)<br />

1600 1000 18 (457)<br />

2000 1200,1350 18 (457)<br />

— 1600 18 (457)<br />

2500 2000 18 (457)<br />

3000 — 23 (584)<br />

3200 — 23 (584)<br />

4000 2500,3000,3200 23 (584)<br />

5000 4000 25 (635)<br />

Expansion Fittings<br />

Expansion fittings accommodate for expansion and contraction of a<br />

busway run and building movement. Expansion fittings typically are<br />

installed in the center of long busway runs, and at the beginning of<br />

riser runs (within the first 20ft of vertical busway when total vertical<br />

run length is equal to or greater then 40ft) to minimize stress on the<br />

lower most device or where a busway run crosses an expansion joint<br />

of a building.<br />

Qty (1) Expansion Section should be used for every 200ft of<br />

continuous Busway run length, at every transition to a vertical run, and<br />

at each building expansion joint. The Busway run must be positioned<br />

accordingly to accommodate the Expansion Section(s).<br />

Expansion Fitting<br />

Suffix XPFT<br />

Flush Mount Expansion Fitting<br />

Often useful in riser application, flush mount expansion fittings allow<br />

for the busway to be positioned closer to building walls (reference<br />

page 15-36 for minimum required clearances). The flush mount design<br />

shifts the centerline of the busway up or down by 5 in. on the 20 in.<br />

height axis shown above.<br />

a 24.0" (610mm) for isolated ground.<br />

15-22<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog