12.01.2021 Views

Speedfax 2017

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Siemens Unit Substation Solutions<br />

Indoor Dry Type Transformer<br />

Diagrams<br />

Indoor - dry transformer<br />

92.0 (2,337)<br />

Swgr<br />

gnd<br />

(X0)<br />

Five PEM nuts<br />

3/ 8 -16 for<br />

joining<br />

switchgear<br />

with<br />

transformer<br />

9.0 9.0<br />

(229) (229)<br />

H1 H2 H3<br />

(X1)(X2)<br />

(X3)<br />

18.5 (470)<br />

56.0 (1,422), 62.0 (1,575), 72.0 (1,829), or<br />

82.0 (2,083) transformer to left of switchgear<br />

(flush front transformer mounting)<br />

A<br />

36.0 (914)<br />

A<br />

Five PEM nuts<br />

3/ 8 -16 for<br />

joining<br />

switchgear<br />

with<br />

transformer<br />

9.0 9.0<br />

(229) (229)<br />

H1 H2 H3<br />

(X3)(X2)<br />

(X1)<br />

18.5 (470)<br />

Swgr<br />

gnd<br />

(X0)<br />

92.0 (2,337)<br />

56.0 (1,422), 62.0 (1,575), 72.0 (1,829), or<br />

82.0 (2,083) transformer to left of switchgear<br />

(flush front transformer mounting)<br />

14 SWITCHGEAR<br />

Footnotes:<br />

1. This arrangement applies to indoor SIEBREAK switch 5 kV-15 kV up to 1,200 A termination with dry-type transformer termination.<br />

2. Filler strips at the ends of the transformer must be provided by the transformer supplier in case the transformer exceeds 92” (2,337<br />

mm) height and 56” (1,422 mm) depth.<br />

3. If cables are to be used for connections to transformer, transformer supplier to provide and install cable connections including lugs<br />

and insulation on terminals if required. Maximum 2 x 500 kcmil cables per phase.<br />

4. If bus bars are to be used for connections to transformer, transformer supplier to provide and install required bus connections.<br />

Transformer supplier also to provide and install flex connectors for connections to switchgear as well as insulation for flex<br />

connectors.<br />

5. Connect switchgear ground when continuous ground is required.<br />

6. Transformer supplier to provide necessary hardware (except PEM nuts) for joining switchgear with transformer.<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 14-49

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!