12.01.2021 Views

Speedfax 2017

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Siemens Unit Substation Solutions<br />

5 – 15 kV SIEBREAK Metal-Enclosed Load Interrupter Switchgear<br />

Technical Data<br />

Rated voltage Type 5 kV 15 kV<br />

Rated frequency<br />

50/60 Hz<br />

Rated duration power frequency withstand voltage 19 kV 36 kV<br />

Rated lightning impulse withstand voltage (BIL) 60 kV 95 kV<br />

Fuse short circuit current rating Current Limiting 50 kA 50 kA<br />

Expulsion 37.5 29.4<br />

Switch rating Continuous Current 600 A and 1200 A<br />

Interrupting rms<br />

25 kA and 38 kA<br />

Momentary rms<br />

40 kA, 61 kA, 80 kA<br />

Assembly rating Main bus continuous current 1200 A and 2000 A<br />

Short-time 2 second<br />

25kA and 38 kA<br />

14<br />

SWITCHGEAR<br />

Fuse Selection Table<br />

System<br />

Voltage<br />

Fuse<br />

type a<br />

Symmetrical<br />

Interrupting kA<br />

Equivalent<br />

MVA 500 kVA 750 kVA 1000 kVA 1500 kVA 2000 kVA 2500 kVA 3000 kVA 3750 kVA 5000 kVA<br />

2400 CL-14 50 260 200 250 400 500 600 — — — —<br />

RBA400 37.5 155 200 250 400 — — — — — —<br />

RBA800 37.5 155 — — — 540 720 — — — —<br />

4160 CL-14 50 450 100 125 200 300 500 500 — — —<br />

RBA400 37.5 270 100 150 200 300 400 — — — —<br />

RBA800 37.5 270 — — — — 540 540 — —<br />

4800 CL-14 50 520 80 125 200 250 400 450 — — —<br />

RBA400 37.5 310 100 125 200 250 400 400 — — —<br />

RBA800 37.5 310 — — — — — — 540 — —<br />

7200 CL-14 50 620 65 80 125 200 250 300 — — —<br />

RBA400 29.4 365 65 80 125 200 250 300 400 — —<br />

RBA800 29.4 365 — — — — — — — 450 —<br />

12470 CL-14 50 1079 40 50 65 100 125 200 200 250 —<br />

RBA400 29.4 635 40 50 80 100 150 200 200 250 400<br />

RBA800 29.4 635 — — — — — — — — —<br />

13200 CL-14 50 1143 30 50 65 100 125 150 200 250 300<br />

RBA400 29.4 672 30 50 65 100 125 150 200 250 300<br />

RBA800 29.4 672 — — — — — — — — —<br />

13800 CL-14 50 1195 30 50 65 100 125 150 200 250 300<br />

RBA400 29.4 702 30 50 65 100 125 150 200 250 300<br />

RBA800 29.4 702 — — — — — — — — —<br />

Notes:<br />

a Incoming cables available top or bottom entry<br />

b Transformer connection available left side or right side<br />

c Auxiliary devices not available with selector and front access<br />

d Outdoor width include 18-inch (457 mm) liquid-filled transformer termination section<br />

e For outdoor dry type transformer, add 2.67 inches (67 mm) to the width for termination<br />

14-42<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog

Hooray! Your file is uploaded and ready to be published.

Saved successfully!