Medium-voltage Equipment<br />

38 kV Gas-Insulated Metal-Clad Switchgear General/Specifications<br />

Gas-Insulated Switchgear<br />

Types 8DA10 and 8DB10 mediumvoltage,<br />

gas-insulated switchgear are gasinsulated,<br />

vacuum circuit breaker designs<br />

with a voltage range of 4.16 kV to 38 kV.<br />

Lightning impulse withstand voltage<br />

ratings up to 200 kV BIL and interrupting<br />

ratings up to 40 kA are available.<br />

The types 8DA10 and 8DB10 mediumvoltage,<br />

gas-insulated switchgear designs<br />

feature fixed-mounted, vacuum circuit<br />

breakers, connectable to the main bus<br />

through three-position (closed-open-ready<br />

to ground) switches. The position of the<br />

switches is externally observable from<br />

the front of the unit using a convenient<br />

camera system. Medium-voltage, gasinsulated<br />

switchgear is suitable for<br />

systems where small size, arc resistance,<br />

environmental immunity or reduced<br />

maintenance needs are important.<br />

Depending upon the voltage rating,<br />

medium-voltage, gas-insulated switchgear<br />

is approximately 1/5th the size of<br />

conventional air-insulated switchgear.<br />

Features include:<br />

n Tested for arc-resistance to IEEE<br />

C37.20.7-2007, type 2A<br />

n Significantly reduced PPE needs<br />

n Compact – up to 80% smaller<br />

than air-insulated switchgear<br />

n 20-year internal maintenance<br />

cycle<br />

n Meets IEEE and IEC standards<br />

n UL or C-UL Listing available<br />

n Single-phase design eliminates<br />

phase-to-phase faults<br />

n Meets NEC visible disconnect<br />

requirement<br />

n Well suited for contaminated<br />

environments<br />

n Pair with Siemens protective<br />

relays to match any application.<br />

14 SWITCHGEAR<br />

Rated Values<br />

Maximum Design Voltage kV 15 27 38 42*<br />

Frequency Hz 60 60 60 60<br />

Power-Frequency Withstand Voltage (1 min.) kV rms 36 60 80 80<br />

Lightning Impulse Withstand Voltage kV peak 95 125 170; 200* 185; 200*<br />

Short-Circuit Interrupting Current kA 40 40 40 40<br />

Short-Time Withstand Current, 3 s kA 40 40 40 40<br />

Short-Circuit Making Current (close and latch) kA peak 104 104 104 104<br />

Peak Withstand Current kA peak 104 104 104 104<br />

Continuous Current of Main Bus A 4,000 4,000 4,000 4,000<br />

Continuous Current of Circuit Breakers A 2,500 2,500 2,500 2,500<br />

* On request. Consult factory<br />

Type 8DA dimensions in inches (mm)<br />

Type 8DB dimensions in inches (mm)<br />

73<br />

(1,850)<br />

47.2<br />

(1,200)<br />

82.7<br />

(2,100)<br />

47.2<br />

(1,200)<br />

106.3<br />

(2,700)<br />

106.3<br />

(2,700)<br />

59<br />

(1,500)<br />

59<br />

(1,500)<br />

23.6<br />

(600)<br />

64<br />

(1,625)<br />

23.6<br />

(600)<br />

105<br />

(2,665)<br />

Front view<br />

Side view<br />

Front view<br />

Side view<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 14-19