Panelboards<br />

Quik-Spec Coordination Panelboard<br />

Specifications<br />

Catalog Symbol: SQSCP4<br />

Description<br />

Panelboards for commercial/industrial<br />

branch or service entrance applications<br />

on systems up through 600Vac.<br />

Main options<br />

▪ Main lug only (MLO)<br />

▪ Fused main disconnect<br />

▪ Non-fused main disconnect<br />

11 PANELBOARDS<br />

The SQSCP is specifically designed<br />

to address the NEC ® Selective<br />

Coordination Requirements for<br />

Emergency, Legally Required Standby,<br />

Healthcare Essential Electrical and<br />

Critical Operation Power Systems<br />

(COPS) per NEC ® 700.28, 701.27,<br />

645.27 and 708.54. Not for applications<br />

requiring AFCI protected circuits. The<br />

SQSCP is configured to order for the<br />

application. To confirm availability of<br />

options and constructions, contact your<br />

Siemens distributor.<br />

Ratings<br />

Volts: 600Vac (or less), 125 Vdc<br />

Amps: 30, 60, 100, 200, 225, 400A<br />

SCCR: 20kA or 100kA @ 125Vdc–See<br />

panelboard short circuit ratings table for<br />

AC ratings.<br />

Agency information<br />

▪ UL 67–Standard for panelboards<br />

▪ UL 50/UL 50E–Enclosures for electrical<br />

equipment<br />

▪ CSA 22.2, No. 29-M1989–<br />

Panelboards and encl. panelboards<br />

▪ UL listed, class CTL panelboard (meets<br />

editions of the NEC prior to 2008 with<br />

regard to the NEC® 408.15 limit of<br />

42 overcurrent devices per panel)<br />

▪ UBC and CBC Seismic Qualified and<br />

IBC Approved<br />

Branch disconnect options<br />

▪ 1-, 2-, and 3-pole 15, 20, 30, 40, 50,<br />

60, 70, 90, and 100A rejecting branch<br />

disconnects (see table for details).<br />

Branch ampacity on 125Vdc panels<br />

limited to SCCPB 80A or less.<br />

Branch circuit positions<br />

▪ 18, 30 and 42<br />

Neutral options<br />

▪ Unbonded and bonded 200A, 400A<br />

and 800A<br />

Ground options<br />

▪ Isolated and non-isolated<br />

Enclosures<br />

▪ NEMA 1 and NEMA 3R. Other ratings<br />

available. Consult factory.<br />

Spare fuse compartment<br />

▪ Six space spare fuse compartment<br />

standard on all models<br />

Panelboard Short-circuit Current Ratings<br />

SCCR<br />

AC main options<br />

Main lug only<br />

(MLO) a<br />

70-200A main disc. no fuses a<br />

or w/ Class J fuses<br />

225-400A main disc. no fuses a<br />

or w/ Class J fuses<br />

SCCP_CF main<br />

disc. (60A) b<br />

High 200kA 200kA 100kA 200kA 100kA<br />

Std. 50kA 50kA 50kA 50kA 20kA<br />

a Class J, T or RK1 fuses upstream, max amps = panel amps.<br />

b CUBEFuse® disconnect<br />

DC<br />

Main lug only<br />

(MLO) a<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 11-107