12.01.2021 Views

Speedfax 2017

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Panelboards<br />

Circuit Breaker / Column Type<br />

Revised on 05/15/18<br />

Selection<br />

11<br />

PANELBOARDS<br />

Branch Breaker Selection C1<br />

Breaker<br />

Type<br />

Available<br />

Ampere<br />

Rating<br />

Maximum Interrupting<br />

Availability<br />

Rating (kA)<br />

1-Pole 2-Pole 3-Pole 120V 120/240V 240V<br />

15, 20, 30, 40, 50, 60 u u u — 10 —<br />

BL (120V) 70 u u u — 10 —<br />

70, 80, 90, 100 — u u — 10 —<br />

BL (HID) 15, 20, 30 u u — — — —<br />

BLF (GFCI)<br />

15, 20, 30 u u — 10 — —<br />

40, 50, 60 — u — 10 — —<br />

BLE (EQGFI) 15, 20, 30 u u — 10 — —<br />

BGL (SWN) 15, 20, 30 — u u 10 — —<br />

BLR (240V)<br />

15, 20, 30, 40, 50, 60 — u — — — 10<br />

70, 80, 90, 100 — u — — — 10<br />

15, 20, 30, 40, 50, 60 u u u — 22 —<br />

BLH (120V) 70 u u u — 22 —<br />

70, 80, 90, 100 — u u — 22 —<br />

BLHF (GFCI)<br />

15, 20, 30 u u — — 22 —<br />

40, 50, 60 — u — — 22 —<br />

HBL<br />

15, 20, 30, 40, 50 u u u — 65 65<br />

60, 70, 80, 90, 100 — u u — 65 65<br />

Subfeed Breakers — Limit One Per Panel b C1 (Not available for 42 circuit panels)<br />

ED4<br />

15, 20, 30, 40, 50, 60, 70, 80, 90, 100 —– u u — — 65<br />

110, 125 —– u u — — 65<br />

HED4<br />

15, 20, 30, 40, 50, 60, 70, 80, 90, 100 —– u u — — 65<br />

110, 125 —– u u — — 100<br />

HHED6 15, 20, 30, 40, 50 (3-pole only) —– — u — — 100<br />

QR2 100, 110, 125, 150, 175, 200, 225 —– u u — — 10<br />

FXD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 —– u u — — 65<br />

HFD6 c 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 —– u u — — 100<br />

Alternate Main Breaker Selection abc C2<br />

Ampere Breaker Catalog<br />

Rating Type IR Number Available Trip Values<br />

100 BQD 14 BD 50, 60, 70, 80, 90, 100<br />

ED4 18 E4 50, 60, 70, 80, 90, 100, 110, 125<br />

125 ED6 25 E6 50, 60, 70, 80, 90, 100, 110, 125<br />

HED4 42 H4 50, 60, 70, 80, 90, 100, 110, 125<br />

HHED6 65 HA 50 (3-pole only)<br />

225<br />

FXD6<br />

HFD6<br />

35<br />

65<br />

FX<br />

HF<br />

70, 80, 90, 100, 110, 125, 150, 175, 200, 225<br />

170, 80, 90, 100, 110, 125, 150, 175, 200, 225<br />

250<br />

FXD6<br />

HFD6<br />

35<br />

65<br />

FX<br />

HF<br />

250<br />

250<br />

Branch Circuit Breakers C2<br />

Breaker<br />

Type<br />

Available<br />

Ampere<br />

Rating<br />

Maximum Interrupting<br />

Availability<br />

Rating (kA)<br />

1-Pole 2-Pole 3-Pole 277V 480/277V 480V<br />

BQD<br />

15, 20, 30, 40, 50, 60 u u u 14 14 —<br />

70, 80, 90, 100 u u u 14 14 —<br />

Subfeed Breakers — Limit One Per Panel ab C2 (Not available for 42 circuit panels)<br />

ED4<br />

15, 20, 30, 40, 50, 60, 70, 80, 90, 100 —– u u — 18 18<br />

110, 125 —– u u — 18 18<br />

d 15, 20, 30, 40, 50, 60, 70, 80, 90, 100 —– u u — — 25<br />

ED6<br />

110, 125 —– u u — — 25<br />

HED4<br />

15, 20, 30, 40, 50, 60, 70, 80, 90, 100 —– u u — — 42<br />

110, 125 —– u u — — 42<br />

FXD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 —– u u — — 35<br />

HFD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 —– u u — — 65<br />

a No increase in box height. Space is already built into<br />

C1 panel.<br />

b BL, BLH, HBL and BQD are horizontally mounted.<br />

All others vertically mounted.<br />

c Interchangeable trip breakers such as FD6 and HFD6<br />

cannot be back fed. Must be top feed only.<br />

d ED6/CED6 2-pole limited amps available (20-50A)<br />

11-100<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog<br />

Product Category PBSB