Panelboards<br />

Circuit Breaker / Column Type<br />

General<br />

11<br />

PANELBOARDS<br />

Type C1<br />

240 Volts AC Maximum<br />

250 Ampere Mains<br />

250 Ampere Maximum Branch<br />

UL Short Circuit Rating —<br />

200,000 IR Maximum<br />

Branch Breaker Symmetrical<br />

Interrupting Rating<br />

Based on Underwriters’ Test Procedure<br />

Type C2<br />

480Y/277 Volts AC Maximum<br />

250 Ampere Mains<br />

250 Ampere Maximum Branch<br />

UL Short Circuit Rating —<br />

100,000 IR Maximum<br />

Meets NEC wire bending requirement,<br />

section 312–6.<br />

Panelboards<br />

Listed by Underwriter’s Laboratories,<br />

Inc., under “Panelboards” File #E2269.<br />

Meets Federal Specification<br />

W–C375B/Gen.<br />

Service<br />

240 Volts Maximum. 1-Phase, 3-Wire, or<br />

3-Phase, 4-Wire.<br />

Panelboards Fronts and Doors<br />

Standard panelboards are furnished with<br />

trim with a flush door lock. All are factory<br />

assembled for ease of installation. Fronts<br />

are fabricated from code gauge steel and<br />

finished ANSI-61.<br />

Main Breakers C1<br />

BL, BLH and HBL frame breakers are<br />

mounted horizontally. All other frames<br />

are mounted vertically.<br />

Main Breakers C2<br />

BQD frame breakers are mounted<br />

horizontally. All other frames are<br />

mounted vertically.<br />

Boxes<br />

C1 — 7 5 ⁄8" wide, 5 3 ⁄4" deep.<br />

C2 — 8 1 ⁄2" wide, 5 3 ⁄4" deep.<br />

Branch Breaker Side Gutters<br />

Circuit<br />

Side Gutter<br />

Type Breaker (inches)<br />

C1 BL, BLH, HBL 3.505<br />

C2 BQD 3.5<br />

Weight–Approximate<br />

Total panelboard weight when filled with<br />

a normal quantity of breakers and<br />

accessories is:<br />

*About 3 lbs. per inch of box height.<br />

Gauge Steel Boxes<br />

Type Width Height Gauge Steel<br />

C1 7 5 ⁄8" 48", 73", 85" #14<br />

C2 8 1 ⁄2" 48", 73", 85" #14<br />

Fronts<br />

C1 7 5 ⁄8" 48", 73", 85"* #14<br />

C2 8 1 ⁄2" 48", 73", 85"* #14<br />

*Note: Feed thru lugs and subfeed breaker not available<br />

for this height.<br />

Main Breaker Connectors<br />

Ampere<br />

Rating Connectors suitable for Cu or Al<br />

100 (1) #14–1/0 AWG<br />

125 (1) #4–1/0 AWG<br />

225 (1) #6 AWG–300 kcmil<br />

250 (1) #4 AWG–350 kcmil Al<br />

(1) #6 AWG–350 kcmil Cu<br />

Main Lugs<br />

125 (1) #6 AWG–350 kcmil<br />

250 (1) #6 AWG–350 kcmil<br />

For inches / millimeters conversion,<br />

see Application Data section.<br />

a Connector ranges indicated do not apply to all main breaker types. Refer to<br />

molded case circuit breaker standard pressure wire connectors in the breaker<br />

section of this catalog for the wire ranges for a specific breaker frame.<br />

11-98<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog