3VA Breaker Configuration Information in Panelboards<br />

Revised on 02/29/20<br />

Internal and External Accessories for 400-600A 3VA Breakers<br />

Selection<br />

Description<br />

Accessories (continued)<br />

Quick<br />

reference<br />

code<br />

Voltage<br />

AC max<br />

or range<br />

Voltage<br />

DC max<br />

or range<br />

Accessory<br />

Catalog<br />

Number b<br />

Qty of<br />

slots in<br />

breaker<br />

req'd<br />

Max.<br />

Qty.<br />

per<br />

Brkr<br />

Position to install for<br />

3VA53/63 and<br />

3VA54/64 only<br />

Left side pocket Right side pocket<br />

Pocket reference # ==> 25 24 23 22 21 11 12 13 14 15<br />

11 PANELBOARDS<br />

Internal Accessories<br />

3VA63/64 (ETU) only<br />

Communications Module - 3VA63/64 COM060 n/a 24VDC 3VA9377-0TB10 4 1 X<br />

COM060-to-T-Connector<br />

ext. cable 0.4 m<br />

COM060-to-T-Connector<br />

ext. cable 0.8 m<br />

COM060-to-T n/a n/a 3VA9987-0TF20 n/a n/a<br />

COM060-to-T n/a n/a 3VA9987-0TF10 n/a n/a<br />

COM060 T-Connector (spare part) T-Connector n/a n/a 3VA9987-0TG10 n/a n/a<br />

External b Accessories<br />

and Field Kits<br />

#1-600 kcmil AL wire<br />

connector Kit c AL-lug n/a n/a 3VA9373-0JB13<br />

#1-600 kcmil CU wire<br />

connector Kit c CU-lug n/a n/a 3VA9373-0JD13<br />

2/0-600 kcmil AL 2 port<br />

connector Kit c AL-2lug n/a n/a 3VA9473-0JJ23<br />

2/0-600 kcmil CU 2 port<br />

connector Kit c CU-2lug n/a n/a 3VA9473-0JE23<br />

Compression Lugs<br />

(future offering - details tbd)<br />

TMTU<br />

or ETU<br />

600A max.<br />

tbd n/a n/a tbd n/a n/a<br />

Line or Load end as needed<br />

availability and<br />

usage locations tbd<br />

3VA53/63 or 54/64 PadLock Device tbd n/a n/a 3VA9338-0LB11 n/a n/a<br />

M0320 Motor Operator<br />

- 24-60V DC<br />

M0320 Motor Operator<br />

- 110-230V AC or 110-250V DC<br />

M0320 n/a 24-60V 3VA9277-0HA10 n/a 1 P4/P5 only<br />

M0320<br />

110-<br />

230V<br />

110-<br />

250V<br />

3VA9277-0HA20 n/a 1 P4/P5 only<br />

COM100 and COM800 modules and cables can be found on Communications Tables with ETU Breakers earlier in this section.<br />

a High capacity/power (HP) max. Amps load capacity is higher than standed module<br />

(.55A up to 6.0A) depends on Voltage and AC/DC requirements - see SpeedFax section<br />

7 or 3VA documentation for more information.<br />

b Many accessories available for the 3VA5 and 3VA6 breakers may not be suitable for use<br />

in Lighting Panelboards.<br />

– COMPAS allows options that are available. All accessories listed above can be used<br />

with Panelboards in general, but there will be exceptions."<br />

c Lugs are NOT supplied with loose breaker as standard - must order separately or configure<br />

in COMPAS to include lugs.<br />

– Factory assembled panels include AL lugs as standard, CU lugs are optional. These<br />

kits include 3 connectors and hardware.<br />

d Special electronically-compatible (el) variants are available for applications that require<br />

the auxiliary switch signals to be linked to low voltage systems.<br />

– May need special Mod in COMPAS.<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 11-69