3VA Breaker Configuration Information in Panelboards<br />

Revised on 02/29/20<br />

3VA54 Breakers – 2 Pole and 3 Pole<br />

Selection<br />

3VA54 Breakers<br />

3VA54 TMTU 600A max.<br />

n Part numbers shown are without Lugs.<br />

n Standard Lug kits used in Panelboards are shown in tables below.<br />

TMTU<br />

frame<br />

Type<br />

kA<br />

code<br />

Type<br />

ref<br />

MB<br />

code<br />

3VA54 MLAS M LAS VJ<br />

3VA54 HLAS H LAS VK<br />

3VA54 CLAS C LAS VL<br />

11 PANELBOARDS<br />

3VA54<br />

3-Pole Description<br />

3 Pole 3VA54 without connectors<br />

The default for Panelboard in COMPAS will be AL 2-conductor connectors:<br />

for AL order one 3VA9473-0JJ23 (accepts (2) 2/0-600kcmil AL/CU conductors)<br />

for CU order one 3VA9473-0JE23 (accepts (2) 2/0-600kcmil CU only conductors)<br />

Alternate single conductor lugs are available:<br />

for AL order one 3VA9473-0JB13 (accepts (1) #1 AWG-600kcmil AL/CU conductors)<br />

for CU order one 3VA9473-0JD13 (accepts (1) #1 AWG-600kcmil CU only conductors)<br />

UL Type Code ==> MLAS HLAS CLAS<br />

Panelboard MB codes ==> VJ VK VL<br />

Ratings 3-pole | 2-pole 3-pole | 2-pole 3-pole | 2-pole<br />

240 VAC kAIC rating ==> 85 | 85 100 | 100 200 a | 200 a<br />

480Y / 277 VAC kAIC rating ==> 35 | 35 65 | 65 100 | 100<br />

480 VAC kAIC rating ==> 35 | 35 65 | 65 100 | 100<br />

600Y / 347 VAC kAIC rating ==> 18 | 18 25 | 25 35 | 35<br />

600 VAC kAIC rating ==> 18 | 18 25 | 25 35 | 35<br />

250 VDC kAIC rating b ==> na | 50 na | 85 na | 100<br />

IC family @ 480 VAC ==> 35kA 65kA 100kA<br />

FTAM Trip included ==> TM230 TM230 TM230<br />

Catalog Number Catalog Number Catalog Number<br />

Amps Code Description<br />

3-pole 3-pole 3-pole<br />

450 45 3VA54 3P breaker w/TM230 3VA5445-5EC31-0AA0 3VA5445-6EC31-0AA0 3VA5445-7EC31-0AA0<br />

500 50 3VA54 3P breaker w/TM230 3VA5450-5EC31-0AA0 3VA5450-6EC31-0AA0 3VA5450-7EC31-0AA0<br />

600 60 3VA54 3P breaker w/TM230 3VA5460-5EC31-0AA0 3VA5460-6EC31-0AA0 3VA5460-7EC31-0AA0<br />

3VA54<br />

2-Pole Description<br />

2 Pole 3VA54 (in 3-Pole frame) without connectors<br />

The default for Panelboard in COMPAS will be AL 2-conductor connectors:<br />

for AL order one 3VA9473-0JJ23 (accepts (2) 2/0-600kcmil AL/CU conductors)<br />

for CU order one 3VA9473-0JE23 (accepts (2) 2/0-600kcmil CU only conductors)<br />

Alternate single conductor lugs are available:<br />

for AL order one 3VA9473-0JB13 (accepts (1) #1 AWG-600kcmil AL/CU conductors)<br />

for CU order one 3VA9473-0JD13 (accepts (1) #1 AWG-600kcmil CU only conductors)<br />

Catalog Number Catalog Number Catalog Number<br />

Amps Code Description<br />

2-pole 2-pole 2-pole<br />

450 45 3VA54 2P breaker w/TM230 3VA5445-5EC61-0AA0 3VA5445-6EC61-0AA0 3VA5445-7EC61-0AA0<br />

500 50 3VA54 2P breaker w/TM230 3VA5450-5EC61-0AA0 3VA5450-6EC61-0AA0 3VA5450-7EC61-0AA0<br />

600 60 3VA54 2P breaker w/TM230 3VA5460-5EC61-0AA0 3VA5460-6EC61-0AA0 3VA5460-7EC61-0AA0<br />

a Although some breakers have a kAIC rating above 100<br />

kAIC – many panels are limited to 100 kAIC or less.<br />

b DC Voltage panels are limited by various factors.<br />

These DC ratings apply to the Breaker only.<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 11-67