3VA Breaker Configuration Information in Panelboards<br />

Revised on 04/30/19<br />

Communications Modules<br />

Selection<br />

3VA6 Communications modules and related accessories for field installation a<br />

n COMPAS may not allow some of these kits for selection - Special Mod may be required.<br />

n Some items may not be installed in panels and may be shipped separate from Panels even if Configured in COMPAS<br />

Description<br />

Quick<br />

reference<br />

code<br />

Voltage<br />

AC max<br />

or range<br />

Voltage<br />

DC max<br />

or range<br />

Accessory<br />

Catalog<br />

Number b<br />

Qty of<br />

slots in<br />

breaker<br />

req'd<br />

Max.<br />

Qty.<br />

per<br />

Brkr<br />

Position to install for<br />

3VA61/62 and<br />

3VA63/64 only<br />

Pocket reference # ==> 25 24 23 22 21 11 12 13 14 15<br />

Group b Left side pocket Right side pocket<br />

COM Modules and Cables<br />

Communications Module - 3VA61/62 COM060 n/a 24VDC 3VA9177-0TB10 4 1 X<br />

Communications Module - 3VA63/64 COM060 n/a 24VDC 3VA9377-0TB10 4 1 X<br />

COM060-to-T-Connector ext. cable 0.4 m COM060-to-T n/a n/a 3VA9987-0TF20 n/a n/a External<br />

COM060-to-T-Connector ext. cable 0.8 m COM060-to-T n/a n/a 3VA9987-0TF10 n/a n/a External<br />

COM060 T-Connector (spare part) T-Connector n/a n/a 3VA9987-0TG10 n/a n/a External<br />

Terminal Resistor TermRes n/a n/a 3VA9987-0TE10 n/a n/a External<br />

COM800 Breaker Data Server = max 8 COM800 n/a n/a 3VA9977-0TA10 n/a n/a P4/P5 only and SWBD<br />

COM100 Breaker Data Server = max 1 COM100 n/a n/a 3VA9977-0TA20 n/a n/a P4/P5 only and SWBD<br />

COM100-800 extension cable 0.4 m COM ext Cable n/a n/a 3VA9987-0TC10 n/a n/a P4/P5 only and SWBD<br />

COM100-800 extension cable 1 m COM ext Cable n/a n/a 3VA9987-0TC20 n/a n/a P4/P5 only and SWBD<br />

COM100-800 extension cable 2 m COM ext Cable n/a n/a 3VA9987-0TC30 n/a n/a P4/P5 only and SWBD<br />

COM100-800 extension cable 4 m COM ext Cable n/a n/a 3VA9987-0TC40 n/a n/a P4/P5 only and SWBD<br />

7KM Pac Profibus DP Expansion Module 7KMAB n/a n/a 7KM9300-0AB01-0AA0 n/a n/a P4/P5 only and SWBD<br />

7KM PAC Switched Ethernet Profinet<br />

Expansion Module<br />

7KMAE n/a n/a 7KM9300-0AE01-0AA0 n/a n/a P4/P5 only and SWBD<br />

7KM PAC RS485 Modbus RTU Exp. Module 7KMAM n/a n/a 7KM9300-0AM00-0AA0 n/a n/a P4/P5 only and SWBD<br />

DAS, Displays and Related Components<br />

DAS Module "Maintenance Mode Box" MMB300 n/a n/a 3VA9977-0UF10 n/a n/a P4/P5 only and SWBD<br />

EFB300 - External function box EFB300 n/a n/a 3VA9977-0UA10 n/a n/a P4/P5 only and SWBD<br />

Display - DSP800 DSP800 n/a n/a 3VA9977-0TD10 n/a n/a P4/P5 only and SWBD<br />

1.5m Connecting cable for MMB300/EFB300 MMB/EFB 1.5m n/a n/a 3VA9987-UB10 n/a n/a P4/P5 only and SWBD<br />

3.0m Connecting cable for MMB300/EFB300 MMB/EFB 3.0m n/a n/a 3VA9987-UB20 n/a n/a P4/P5 only and SWBD<br />

Motor Operators<br />

M0320 Motor Operator - 24-60V DC M0320 n/a 24-60V 3VA9447-0HA10 n/a 1 P4/P5 only and SWBD<br />

M0320 Motor Operator - 110-230V AC or<br />

110-250V DC<br />

EFB300 n/a n/a 3VA9977-0UA10 n/a 1 P4/P5 only and SWBD<br />

Misc. External Components and Cables<br />

Neutral Current Transformer, In = 25-150A NCT150 n/a n/a 3VA9077-0NA10 n/a n/a P4/P5 only and SWBD<br />

Neutral Current Transformer, In= 160-350A NCT350 n/a n/a 3VA9177-0NA10 n/a n/a P4/P5 only and SWBD<br />

Neutral Current Transformer, In = 400-630A NCT630 n/a n/a 3VA9377-0NA10 n/a n/a P4/P5 only and SWBD<br />

TD300 - Activation & Trip Box TD300 n/a n/a 3VA9977-0MA10 n/a n/a P4/P5 only and SWBD<br />

TD500 - Test device TD500 n/a n/a 3VA9977-0MB10 n/a n/a P4/P5 only and SWBD<br />

TD500 External Power Supply TD500EX n/a n/a 3VA9987-0MX10 n/a n/a P4/P5 only and SWBD<br />

Cable to connect to TD500 from 3VA6 TD500CBL n/a n/a 3VA9977-0MY10 n/a n/a P4/P5 only and SWBD<br />

Special Connector Lugs with Control Wire Tap<br />

#14-3/0 AL wire connector Kit c w/con-tap AL-lug 3VA51 3VA9133-0JG11 125A TMTU only Line or Load end as needed<br />

#14-2/0 CU wire connector Kit c w/con-tap CU-lug 3VA51 3VA9133-0JK11 125A TMTU only Line or Load end as needed<br />

#6-350 kcmil AL wire conn. Kit c w/con-tap AL-lug 3VA52 3VA9233-0JG12 250A TMTU only Line or Load end as needed<br />

#6-350 kcmil CU wire conn. Kit c w/con-tap CU-lug 3VA52 3VA9233-0JK12 250A TMTU only Line or Load end as needed<br />

11 PANELBOARDS<br />

#14-1/0 AL wire connector Kit c w/con-tap AL-lug 3VA61 3VA9143-0JG11 150A ETU only Line or Load end as needed<br />

#6-350 kcmil AL wire conn. Kit c w/con-tap AL-lug 3VA61/62 3VA9243-0JG12 150/250A ETU only Line or Load end as needed<br />

#14-1/0 CU wire connector Kit c w/con-tap CU-lug 3VA61 3VA9143-0JK11 150A ETU only Line or Load end as needed<br />

#6-350 kcmil CU wire conn. Kit c w/con-tap CU-lug 3VA61/62 3VA9243-0JK12 150/250A ETU only Line or Load end as needed<br />

#1-600 kcmil AL wire conn. Kit c w/con-tap AL-lug 3VA53/63 3VA9373-0JG13 400A TMTU or ETU Line or Load end as needed<br />

#1-600 kcmil CU wire conn. Kit c w/con-tap CU-lug 3VA53/63 3VA9373-0JK13 400A TMTU or ETU Line or Load end as needed<br />

2/0-600 kcmil AL 2 port conn. Kit c w/con-tap AL-2lug 3VA54/64 3VA9473-0JC23 600A TMTU or ETU Line or Load end as needed<br />

a Some accessories may be "field install only" if not available in COMPAS, or not<br />

available for use in Panelboards<br />

b Many accessories available for the 3VA5 and 3VA6 breakers may not be suitable for use<br />

in Lighting Panelboards.<br />

- COMPAS allows only options that are available for factory assembly.<br />

Some accessories listed above may not be available for all Panelboard configurations.<br />

c Lugs are NOT supplied with loose breaker as standard - must order seperately or<br />

configure in COMPAS to include lugs.<br />

- Factory assembled panels include AL lugs as standard without control wire tap,<br />

CU lugs are optional. These kits include 3 connectors and hardware.<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 11-59