3VA Breaker Configuration Information in Panelboards<br />

P2 Lighting Panel General information<br />

Minimum enclosure size: 20" wide x 5.75" deep<br />

P2 Lighting Panelboard<br />

P2 interiors have flexible unit space setup for<br />

Multiple Branch Breaker Types and many different<br />

Main/Subfeed options.<br />

Neutral Cross<br />

Strap<br />

– positions for<br />

mounting<br />

Neutral lugs<br />

– many different<br />

configurations<br />

are used.<br />

Neutral Strips:<br />

1/0 max. cable size<br />

"Step lugs" and other<br />

varieties depending<br />

on the configuration<br />

– factory assembled<br />

only<br />

– optional field installable<br />

kits may be added in<br />

near future to include<br />

2/0 capability.<br />

Various Branch<br />

Breaker Strap<br />

Kits installed<br />

Field installable<br />

Neutral Extension<br />

can be added for<br />

AFCI/GFCI when<br />

needed due to<br />

short pigtails. It<br />

can be positioned<br />

anywhere along<br />

the base rail on<br />

either side.<br />

kit # BNKP2EX1<br />

BNKP2EX1<br />

Deadfront Supports<br />

Base Rails<br />

Main Space<br />

P2 Lighting Panel<br />

P2 Main Space can include:<br />

Main Lugs: 125A, 250A, 400A or 600A<br />

==> also Subfeed Lugs: 125A, 250A or 400A<br />

Main Breaker Types:<br />

n 100A max. BL/BQD or 125A max. xGB or ED<br />

n 250A max. FD series (horizontal mount)<br />

n 400A max. JD series (vertical mount)<br />

n 600A max. LD series (vertical mount)<br />

Future 3VA offering in development:<br />

n 250A max. 3VA52/62 (TMTU/ETU)<br />

(horiz. mount)<br />

n 400A max. 3VA53/63 (TMTU/ETU)<br />

(vertical mount)<br />

n 600A max. 3VA54/64 (TMTU/ETU)<br />

(vertical mount)<br />

(ETU = Electronic Trip Unit)<br />

(TMTU = Thermal Magnetic Trip Unit)<br />

P2 Branch Breakers — Small Frame:<br />

a) 100A max BL series<br />

b) 100A max BQD series<br />

c) Various AFCI/GFCI series<br />

d) 125A max ED series (480V delta capable)<br />

e) 125A max xGB series<br />

f) 125A max GB2 series<br />

(480V delta capable)<br />

Future 3VA offering in development:<br />

g) 125A max. 3VA41 TMTU<br />

(480V delta capable)<br />

P2 Branch Breakers — Large Frame<br />

(6 max.)<br />

1) 225A max QR series (total 225A/250A<br />

frame, four per panel limit)<br />

Future 3VA offering in development:<br />

2) 150A max 3VA61 ETU single mount<br />

3) 250A max 3VA52/62 TMTU/ETU<br />

single mount<br />

11 PANELBOARDS<br />

Bus Bars:<br />

250A - CU or AL<br />

400A - CU or AL<br />

600A - CU or AL<br />

Subfeed Space offering:<br />

Feed-thru Lugs:<br />

A) 125A, 250A, 400A, or 600A<br />

B) Surge Protection Devices (SPD)<br />

C Subfeed Breakers:<br />

– 250A max. FD twin mount vertical<br />

– 400A max. JD single mount vertical<br />

Future 3VA offering in development:<br />

– 400A max. 3VA53/63 (TMTU/ETU)<br />

(vertical single mount)<br />

Subfeed Space<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 11-53