12.01.2021 Views

Speedfax 2017

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Revised on 02/29/20<br />

3VA Breaker Configuration Information in Panelboards<br />

P1 Lighting Panel General information<br />

Minimum enclosure size: 20" wide x 5.75" deep<br />

11<br />

PANELBOARDS<br />

P1 Lighting Panelboard<br />

P1 interiors have unit space setup for either:<br />

A) BL/BQD type of breakers only<br />

or<br />

B) xGB and 3VA41 breakers only in same interior<br />

(no BL/BQD allowed)<br />

Deadfront Supports<br />

Neutral Riser<br />

Neutral Strips:<br />

1/0 max. factory<br />

assembled<br />

(BL/BQD)<br />

2/0 max.<br />

available for<br />

field install<br />

2/0 max. std.<br />

for xGB/3VA41<br />

A/C-Phase<br />

Connector<br />

- CU or AL<br />

Base Rails<br />

Main Space<br />

P1 Lighting Panel<br />

P1 Main Space can include:<br />

Main Lugs: 250A or 400A max<br />

Main Breaker Types:<br />

n 100A max BL/BQD & 125A max. xGB or ED<br />

n 125A max. 3VA41 (TMTU)<br />

(horiz. mount)<br />

n 225A max. QR series (horizontal mount)<br />

n 250A max. FD series (horizontal mount)<br />

n 400A max. 3VA53/63 (TMTU/ETU)<br />

(vertical mount)<br />

(ETU = Electronic Trip Unit)<br />

(TMTU = Thermal Magnetic Trip Unit)<br />

n 400A max. JD series (vertical mount)<br />

Future 3VA offering in development:<br />

n 250A max. 3VA52/62 (TMTU/ETU)<br />

(horiz. mount)<br />

P1 Branch Breakers — Small Frame only:<br />

a) 100A max BL series<br />

b) 100A max BQD series<br />

c) 125A max xGB or 3VA41<br />

series after 3/1/2020<br />

(Cannot Mix with BL/BQD)<br />

Note: always check dead front labels<br />

for allowed breakers<br />

B-Phase<br />

Connector<br />

- CU or AL<br />

Bus Bars:<br />

250A - CU or AL<br />

400A - CU or AL<br />

Subfeed Space<br />

P1 Subfeed Space offering:<br />

Feed-thru Lugs:<br />

A) 250A or 400A<br />

B) Surge Protection Devices (SPD)<br />

C) Subfeed Breakers:<br />

– 250A max. horizontal mounnt FD<br />

– 225A max. QR<br />

– 100A max. BL/BQD<br />

– 125A max. xGB/3VA41/ED<br />

Future 3VA offering in development:<br />

– 250A max. 3VA52 TMTU<br />

– 250A max. 3VA62 ETU<br />

– Horizontal mount only<br />

11-52<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog