Panelboards<br />

Circuit Breaker / Lighting and Distribution<br />

Revised on 04/30/19<br />

Selection<br />

Table P1-13 – Main Breaker Gutter Dimensions Inches (mm)<br />

Main<br />

Gutter Space<br />

Neutral Location<br />

to Endwall<br />

Breaker<br />

20” wide box 24” wide box 20” wide box<br />

BL, BLH, HBL 8.680 (220) 10.690 (272) 10.500 (267)<br />

BQD 7.880 (200) 9.880 (251) 10.500 (267)<br />

NGB, HGB, LGB 7.770 (197) 9.770 (248) 10.500 (267)<br />

ED4, ED6, HED4 6.125 (156) 8.125 (206) 10.500 (267)<br />

QR2, QRH2, HQR2, HQR2H 6.500 (165) 8.500 (216) 10.500 (267)<br />

FD6, FXD6, HFD6, HFXD6 5.250 (133) 7.250 (184) 10.500 (267)<br />

JD6, JXD6 15.000 (381) 15.000 (381) 26.500 (674)<br />

<br />

JD frame mounted vertically.<br />

For Revised P1 with Back-fed Main option, use Side Gutter<br />

Wiring Spec Table P1-15.<br />

<br />

These dimensions are for Revised P1 only. See Original P1 cut sheets for valid<br />

dimensions if needed (P1 production prior to January 2015).<br />

Table P1-14 – Main Lug End Gutter Dimensions Inches (mm)<br />

Amp End Gutter<br />

Neutral Location - to Endwall<br />

Rating 20” wide box 24” wide box 20” wide box 24” wide box<br />

125 9.500 (242) 9.500 (242) 10.500 (267) 10.500 (267)<br />

250 9.500 (242) 9.500 (242) 10.500 (267) 10.500 (267)<br />

400 25.500 (648) 25.500 (648) 26.750 (680) 26.750 (680)<br />

NOTE: Feed-thru lug and neutral wire bending space is 15.000” and 16.250” respectively<br />

on 400A panel.<br />

Table P1-15 – Side Gutter Wiring<br />

Space Inches (mm) (Fig P1-1) Fig P1-1<br />

Reference<br />

Letter<br />

Panel<br />

Width 20”<br />

Panel<br />

Width 24”<br />

Optional<br />

A 6.375 (167) 8.375 (213)<br />

B 5.500 (140) 7.500 (191)<br />

C 5.000 (127) 7.000 (178)<br />

D 6.125 (156) 8.125 (206)<br />

E 6.500 (165) 8.500 (216)<br />

F 5.250 (133) 7.250 (184)<br />

<br />

Subfeed mounting limit 1 per panel.<br />

Panel Width<br />

20 in. (508 mm)<br />

For all Revised P1 panels using BL/BQD or xGB breakers as<br />

mains in back-fed position, use this chart for wiring space.<br />

Miscellaneous Parts and Accessories<br />

Catalog # Description<br />

BK1<br />

Bonding Kit for 400A max. Original P1 Panels<br />

BK1A<br />

Bonding Kit for 400A max. Revised P1 Panels<br />

BK2 Bonding kit for S1/S2 400 & 600<br />

BK3<br />

Bonding kit<br />

IMK1<br />

Interior Adjusting Kit<br />

LPDC01 Directory Card (Pack of 10; ref. 12-1110-01)<br />

LPDC02 Directory Card Holder (Pack of 10; ref. 11-1824-01)<br />

MCHK<br />

Metal Card Holder Kit<br />

NBK03<br />

Number Strips 1–42. Stick-on type (P1 Panel only)<br />

NBK04<br />

Number Strips 43–84. Stick-on type;<br />

Use w/ P1 series Panels<br />

NBK05<br />

Number Strips 85–126. Stick-on type;<br />

Use w/ P1 series Panels<br />

NBK06<br />

Number Strips 127–168. Stick-on type;<br />

Use w/ P1 series Panels<br />

EGK<br />

AL Ground Bus 44 Connections<br />

ECGK<br />

CU Ground Bus 44 Connections<br />

IGK<br />

Insulated AL Ground Bus<br />

ICGK<br />

Insulated CU Ground Bus<br />

SEBKRP1V1 c FD, QJ, QR Service Entrance Barrier Kit<br />

(Revised P1)<br />

SEBKRP1V2 c ED Service Entrance Barrier Kit (Revised P1)<br />

SEBKRP1V3 c BL/BQD Service Entrance Barrier Kit<br />

(Revised P1) back-fed<br />

SEBKRP1V4 c xGB Service Entrance Barrier Kit<br />

(Revised P1) back-fed<br />

SEBKRP1V5 c BL/BQD/xGB Service Entrance Barrier Kit<br />

(RP1 in main space)<br />

SEBKP1P2P3V1 c JD, LD Service Entrance Barrier Kit<br />

(RP1, P1, P2, P3)<br />

EWK1<br />

End Wall Kit with Knockouts (20" W x 5.75" DP)<br />

EWK2<br />

End Wall Kit with Knockouts (24" W x 7.75" DP)<br />

EBF1<br />

NEB/HEB Filler Plate<br />

P1SCRWS Package of 42 breaker mounting screws for P1<br />

DFFP1<br />

1" Branch circuit filler plate (used for BL/BQD/<br />

xGB/xGB2/ED blank positions) (suitable for<br />

replacing QF3 in P1 thru P5 Panelboards and<br />

Switchboards)<br />

P1CONBPHCU Connector kit – 6 pcs. B-phase Copper<br />

P1CONBPHAL Connector kit – 6 pcs. B-phase Aluminum<br />

P1CONACPHCU d Connector kit – 6 pcs. A or C-phase Copper<br />

MBKQRFK<br />

P1/Revised P1 Filler for 1PH/3PH QR.<br />

Horizontal mount only.<br />

ANSI/NEMA<br />

PB 1.1-2013<br />

General Instructions for Proper Installation,<br />

Operation, and Maintenance of Panelboards<br />

Rated 600 Volts or Less (O&M Manual) <br />

Replacement parts only.<br />

b PDF can be downloaded (at no cost) and printed at:<br />

www.nema.org/standards/pages/Panelboards.aspx<br />

c Factory installed and Field installable Service Entrance<br />

Barrier kits are now available as required by UL67. (In<br />

COMPAS, you must select Service Entrance Required.)<br />

d Use for both CU + AL bus interiors.<br />

11 PANELBOARDS<br />

Feed-Thru (FT) Non-Feed-Thru (NFT) Example of Back-fed xGB Main breaker installed<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 11-23