Speedfax 2017
Distribution Dry Type Transformers Single Phase Revised on 12/31/19 Selection kVA Catalog Number Taps a Temperature Rise 600 Volts Primary, 120/240 Volts Secondary Insulation Mounting Type be Drip Shield Provided c Enclosure Style d Optional Modifications 3 1G1R003 R 135° C 180° C Wall No Encapsulated – NEMA 3R 1, 2, 4 5 1G1R005 R 135° C 180° C Wall No 1, 2, 4 7.5 1G1R007 R 135° C 180° C Wall No 1, 2, 4 10 1G1R010 R 135° C 180° C Wall No 1, 2, 4 15 1G1R015 R 135° C 180° C Wall No 1, 2, 4 25 1G1R025 R 135° C 180° C Wall No 1, 2, 4 25 1G1T025TP1 Y g T h 150° C 220° C Floor & Wall Yes Ventilated – NEMA 3R 1, 2, 3 37.5 1G1T037TP1 Y g T h 150° C 220° C Floor & Wall Yes 1, 2, 3 50 1G1T050TP1 Y g T h 150° C 220° C Floor & Wall Yes 1, 2, 3 75 1G1T075TP1 Y g T h 150° C 220° C Floor Yes Ventilated – NEMA 3R 1, 2, 3 100 1G1T100TP1 Y g T h 150° C 220° C Floor Yes 1, 2, 3 167 1G1T167TP1 Y g T h 150° C 220° C Floor Yes 1, 2, 3 Overseas Model 190/200/208/220 x 380/400/416/440 Volts Primary, 120/240 Volts Secondary—1Ø, 50/60 Hz 1 1H1N001 N 95° C 130° C Wall No Encapsulated – NEMA 3R 2, 3 2 1H1N002 i N 135° C 180° C Wall No 2, 3 3 1H1N003 i N 135° C 180° C Wall No 2, 3 5 1H1N005 i N 135° C 180° C Wall No 2, 3 7.5 1H1N007 N 135° C 180° C Wall No 2, 3 10 1H1N010 N 135° C 180° C Wall No 2, 3 15 1H1N015 N 135° C 180° C Wall No 2, 3 25 1H1N025 N 135° C 180° C Wall No 2, 3 Overseas Model 190/208/220/240 x 380/416/440/480 Volts Primary, 120/240 Volts Secondary—1Ø, 50/60 Hz 1 1X1N001 N 95° C 130° C Wall No Encapsulated – NEMA 3R 2, 3 2 1X1N002 i N 135° C 180° C Wall No 2, 3 3 1X1N003 i N 135° C 180° C Wall No 2, 3 5 1X1N005 i N 135° C 180° C Wall No 2, 3 7.5 1X1N007 N 135° C 180° C Wall No 2, 3 10 1X1N010 N 135° C 180° C Wall No 2, 3 15 1X1N015 N 135° C 180° C Wall No 2, 3 25 1X1N025 N 135° C 180° C Wall No 2, 3 Overseas Model 190/200/208/220 x 380/400/416/440 Volts Primary, 110/220 Volts Secondary—1Ø, 50/60 Hz 1 1H8N001 N 95° C 130° C Wall No Encapsulated – NEMA 3R 2, 3 2 1H8N002 i N 135° C 180° C Wall No 2, 3 3 1H8N003 i N 135° C 180° C Wall No 2, 3 5 1H8N005 i N 135° C 180° C Wall No 2, 3 7.5 1H8N007 N 135° C 180° C Wall No 2, 3 8 TRANSFORMERS Optional Modifications Table (Contact Sales office for List Price) Optional (commonly used) Modifications 1a. 115° C Rise F 1b. 80° C Rise B 2. Electrostatic Shield ES 3. Copper Windings C 4. Wall Mounting Brackets1 W 5. Drip Shields DS Catalog Suffix Code Taps Description None N 2–5% FCBN R 2–5% (1 FCAN, 1 FCBN) S 2–2.5% FCBN U 6–2.5% (2 FCAN, 4 FCBN) Y Designation a Actual taps may vary based on volts/turn ratio. b Wall designations for units having standard features. c For outdoor application. Ventilated transformers requiring drip shields/weathershields are UL listed for outdoor use. All are NEMA 3R rated. d Encapsulated transformers are UL listed for indoor/ outdoor use. NEMA 3R rated. e Items marked floor and wall can be wall mounted with optional wall bracket. f See table on page 8-8 for available kits. g Series H Tap Standard. h Series J Tap Standard. i Available with CE mark. 8-10 Siemens Industry, Inc. SPEEDFAX Product Catalog Product Category XFMR
Distribution Dry Type Transformers Three Phase Revised on 05/31/18 Selection kVA Catalog Number Taps a Temperature Rise Insulation Mounting Type beh Drip Shield Provided c Enclosure Style d Optional Modifications 480 Volts ∆ Primary, 240 Volts ∆ Secondary With 120 Volt Tap On B Phase 15 3F1Y015D16 Y 150° C 220° C Floor & Wall Yes Ventilated – NEMA 3R 1, 2, 3, 4 30 3F1Y030D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4 45 3F1Y045D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4 75 3F1Y075D16 Y 150° C 220° C Floor Yes Ventilated – NEMA 3R 1, 2, 3, 4 112.5 3F1Y112D16 Y 150° C 220° C Floor Yes 1, 2, 3, 4 150 3F1Y150D16 Y 150° C 220° C Floor Yes 1, 2, 3 225 3F1Y225D16 Y 150° C 220° C Floor Yes 1, 2, 3 300 3F1Y300D16 Y 150° C 220° C Floor Yes 1, 2, 3 500 3F1T500D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3 750 3F1T750D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3 480 Volts ∆ Primary, 240 Volts ∆ Secondary 3 3F2R003 f R 135° C 180° C Wall No Encapsulated – NEMA 3R 1, 2, 3 6 3F2R006 f R 135° C 180° C Wall No 1, 2, 3 9 3F2R009 f R 135° C 180° C Wall No 1, 2, 3 15 3F2R015 f R 135° C 180° C Wall No 1, 2, 3 480 Volts ∆ Primary, 208Y/120 Volts Secondary 3 3F3R003 R 135° C 180° C Wall No Encapsulated – NEMA 3R 1, 2, 3 6 3F3R006 R 135° C 180° C Wall No 1, 2, 3 9 3F3R009 R 135° C 180° C Wall No 1, 2, 3 15 3F3R015 R 135° C 180° C Wall No 1, 2, 3 15 3F3Y015D16 Y 150° C 220° C Floor & Wall Yes Ventilated – NEMA 3R 1, 2, 3, 4, 6 30 3F3Y030D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4, 6 45 3F3Y045D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4, 6 75 3F3Y075D16 Y 150° C 220° C Floor & Wall Yes Ventilated – NEMA 3R 1, 2, 3, 4, 6 112.5 3F3Y112D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6 150 3F3Y150D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6 225 3F3Y225D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6 300 3F3Y300D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6 500 3F3T500D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3, 6 750 3F3T750D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3, 6 1000 3F3T000D16 T 150° C 220° C Floor Yes 1, 2, 3, 6 kVA Catalog Temperature Number Taps a Rise Optional Modifications Table (Contact Sales office for List Price) Optional (commonly used) Catalog Modifications Suffix Code 1a. 115°C Rise F 1b. 80°C Rise B 2. Electrostatic Shield ES 3. Copper Windings C 4. Wall Mounting Brackets1 W 6. Low noise — XdB below std. LNX Insulation Mounting Type Drip Shield Required Taps Description Designation None N 2–5% FCBN R 2–5% (1 FCAN, 1 FCBN) S 2–2.5% FCBN U 6–2.5% (2 FCAN, 4 FCBN) Y Optional Modifications Avg. Sound Level Totally Enclosed Transformers, Indoor/Outdoor Use 480 Volts ∆ Primary, 208Y/120 Volts Secondary g 15 3F3Y015TE Y 150° C 220° C Floor No 1, 2, 3 50dB 30 3F3Y030TE Y 150° C 220° C Floor No 1, 2, 3 50dB 45 3F3Y045TE Y 150° C 220° C Floor No 1, 2, 3 50dB 75 3F3Y075TE Y 150° C 220° C Floor No 1, 2, 3 55dB 112.5 3F3Y112TE Y 150° C 220° C Floor No 1, 2, 3 55dB 150 3F3Y150TE Y 150° C 220° C Floor No 1, 2, 3 55dB1 225 3F3Y225TE Y 150° C 220° C Floor No 1, 2, 3 57dB1 300 3F3Y300TE Y 150° C 220° C Floor No 1a, 2, 3 57dB1 480 Volts ∆ Primary, 240 Volts ∆ Secondary with 120V Lighting Tap on B Phase g 15 3F1Y015TE Y 150° C 220° C Floor No 1, 2, 3 50dB 30 3F1Y030TE Y 150° C 220° C Floor No 1, 2, 3 50dB 45 3F1Y045TE Y 150° C 220° C Floor No 1, 2, 3 50dB 75 3F1Y075TE Y 150° C 220° C Floor No 1, 2, 3 55dB 112.5 3F1Y112TE Y 150° C 220° C Floor No 1, 2, 3 55dB 150 3F1Y150TE Y 150° C 220° C Floor No 1, 2, 3 55dB 225 3F1Y225TE Y 150° C 220° C Floor No 1, 2, 3 57dB 300 3F1Y300TE Y 150° C 220° C Floor No 1a, 2, 3 57dB 8 TRANSFORMERS a Actual taps may vary based on volts/turn ratio. b Wall designations for units having standard features. c Ventilated transformers with drip shields are UL listed for outdoor use. NEMA 3R rated. d Encapsulated transformers are UL listed for indoor/ outdoor use. NEMA 3R rated. e See table on page 8-8 for available kits. f 240 volt secondary (3F2) is available in 3-phase 3 to 15kVA only. g TE units will have inrush equal to 2 sizes larger than rated kVA. h Items marked floor and wall can be wall mounted with optional wall bracket that may be identified with “W” suffix on catalog number. i Wall mounting for 150˚C temperature rise. j Series H Tap Standard. k Series J Tap Standard. Product Category XFMR Siemens Industry, Inc. SPEEDFAX Product Catalog 8-11
- Page 559 and 560: VL Circuit Breakers PG 1600A Frame,
- Page 561 and 562: VL Circuit Breakers Internal Access
- Page 563 and 564: VL Circuit Breakers Motor Circuit P
- Page 565 and 566: External Accessories Selection 7 MO
- Page 567 and 568: For MG Frame For NG to PG Frame 800
- Page 569 and 570: For MG Frame For NG Frame For PG Fr
- Page 571 and 572: Revised on 11/30/19 For JG to LG Fr
- Page 573 and 574: For JG Frame For LG Frame For MG Fr
- Page 575 and 576: Revised on 11/30/19 For JG Frame Fo
- Page 577 and 578: Revised on 11/30/19 For JG Frame F
- Page 579 and 580: VL Circuit Breakers Selection Suffi
- Page 581 and 582: Technical Data Revised on 05/31/18
- Page 583 and 584: Technical Data Unusual Operating Co
- Page 585 and 586: Molded Case Circuit Breakers Series
- Page 587 and 588: Molded Case Circuit Breakers Series
- Page 589 and 590: Molded Case Circuit Breakers Series
- Page 591 and 592: Molded Case Circuit Breakers Series
- Page 593 and 594: Molded Case Circuit Breakers Series
- Page 595 and 596: Molded Case Circuit Breakers IEC 94
- Page 597 and 598: Molded Case Circuit Breakers Supers
- Page 599 and 600: Molded Case Circuit Breakers Supers
- Page 601 and 602: Transformers SPEEDFAX TM Section Se
- Page 603 and 604: Distribution Dry Type Transformers
- Page 605 and 606: Distribution Dry Type Transformers
- Page 607 and 608: Distribution Dry Type Transformers
- Page 609: Distribution Dry Type Transformers
- Page 613 and 614: Distribution Dry Type Transformers
- Page 615 and 616: Distribution Dry Type Transformers
- Page 617 and 618: Distribution Dry Type Transformers
- Page 619 and 620: Transformers Sentron Harmonic Mitig
- Page 621 and 622: Warehouse Stock Transformers Wareho
- Page 623 and 624: Warehouse Stock Transformers Buck-B
- Page 625 and 626: Buck-Boost Transformers Single Phas
- Page 627 and 628: Warehouse Stock Transformers Access
- Page 629 and 630: Digital Power & Thermal Monitoring
- Page 631 and 632: Power Distribution Solutions Revise
- Page 633 and 634: Power Distribution Solutions Revise
- Page 635 and 636: Power Distribution Solutions Revise
- Page 637 and 638: Power Distribution Solutions Revise
- Page 639 and 640: Power Distribution Solutions Revise
- Page 641 and 642: Power Distribution Solutions Revise
- Page 643 and 644: Power Distribution Solutions Embedd
- Page 645 and 646: Power Distribution Solutions Embedd
- Page 647 and 648: Power Distribution Solutions Embedd
- Page 649 and 650: Power Distribution Solutions Enclos
- Page 651 and 652: Power Distribution Solutions MD Ser
- Page 653 and 654: Power Distribution Solutions Revise
- Page 655 and 656: Power Distribution Solutions SEM3T
- Page 657 and 658: Power SEM3T | Selection Distributio
- Page 659 and 660: Power Distribution Solutions SEM3T
Distribution Dry Type Transformers<br />
Three Phase<br />
Revised on 05/31/18<br />
Selection<br />
kVA<br />
Catalog<br />
Number Taps a Temperature<br />
Rise<br />
Insulation<br />
Mounting<br />
Type beh<br />
Drip Shield<br />
Provided c<br />
Enclosure<br />
Style d<br />
Optional<br />
Modifications<br />
480 Volts ∆ Primary, 240 Volts ∆ Secondary With 120 Volt Tap On B Phase <br />
15 3F1Y015D16 Y 150° C 220° C Floor & Wall Yes Ventilated – NEMA 3R 1, 2, 3, 4<br />
30 3F1Y030D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4<br />
45 3F1Y045D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4<br />
75 3F1Y075D16 Y 150° C 220° C Floor Yes Ventilated – NEMA 3R 1, 2, 3, 4<br />
112.5 3F1Y112D16 Y 150° C 220° C Floor Yes 1, 2, 3, 4<br />
150 3F1Y150D16 Y 150° C 220° C Floor Yes 1, 2, 3<br />
225 3F1Y225D16 Y 150° C 220° C Floor Yes 1, 2, 3<br />
300 3F1Y300D16 Y 150° C 220° C Floor Yes 1, 2, 3<br />
500 3F1T500D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3<br />
750 3F1T750D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3<br />
480 Volts ∆ Primary, 240 Volts ∆ Secondary<br />
3 3F2R003 f R 135° C 180° C Wall No Encapsulated – NEMA 3R 1, 2, 3<br />
6 3F2R006 f R 135° C 180° C Wall No 1, 2, 3<br />
9 3F2R009 f R 135° C 180° C Wall No 1, 2, 3<br />
15 3F2R015 f R 135° C 180° C Wall No 1, 2, 3<br />
480 Volts ∆ Primary, 208Y/120 Volts Secondary<br />
3 3F3R003 R 135° C 180° C Wall No Encapsulated – NEMA 3R 1, 2, 3<br />
6 3F3R006 R 135° C 180° C Wall No 1, 2, 3<br />
9 3F3R009 R 135° C 180° C Wall No 1, 2, 3<br />
15 3F3R015 R 135° C 180° C Wall No 1, 2, 3<br />
15 3F3Y015D16 Y 150° C 220° C Floor & Wall Yes Ventilated – NEMA 3R 1, 2, 3, 4, 6<br />
30 3F3Y030D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4, 6<br />
45 3F3Y045D16 Y 150° C 220° C Floor & Wall Yes 1, 2, 3, 4, 6<br />
75 3F3Y075D16 Y 150° C 220° C Floor & Wall Yes Ventilated – NEMA 3R 1, 2, 3, 4, 6<br />
112.5 3F3Y112D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6<br />
150 3F3Y150D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6<br />
225 3F3Y225D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6<br />
300 3F3Y300D16 Y 150° C 220° C Floor Yes 1, 2, 3, 6<br />
500 3F3T500D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3, 6<br />
750 3F3T750D16 Y j , T 150° C 220° C Floor Yes 1, 2, 3, 6<br />
1000 3F3T000D16 T 150° C 220° C Floor Yes 1, 2, 3, 6<br />
kVA<br />
Catalog<br />
Temperature<br />
Number Taps a Rise<br />
Optional Modifications Table (Contact Sales office for List Price)<br />
Optional (commonly used)<br />
Catalog<br />
Modifications<br />
Suffix Code<br />
1a. 115°C Rise F<br />
1b. 80°C Rise B<br />
2. Electrostatic Shield ES<br />
3. Copper Windings C<br />
4. Wall Mounting Brackets1 W<br />
6. Low noise — XdB below std. LNX<br />
Insulation<br />
Mounting<br />
Type<br />
Drip Shield<br />
Required<br />
Taps<br />
Description<br />
Designation<br />
None<br />
N<br />
2–5% FCBN R<br />
2–5% (1 FCAN, 1 FCBN) S<br />
2–2.5% FCBN U<br />
6–2.5% (2 FCAN, 4 FCBN) Y<br />
Optional<br />
Modifications<br />
Avg. Sound<br />
Level<br />
Totally Enclosed Transformers, Indoor/Outdoor Use 480 Volts ∆ Primary, 208Y/120 Volts Secondary g<br />
15 3F3Y015TE Y 150° C 220° C Floor No 1, 2, 3 50dB<br />
30 3F3Y030TE Y 150° C 220° C Floor No 1, 2, 3 50dB<br />
45 3F3Y045TE Y 150° C 220° C Floor No 1, 2, 3 50dB<br />
75 3F3Y075TE Y 150° C 220° C Floor No 1, 2, 3 55dB<br />
112.5 3F3Y112TE Y 150° C 220° C Floor No 1, 2, 3 55dB<br />
150 3F3Y150TE Y 150° C 220° C Floor No 1, 2, 3 55dB1<br />
225 3F3Y225TE Y 150° C 220° C Floor No 1, 2, 3 57dB1<br />
300 3F3Y300TE Y 150° C 220° C Floor No 1a, 2, 3 57dB1<br />
480 Volts ∆ Primary, 240 Volts ∆ Secondary with 120V Lighting Tap on B Phase g<br />
15 3F1Y015TE Y 150° C 220° C Floor No 1, 2, 3 50dB<br />
30 3F1Y030TE Y 150° C 220° C Floor No 1, 2, 3 50dB<br />
45 3F1Y045TE Y 150° C 220° C Floor No 1, 2, 3 50dB<br />
75 3F1Y075TE Y 150° C 220° C Floor No 1, 2, 3 55dB<br />
112.5 3F1Y112TE Y 150° C 220° C Floor No 1, 2, 3 55dB<br />
150 3F1Y150TE Y 150° C 220° C Floor No 1, 2, 3 55dB<br />
225 3F1Y225TE Y 150° C 220° C Floor No 1, 2, 3 57dB<br />
300 3F1Y300TE Y 150° C 220° C Floor No 1a, 2, 3 57dB<br />
8 TRANSFORMERS<br />
a Actual taps may vary based on volts/turn ratio.<br />
b Wall designations for units having standard features.<br />
c Ventilated transformers with drip shields are UL listed<br />
for outdoor use. NEMA 3R rated.<br />
d Encapsulated transformers are UL listed for indoor/<br />
outdoor use. NEMA 3R rated.<br />
e See table on page 8-8 for available kits.<br />
f 240 volt secondary (3F2) is available in 3-phase 3 to<br />
15kVA only.<br />
g TE units will have inrush equal to 2 sizes<br />
larger than rated kVA.<br />
h Items marked floor and wall can be wall mounted<br />
with optional wall bracket that may be identified with<br />
“W” suffix on catalog number.<br />
i Wall mounting for 150˚C temperature rise.<br />
j Series H Tap Standard.<br />
k Series J Tap Standard.<br />
Product Category XFMR<br />
Siemens Industry, Inc. SPEEDFAX Product Catalog 8-11