Distribution Dry Type Transformers<br />

Catalog Number Coding System for Transformers<br />

Revised on 05/31/18<br />

Selection<br />

Seismic Rated:<br />

All others not listed below are not seismic rated<br />

(contact customer support for Wall Mounting Ratings if needed)<br />

Encapsulated Ventilated Non Ventilated<br />

Phase Series J Series J Series H Series J <br />

1 1-25kVA<br />

(Wall Mounted)<br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

1-250 kVA<br />

(Floor Mounted)<br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

15-167kVA<br />

(Floor Mounted Only)<br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

1-250kVA<br />

(Floor Mounted Only)<br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

3 3-75kVA<br />

(Floor Mounted)<br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

1-1000kVA<br />

(Floor Mounted)<br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

15-750kVA<br />

(Floor Mounted Only) <br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

1-500kVA<br />

(Floor Mounted Only)<br />

S DS =2.00g ; z/h = 1.00 ; I p = 1.5<br />

DOE 2016 3 Phase Ventilated<br />

3 NA 1-1000kVA<br />

(Floor Mounted)<br />

Seismic labels are standard up to 750kVA with 150C temperature rise.<br />

Series J Results are filed with OSHPD per OSP-0109-10.<br />

Series H results are filed with OSHPD per OSP-0136-10.<br />

15-750kVA<br />

(Floor Mounted Only)<br />

Seismic Qualified according to:<br />

• International Building Code (IBC) 2012<br />

• American Society of Civil Engineers (ASCE) 7-10<br />

NA<br />

8<br />

TRANSFORMERS<br />

Wall Mounting Brackets and Drip Shields<br />

1 Phase Dry Type Wall Brackets/Drip Shields<br />

Wall Mounting Brackets (W) Drip Shields (DS)<br />

kVA<br />

Series J Series H Series J Series H<br />

0.25-25 Encapsulated Wall Mount only NA NA NA<br />

All items below are Ventilated<br />

15, 25 Optional** Standard Standard Standard<br />

37.5 Optional** See Note 1 Standard Standard<br />

50 Optional** See Note 1 Standard Standard<br />

75 NA See Note 1 Standard Standard<br />

100-500 NA Standard Standard<br />

3 Phase Dry Type Ventilated DOE 2016 Wall Brackets/Drip Shields<br />

Wall Mounting Brackets (W) Drip Shields (DS)<br />

kVA<br />

Series J Series H Series J Series H<br />

15, 30 Optional** Standard Standard Standard<br />

45 Optional** See Note 1 Standard Standard<br />

75 See Note 2 See Note 1 Standard Standard<br />

112.5-1000 N/A See Note 1 Standard Standard<br />

3 Phase Dry Type Encapsulated<br />

Wall Mounting Brackets (W) Drip Shields (DS)<br />

kVA<br />

Series J Series H Series J Series H<br />

3-15 Standard Standard N/A N/A<br />

**For DOE 2016 and 1-Phase ventilated, cost of transformer will not include wall brackets.<br />

Wall brackets will be an additional charge.<br />

Standard Terminal Lug Offerings <br />

(Primary and Secondary) for Ventilated Transformers (150 Degree Rise - Series J only - Without a K rating)<br />

1-Phase<br />

3-Phase<br />

kVA 120/240V 208V 480V 600V kVA 120/240V 208V 480V 600V<br />

0-15 Contact customer support 0-15 Contact customer support<br />

15 #2/0-6 #14-2 #14-2 #14-2 15 #14-2 #14-2 #14-2 #14-2<br />

25 250MCM-6 250MCM-6 #14-2 #14-2 30 #2/0-6 #2/0-6 #14-2 #14-2<br />

37.5 350MCM-6 350MCM-6 #14-2 #14-2 45 250MCM-6 250MCM-6 #14-2 #14-2<br />

50 600MCM-2 600MCM-2 #2/0-6 #2/0-6 75 600MCM-2 350MCM-6 #2/0-6 #2/0-6<br />

>50 Contact customer support >75 Contact customer support<br />

Values listed above are for standard configurations.<br />

There may be slight variations depending on requirements.<br />

Contact Customer Support for special requirements<br />

For Series H, see chart in Series H Addendum - Page H-16. Lug sizes are not available except on cutsheets.<br />

Contact Customer Support for special requirements.<br />

1. Standard with DH1 and DH2 enclosures.<br />

For DH3 enclosure, Series H transformers<br />

1000 lbs or less can be wall mounted with<br />

kit p/n TWB75H. The DH3 designation is<br />

found on the lower left corner of the Front<br />

View Outline on the transformer drawing.<br />

2. Optional except with copper windings or<br />

options B, K13, K20. See table page 8-27.<br />

8-8<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog