Molded Case Circuit Breakers<br />

Series Connected Short Circuit Ratings<br />

Revised on 03/25/17<br />

General<br />

7<br />

MOLDED CASE<br />

CIRCUIT BREAKERS<br />

The term “Series Connected Short<br />

Circuit Rating” refers to the application of<br />

series circuit breakers in a combination<br />

that allows downstream breakers to have<br />

lower individual interrupting ratings than<br />

the available fault current.<br />

240V Breaker Series Ratings<br />

Series<br />

Rating<br />

kAIR<br />

22000<br />

Main Breaker<br />

Branch Breaker<br />

Type<br />

Max.<br />

Amperes Type<br />

QPH, BQH,<br />

BLH<br />

QPMH<br />

QJH2<br />

QPPH<br />

QRH2<br />

42000 QJ2H<br />

65000<br />

HQP, HBQ,<br />

HBL<br />

70 (1P)<br />

125 (2P)<br />

100 (3P)<br />

QP, BQ, BL<br />

This is permitted as long as the series<br />

combination has been tested and certified<br />

by UL.<br />

The tables on these pages list specific<br />

main and branch breaker combinations<br />

that may be used for the short circuit<br />

interrupting ratings shown.<br />

Number<br />

of Poles Voltage Amperes<br />

1<br />

2<br />

3<br />

120/240<br />

240<br />

240<br />

15-70<br />

15-125<br />

15-100<br />

QE, BLE, QPF, BLF 2 120/240 15-60<br />

QE, BLE, BE, QPF,<br />

BQF, BLF QPF2, BLF2<br />

1 240 15-30<br />

QT 1, 2 120/240 15-40<br />

QG, BG, BLG 1, 2 120/240 15-30<br />

BAF, QAF, QAF2, BAF2,<br />

QFGA2, BFGA2<br />

1 120 15-20<br />

BAF, QAF 2 120/240 15-20<br />

QP 1<br />

120 15-25<br />

120/240 35-70<br />

2 120/240 15-25<br />

35-125<br />

200 (2P)<br />

1<br />

QE, QPF<br />

120/240 15-30<br />

2<br />

15-60<br />

QAF, BAF<br />

1 120 15-20<br />

2 120/240 15-20<br />

QT 2 120/240 15-30<br />

1 120/240 15-70<br />

QP, BQ, BL<br />

2 240 15-125<br />

3 240 60-100<br />

QPF, BQF, BLF, BG, BLG<br />

1 120 15-30<br />

QE, BE, BLE, QPF2, BLF2<br />

225<br />

QPF, BLF, BG, BLG, QE<br />

(2P, 3P)<br />

2 120/240 15-60<br />

BE, BLE<br />

BAF, QAF, QAF2, BAF2 1 120 15-20<br />

BAF, QAF 2 120/240 15-20<br />

QT 1, 2 120/240 15, 20, 40<br />

QR2 2,3 240 100-225<br />

225 (2P)<br />

250<br />

(2, 3P)<br />

225<br />

(2, 3P)<br />

70 (1P)<br />

125 (2P)<br />

100 (3P)<br />

1<br />

2<br />

120/240<br />

120/240<br />

15-70<br />

15-125<br />

QP, BQ, BL<br />

QE, BLE, BE, QPF, BQF,<br />

BLF, QPF2, BLF2<br />

1 120 15-30<br />

QE, BLE, BE, QPF, BLF 2 120/240 15-60<br />

BAF, QAF, QAF2, BAF2 1 120 15-20<br />

BAF, QAF 2 120/240 15-20<br />

QPP 2 120/240 125-200<br />

QT 1, 2 120/240 15-40<br />

QP,BQ,BL<br />

1<br />

2<br />

2<br />

3<br />

1<br />

2<br />

120/240 15-70<br />

120/240 15-125<br />

240 15-125<br />

240 15-100<br />

120 15-30<br />

120/240 15-30<br />

QG, BG, BLG<br />

QT 1,2 120/240 15-50<br />

QFGA2, BFGA2, QAF2,<br />

BAF2, QAF, BAF<br />

1 120 15-20<br />

QAF, BAF 2 120/240 15-20<br />

QPF2, BLF2, QPF, BQF,<br />

BLF, QE, BLE, BE<br />

1 120 15-30<br />

QPF, BLF, QE, BLE 2 120/240 15-60<br />

QN, QNR 2 120/240 150-200<br />

QS 2 120/240 100-225<br />

QR2 2 120/240 100-250<br />

QP, BQ, BL<br />

1<br />

2<br />

120/240 15-70<br />

120/240 15-125<br />

3 240 60-100<br />

QPH, BQH, BLH<br />

1<br />

2<br />

120/240 15-70<br />

120/240 15-125<br />

3 240 15-100<br />

QR2, QRH2 2,3 240 100-225<br />

QJH2 2, 3 240 60-225<br />

QP, BQ, BL,<br />

QPH, BQH, BLH<br />

QPF, BQF, BLF, BE, QPHF,<br />

BQHF, BLHF, QEH, BLEH,<br />

QE, BLE, QPF2, BLF2,<br />

QPHF2, BLHF2, QPHF2,<br />

BLHF2<br />

1<br />

2<br />

3<br />

120/240<br />

240<br />

240<br />

15-70<br />

15-125<br />

15-100<br />

1 120 15-30<br />

QEH, BLEH, QE, QPHF,<br />

BLHF, BLE, QPF, BLF<br />

2 120/240 15-60<br />

QT 1, 2 120/240 15-40<br />

QG, BG, BLG 1, 2 120/240 15-30<br />

Series<br />

Rating<br />

kAIR<br />

65000<br />

(cont.)<br />

Main Breaker<br />

Branch Breaker<br />

Type<br />

Max.<br />

Amperes Type<br />

HQP, HBQ,<br />

HBL<br />

ED4,<br />

ED4, ED6<br />

NDGA,<br />

NDGB<br />

HQPP<br />

FD6-A,<br />

FXD6-A<br />

NFGA,<br />

NFGB<br />

70 (1P)<br />

125 (2P)<br />

100 (3P)<br />

100<br />

(1P)<br />

125<br />

(2P, 3P)<br />

150<br />

(2P, 3P)<br />

225<br />

(2P)<br />

250<br />

(2P,3P)<br />

No substitutions are permitted. All combinations<br />

shown have been tested and<br />

are UL Listed. This information is provided<br />

as a reference tool only. For verification<br />

of specific combination ratings<br />

consult the UL Recognized<br />

Components Directory.<br />

240V Breaker Series Ratings (continued)<br />

HQR2<br />

BAF, QAF, BQAF, QAF2,<br />

BAF2, QAFH2, BAFH2,<br />

QFGA2, BFGA2, QF-<br />

GAH2, BFGAH2<br />

Number<br />

of Poles Voltage Amperes<br />

1 120 15-20<br />

BAF, QAF 2 120/240 15-20<br />

1 120/240 15-70<br />

QP, BQ, BL<br />

2 240 15-125<br />

QPH, BQH, BLH<br />

3 240 15-100<br />

QPHF, BQHF, BLHF, QPF,<br />

BQF, BLF, QE, QEH, BLEH,<br />

1<br />

BE, BLE, QPF2, BLF2,<br />

120 15-30<br />

QPHF2, BLHF2<br />

QEH, BLEH, QE, QPHF,<br />

BLHF,BLE, QPF, BLF<br />

2 120/240 15-60<br />

QAF2, BAF2, BAF, QAF,<br />

BQAF, QAFH2, BAFH2,<br />

QAFH, BQAFH, BAFH, 1 120 15-20<br />

QFGA2, BFGA2, QF-<br />

GAH2, BFGAH2<br />

QAF, BAF, QAFH, BAFH 2 120/240 15-20<br />

ED2 1,2,3 120/240 15-100<br />

QT 1,2 120/240 15-40<br />

1<br />

QPH, BQH, BLH<br />

2<br />

3<br />

QP, BQ, BL,<br />

1<br />

QPH, BQH, BLH<br />

2<br />

QPF, BQF, BLF, QPHF,<br />

BQHF, BLHF, QEH, BLEH,<br />

QE, BLE, BE, BLF2, QPF2,<br />

QFGA2, BFGA2<br />

QEH, BLEH, QE, QPHF,<br />

BLHF, BLE, QPF, BLF<br />

BAF, QAF, BQAF, QAF2,<br />

BAF2, QAFH2, BAFH2,<br />

QAFH, BQAFH, QFGAH2,<br />

BFGAH2<br />

120/240<br />

240<br />

240<br />

120/240<br />

120/240<br />

15-70<br />

15-125<br />

15-100<br />

15-70<br />

15-125<br />

1 120/240 15-30<br />

2 120/240 15-60<br />

1 120 15-20<br />

BAF, QAF, QAFH, BAFH 2 120/240 15-20<br />

QT 1, 2 120 15-40<br />

QPPH, QPP 2 120/240 125-200<br />

QP, BQ, BL<br />

QPH, BQH, BLH<br />

1<br />

2<br />

3<br />

120/240 15-70<br />

120/240 15-125<br />

240 15-100<br />

QPF, QPHF, BLF, BLHF 1,2 120/240 15-60<br />

QPF2, BLF2, QPHF2,<br />

BLHF2<br />

1<br />

2<br />

120<br />

120/240<br />

15-30<br />

15-60<br />

QAF, BAF, QAF2, BAF2,<br />

BQAF, QAFH2, BAFH2,<br />

QAFH, BQAFH, BAFH, 1 120 15-20<br />

QFGA2, BFGA2, QF-<br />

GAH2, BFGAH2<br />

QAF, BAF, QAFH, BAFH 2 120/240 15-20<br />

QR2, QRH2 2,3 240 100-225<br />

QJ2H, QJ2, QJH2 2,3 240 60-225<br />

QPPH 2 120/240 125-225<br />

1 120/240 15-70<br />

QPH, BQH, BLH<br />

2 120/240 15-125<br />

3 240 15-100<br />

QR2, QRH2 2,3 240 100-250<br />

QP, BQ, BL<br />

1<br />

2<br />

3<br />

120/240 15-70<br />

120/240 15-125<br />

240 15-100<br />

QT 1,2 120/240 15-50<br />

QFGA2, BFGA2, QAF2,<br />

1 120 15-20<br />

BAF2, QAF, BAF<br />

QAF, BAF 2 120/240 15-20<br />

QPF2, BLF2, QPF, BQF,<br />

1 120 15-30<br />

BLF, QE, BLE, BE<br />

QPF, BLF, QE, BLE 2 120/240 15-60<br />

QPH, BQH, BLH<br />

1<br />

2<br />

3<br />

120/240 15-70<br />

120/240 15-125<br />

240 15-100<br />