Molded Case Circuit Breakers<br />

SLD 600A Frame Digital Solid State Sentron Sensitrip IV Series<br />

Revised on 10/31/18<br />

Selection<br />

Current Limiting<br />

Type SLD6-B Type SHLD6-B Type SCLD6-B<br />

Blue Label Black Label Red Label<br />

Max 3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC<br />

Current<br />

Rating<br />

Catalog Number<br />

(Advanced trip unit) a<br />

Catalog Number<br />

(Basic trip unit)<br />

Catalog Number<br />

(Advanced trip unit) a<br />

Catalog Number<br />

(Basic trip unit)<br />

Catalog Number<br />

(Advanced trip unit) a<br />

Catalog Number<br />

(Basic trip unit)<br />

300 SLD6A300LI SLD6B300LI SHLD6A300LI SHLD6B300LI SCLD6A300LI SCLD6B300LI<br />

400 SLD6A400LI SLD6B400LI SHLD6A400LI SHLD6B400LI SCLD6A400LI SCLD6B400LI<br />

500 SLD6A500LI SLD6B500LI SHLD6A500LI SHLD6B500LI SCLD6A500LI SCLD6B500LI<br />

600 SLD6A600LI SLD6B600LI SHLD6A600LI SHLD6B600LI SCLD6A600LI SCLD6B600LI<br />

300 SLD6A300LIG SLD6B300LIG SHLD6A300LIG SHLD6B300LIG SCLD6A300LIG SCLD6B300LIG<br />

400 SLD6A400LIG SLD6B400LIG SHLD6A400LIG SHLD6B400LIG SCLD6A400LIG SCLD6B400LIG<br />

500 SLD6A500LIG SLD6B500LIG SHLD6A500LIG SHLD6B500LIG SCLD6A500LIG SCLD6B500LIG<br />

600 SLD6A600LIG SLD6B600LIG SHLD6A600LIG SHLD6B600LIG SCLD6A600LIG SCLD6B600LIG<br />

300 SLD6A300LSI SLD6B300LSI SHLD6A300LSI SHLD6B300LSI SCLD6A300LSI SCLD6B300LSI<br />

400 SLD6A400LSI SLD6B400LSI SHLD6A400LSI SHLD6B400LSI SCLD6A400LSI SCLD6B400LSI<br />

500 SLD6A500LSI SLD6B500LSI SHLD6A500LSI SHLD6B500LSI SCLD6A500LSI SCLD6B500LSI<br />

600 SLD6A600LSI SLD6B600LSI SHLD6A600LSI SHLD6B600LSI SCLD6A600LSI SCLD6B600LSI<br />

300 SLD6A300LSIG SLD6B300LSIG SHLD6A300LSIG SHLD6B300LSIG SCLD6A300LSIG SCLD6B300LSIG<br />

400 SLD6A400LSIG SLD6B400LSIG SHLD6A400LSIG SHLD6B400LSIG SCLD6A400LSIG SCLD6B400LSIG<br />

500 SLD6A500LSIG SLD6B500LSIG SHLD6A500LSIG SHLD6B500LSIG SCLD6A500LSIG SCLD6B500LSIG<br />

600 SLD6A600LSIG SLD6B600LSIG SHLD6A600LSIG SHLD6B600LSIG SCLD6A600LSIG SCLD6B600LSIG<br />

Trip Unit Adjustable Functions<br />

Suffix<br />

Letter<br />

Code<br />

Trip<br />

Type<br />

Cont<br />

Current<br />

Setting<br />

Long<br />

Time<br />

Delay<br />

Instantaneous<br />

Pick Up<br />

LI LI u u u<br />

Short<br />

Time<br />

Pick Up<br />

Short<br />

Time<br />

Fixed<br />

Delay<br />

Short<br />

Time<br />

l 2 t<br />

Delay<br />

Ground<br />

Fault<br />

Pick Up<br />

LIG LIG u u u u u<br />

LSI LSI u u u u u u<br />

LSIG LSIG u u u u u u u u<br />

Ground<br />

Fault<br />

Delay<br />

Ordering Information<br />

Pricing information for all Digital<br />

Sentron Series SLD Frames is<br />

for complete breaker only – price<br />

required lugs as separate items –<br />

lugs are suitable for 75°C Wire.<br />

SLD6, SHLD6 and SCLD6 are<br />

acceptable for reverse connection<br />

application.<br />

Interrupting Ratings<br />

Breaker<br />

Type<br />

RMS Symmetrical kA<br />

UL 489 (File E10848)<br />

240V AC 480V AC 600V AC<br />

SLD6-B 65 35 25<br />

SHLD6-B 100 65 35<br />

SCLD6-B 200 150 100<br />

Neutral Transformers<br />

Ampere Rating Catalog Number<br />

300 N03SJD<br />

400 N04SJD<br />

500 N05SLD<br />

600 N06SLD<br />

Shipping Weights<br />

Breaker<br />

Type<br />

Number per<br />

Carton<br />

SLD6-B 1 20<br />

SHLD6-B 1 20<br />

SCLD6-B 1 33<br />

Shipping<br />

Weight (lbs)<br />

7<br />

MOLDED CASE<br />

CIRCUIT BREAKERS<br />

Note: “G” suffix in catalog number denotes circuit<br />

breaker for 3-phase, 3-wire circuits.<br />

For 3-phase, 4-wire, order correct 4th wire (neutral)<br />

transformer as separate and additional item.<br />

For ordering information and terminal connectors see<br />

page 7-121; for enclosures, see page 7-122.<br />

100% Rated – Not available in SLD6 Frame.<br />

All breakers built to order. Allow 2-3 weeks for delivery.<br />

a Advanced trip unit equipped with DAS / Maintenance<br />

Mode. Requires customer-supplied 24V external power<br />

supply, maintenance switch and light.<br />