Molded Case Circuit Breakers<br />

Reference Guide<br />

Revised on 10/31/18<br />

Selection/Application<br />

Page 7-175 7-179 7-183<br />

Breaker Frame Family DG FG JG<br />

Continuous Amps 30–150A 40–250A 70–400A<br />

Poles 2, 3 2, 3 2, 3<br />

Max. Volts AC 600Y/347V 600Y/347V 600V<br />

Breaker Type NDGA HDGA LDGA NFGA HFGA LFGA NJGA HJGA LJGA<br />

Interrupting Class N H L N H L N H L<br />

240Vac 65 100 200 65 100 200 65 100 200<br />

Interrupting UL 480Vac 35 65 100 35 65 100 35 65 100<br />

Rating RMS<br />

600Vac 18 18 18 18 18 18 25 25 25<br />

Symmetrical<br />

Ratings Amperes<br />

220/240Vac 65/65 100/75 200/150 65/65 100/75 200/150 65/65 100/75 200/150<br />

AC 50/60Hz l CU /l CS 380/415Vac 40/40 70/70 100/75 40/40 70/70 100/75 45/45 70/70 100/75<br />

690Vac 12/6 12/6 12/6 12/6 12/6 12/6 12/6 15/8 15/8<br />

DC<br />

250Vdc (2-Pole) 30 30 30 30 30 30 30 30 30<br />

Ratings (UL) b 600Vdc (3-Pole) — — — — 42 — — 65 —<br />

Interrupting<br />

500Vdc (3-Pole) 18 18 18 18 18 30 25 35 35<br />

Dimensions<br />

in Inches<br />

Trip Unit<br />

Information<br />

Specific<br />

Application<br />

Breakers<br />

Accessories &<br />

Modifications<br />

1-Pole — —<br />

2-Pole 6.9H x 4.1W x 3.4D 11H x 5.5W x 4.2D<br />

3-Pole 6.9H x 4.1W x 3.4D 11H x 5.5W x 4.2D<br />

4-Pole — —<br />

Thermal-Magnetic u u u<br />

Electronic u u u<br />

Electronic with LCD u u u<br />

Interchangeable Trip Unit — — u<br />

Reverse Feed (w/Non-Interchangeable Trip) u u u<br />

Communications Capability u u u<br />

Molded Case Switch u u u<br />

Motor Circuit Protector u u u<br />

100% Rated u u<br />

50°C Calibrated <br />

Auxiliary Switch u u u<br />

Alarm Switch u u u<br />

Shunt Trip u u u<br />

Undervoltage Release u u u<br />

Mechanical Interlocks u u u<br />

Electric Motor or Stored Energy Operator u u u<br />

Rear Connecting Studs u u u<br />

Plug-In Mounting Assy. w/Trip Interlock u u u<br />

Draw-Out Assembly u u u<br />

Handle Mechanism Options u u u<br />

Enclosures NEMA 3R – Outdoor, Rain Proof u u<br />

NEMA 4, 4X – Stainless Steel u u<br />

NEMA 1 – Indoor, Surface Mount u u<br />

NEMA 1 – Indoor, Flush Mount u u<br />

NEMA 7, 9 – Hazardous Locations<br />

NEMA 12 – Dust u u<br />

Terminal Shields u u u<br />

Distribution Lugs u u u<br />

Ground Sensor (Neutral Transformer) u u u<br />

7<br />

MOLDED CASE<br />

CIRCUIT BREAKERS<br />

a 500Vdc nominal, 600Vdc max. for ungrounded DC UPS systems.<br />

b DC Interrupting Ratings are not applicable to electronic circuit breakers.<br />

Communications available via a COMPRO or COMMOD modules using Profibus or Modbus protocols.<br />

Consult Siemens for availability.<br />

“Non-metallic” NEMA 4X enclosure for NGG breakers.<br />

Special version, see page 7-204.<br />

GG are not VL family breakers and do not share common VL accessories.<br />

304 and 316 Stainless Steel<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 7-17