12.01.2021 Views

Speedfax 2017

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Molded Case Circuit Breakers<br />

Reference Guide<br />

Revised on 11/30/19<br />

Selection/Application<br />

Thermal-Magnetic Trip Breakers<br />

General Purpose Breakers<br />

CQD NGG HGG LGG<br />

Page 7-42 7-43 7-43 7-43<br />

Poles 1, 2, 3 1, 2, 3 1, 2, 3 1, 2, 3<br />

1-Pole 15–100 15–125 15–125 15–125<br />

Amperes, Continuous<br />

2-Pole 15–100 15–125 15–125 15–125<br />

3-Pole 15–100 15-125 15–125 15–125<br />

1-Pole 277 347 347 347<br />

Volts (50/60 Hertz)<br />

2-Pole 480/277 600/347 600/347 600/347<br />

3-Pole 480/277 600/347 600/347 600/347<br />

120V 65,000 65,000 65,000 65,000<br />

UL<br />

240V 65,000 65,000 65,000 65,000<br />

480V 14,000 25,000 35,000 65,000<br />

600/347V 10,000 b 14,000 14,000 14,000<br />

AC<br />

Icu 18,000<br />

1-Pole<br />

25,000 — —<br />

220/<br />

Ics 9,000 d 12,500 — —<br />

240V<br />

Ratings<br />

DC<br />

Dimensions<br />

in inches<br />

Overcurrent<br />

Devices<br />

Accessories and<br />

Modifications<br />

Individual<br />

Enclosures<br />

Interrupt Rating Symmetrical RMS Amperes<br />

IEC<br />

947-2<br />

50/<br />

60Hz<br />

380/<br />

415V<br />

500V<br />

2,3-<br />

Pole<br />

1-Pole<br />

2,3-<br />

Pole<br />

1-Pole<br />

2,3-<br />

Pole<br />

Icu 65,000 d 65,000 — —<br />

Ics 32,500 d 32,500 — —<br />

Icu — — — —<br />

Ics — — — —<br />

Icu 18,000 d 25,000 — —<br />

Ics 9,000 d 12,500 — —<br />

Icu — — — —<br />

Ics — — — —<br />

Icu — — — —<br />

Ics — — — —<br />

Volts — 2-Pole 125/250 125/250 125/250 125/250<br />

Interrupting Rating — DC Amperes 14,000 14,000 14,000 14,000<br />

15–50A 4.50 5.40 5.40 5.40<br />

Height<br />

55–125A 4.50 5.40 5.40 5.40<br />

60–225A — — — —<br />

1-Pole 1.00 1.00 1.00 1.00<br />

Width<br />

2-Pole 2.00 2.00 2.00 2.00<br />

3-Pole 3.00 3.00 3.00 3.00<br />

Depth 2.87 2.90 2.90 2.90<br />

Thermal and Fixed Magnetic Trip u u u u<br />

Molded Case Switch — — — —<br />

Undervoltage Trip — — — —<br />

Shunt Trip u u u u<br />

Auxiliary Switch u u u u<br />

Alarm Switch u u u u<br />

Mechanical Interlock — — — —<br />

Fungus Proofing (ref. page 7-156) u u u u<br />

Type 1 — Indoor Surface — u u u<br />

Type 1 — Indoor, Flush — u u u<br />

Type 3R — Outdoor-Rainproof — u u u<br />

Type 5, 12 — Lint, Fine Dust, Oils, Coolants — — u u<br />

7<br />

MOLDED CASE<br />

CIRCUIT BREAKERS<br />

CQD120<br />

LGG2B020L<br />

For inches / millimeters conversion, see Application Data section.<br />

CQD breakers are rated 14,000 KAIC at 480/277V.<br />

Type CQD6—CSA only.<br />

3-pole only.<br />

d Applicable for 15-30A breakers only.<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 7-9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!