Molded Case Circuit Breakers<br />

Reference Guide<br />

Revised on 11/30/19<br />

Selection/Application<br />

Thermal-Magnetic Trip Breakers<br />

General Purpose Breakers<br />

7<br />

MOLDED CASE<br />

CIRCUIT BREAKERS<br />

BQ BQH HBQ QR2 QRH2 HQR2 HQR2H<br />

Page 7-38 7-38 7-38 7-40 7-40 7-40 7-40<br />

Poles 1, 2, 3 1, 2, 3 1, 2, 3 2, 3 2, 3 2, 3 2, 3<br />

1-Pole 15–70 15–70 15–50 — — — —<br />

Amperes, Continuous<br />

2-Pole 15–125 15–100 15–70 100–250 100–250 100–250 100–250<br />

3-Pole 15–100 15–100 15–100 100–250 100–250 100–250 100–250<br />

1-Pole 120/240 120/240 120/240 — — — —<br />

Volts (50/60 Hertz)<br />

2-Pole 240 240 240 240 240 240 240<br />

3-Pole 240 240 240 240 240 240 240<br />

120V 10,000 22,000 65,000 — — — —<br />

UL<br />

240V 10,000 22,000 65,000 10,000 25,000 65,000 100,000<br />

480V — — — — — — —<br />

600/347V — — — — — — —<br />

AC<br />

Icu — — — — — — —<br />

1-Pole<br />

220/<br />

Ics — — — — — — —<br />

240V<br />

Icu — — — — — — —<br />

2,3-Pole<br />

Ics — — — — — — —<br />

Ratings<br />

DC<br />

Dimensions<br />

in inches<br />

Overcurrent<br />

Devices<br />

Accessories and<br />

Modifications<br />

Individual<br />

Enclosures<br />

Interrupt Rating Symmetrical RMS Amperes<br />

IEC<br />

947-2<br />

50/<br />

60Hz<br />

380/<br />

415V<br />

500V<br />

1-Pole<br />

2,3-Pole<br />

1-Pole<br />

2,3-Pole<br />

Icu — — — — — — —<br />

Ics — — — — — — —<br />

Icu — — — — — — —<br />

Ics — — — — — — —<br />

Icu — — — — — — —<br />

Ics — — — — — — —<br />

Icu — — — — — — —<br />

Ics — — — — — — —<br />

Volts — 2-Pole — — — — — — —<br />

Interrupting Rating — DC Amperes — — — — — — —<br />

15–50A 3.75 3.75 4.00 — — — —<br />

Height<br />

55–125A 4.00 4.00 4.00 — — — —<br />

60–225A — — — 7.00 7.00 7.00 7.00<br />

1-Pole 1.00 1.00 1.00 — — — —<br />

Width<br />

2-Pole 2.00 2.00 2.00 3.00 3.00 3.00 3.00<br />

3-Pole 3.00 3.00 3.00 4.50 4.50 4.50 4.50<br />

Depth 2.37 2.37 2.37 2.53 2.53 2.53 2.53<br />

Thermal and Fixed Magnetic Trip u u u u u u u<br />

Molded Case Switch u — — — — — u <br />

Undervoltage Trip — — — — — — —<br />

Shunt Trip u u u u u u u<br />

Auxiliary Switch u u u u u u u<br />

Alarm Switch — — — — — — —<br />

Mechanical Interlock — — — u u u u<br />

Fungus Proofing (ref. page 7-156) u u u u u u u<br />

Type 1 — Indoor Surface u u u u u u u<br />

Type 1 — Indoor, Flush u u u u u u u<br />

Type 3R — Outdoor-Rainproof u u u u u u u<br />

Type 5, 12 — Lint, Fine Dust, Oils, Coolants — — — — — — —<br />

BQ1B020 BQ1B020H HB1B020<br />

For inches / millimeters conversion, see Application Data section.<br />

CQD breakers are rated 14,000 KAIC at 480/277V.<br />

Type CQD6—CSA only.<br />

3-pole only.<br />

d Applicable for 15-30A breakers only.<br />

7-8<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog