Power Mod<br />

Revised on 06/30/19<br />

WML and WMT Commercial Meter Stacks Rating Charts<br />

Use the tables below to determine the correct combination of equipment and circuit breakers for the available fault current.<br />

This chart provides series rating information for the most common applications. For a complete series rating chart please contact<br />

your local sales office.<br />

3<br />

METER<br />

CENTERS<br />

Available fault current<br />

RMS symmetrical amps at<br />

120/240V max 1-phase, 240V<br />

max 3-Phase Main Modules a Meter module<br />

branch circuit breakers<br />

to 10,000<br />

to 22,000<br />

Series<br />

WB, WB_U, WBM, WBM_U<br />

WEB, WEB_U, WEBM, WEBM_U<br />

WS_U, WES_U, WTB_U,<br />

WET_U, WXB, WXB_U, WXS,<br />

WXBM, WXBM_U, WBTM,<br />

WBTM_U, BFTM and BFTM_U<br />

Series<br />

WB, WB_U, WBM, WBM_U<br />

WEB, WEB_U, WEBM,<br />

WEBM_U, WXB, WXB_U,<br />

WXBM, WXBM_U, WBTM,<br />

WBTM_U, BFTM and BFTM_U<br />

Series<br />

WS_U, WES_U<br />

WXS<br />

Series<br />

WTB_U<br />

WET_U<br />

QP, QPH, HQP, HQPH (2 pole,15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole,100-225A)<br />

QP, QPH, HQP (3 pole,15–100A)<br />

QR2, QRH2, HQR2, HQR2H (3 Pole, 100–225A)<br />

JXD2-A, JD6-A, JXD6-A (2 and 3 pole, 200–400A)<br />

LD6-A, LXD6-A (2 and 3 pole, 600A)<br />

QPH, HQP, HQPH (2 pole,15–125A)<br />

QS, QSH, QSHH, HQS, HQSH (2 pole,100–225A)<br />

QPH, HQP (3 pole,15–100A)<br />

QR2, QRH2, HQR2, HQR2H (3 Pole, 100–225A)<br />

QPH, HQP, HQPH (2 pole,15–125A)<br />

QS, QSH, QSHH, HQS, HQSH (2 pole,100–225A)<br />

QPH, HQP (3 pole,15–100A)<br />

QR2, QRH2, HQR2, HQR2H (3 Pole, 100–225A)<br />

QPH, HQP, HQPH (2 pole,15–125A)<br />

QSH, QSHH, HQS, HQSH (2 pole,100–225A)<br />

QPH, HQP (3 pole,15–100A)<br />

QRH2, HQR2, HQR2H (3 Pole, 100–225A)<br />

Load center<br />

branch circuit breakers<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

to 25,000<br />

Series<br />

WB, WB_U, WBM, WBM_U<br />

WEB, WEB_U, WEBM, WEBM_U<br />

WS_U, WES_U, WTB_U,<br />

WET_U, WXB, WXB_U, WXS,<br />

WXBM, WXBM_U, WBTM,<br />

WBTM_U, BFTM and BFTM_U<br />

JXD2-A, JD6-A, JXD6-A<br />

(2 and 3 pole, 200–400A)<br />

LD6-A, LXD6-A<br />

(2 and 3 pole, 600A)<br />

QPH, HQP<br />

to 42,000<br />

Series<br />

WB, WB_U, WBM, WBM_U,<br />

WEB, WEB_U, WEBM,<br />

WEBM_U, WXB, WXB_U,<br />

WXBM, WXBM_U, WBTM,<br />

WBTM_U, BFTM and BFTM_U<br />

Series<br />

WS_U, WES_U<br />

WXS<br />

QPH, HQP, HQPH (2 pole,15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole,100–225A)<br />

QPH, HQP (3 pole,15–100A)<br />

QR2, QRH2, HQR2, HQR2H (3 Pole, 100–225A)<br />

QPH, HQP, HQPH (2 pole,15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole,100–225A)<br />

QPH, HQP (3 pole,15–100A)<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

QR2, QRH2, HQR2, HQR2H (3 Pole, 100–225A)<br />

Series<br />

WTB_U<br />

WET_U<br />

HQP, HQPH (2 pole,15–125A)<br />

QSHH, HQS, HQSH (2 pole,100–225A)<br />

HQP (3 pole,15–100A)<br />

HQR2, HQR2H (3 Pole, 100–225A)<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

QP, QPH, HQP<br />

a Service Entrance Modules:<br />

WB, WEB, WXB, WBT and BFT have 65k AIC breakers factory installed [(JXD2-A, JXD6-A) (LXD6-A) (MXD6) (NXD6) (PXD6) (RXD6)]<br />

WB_U, WEB_U, WXB_U, WBT_U and BFT_U have 100k AIC breakers factory installed [(HJXD6-A) (HLXD6-A) (HMXD6) (HNXD6) (HPXD6) (HRXD6)]<br />

WBM, WEBM, WXBM, WBTM and BFTM have 65k AIC DAS breakers factory installed [(SND6) (SPD6)]<br />

WBM_U, WEBM_U, WXBM_U, WBTM_U and BFTM_U have 100k AIC DAS breakers factory installed [(SHND6) (SHPD6)]<br />

WS_U and WES_U are fused switches (Class T – 300 volt)<br />

WTB_U and WET_U have NO overcurrent protection<br />