Power Mod<br />

Revised on 06/30/19<br />

WMM Residential Meter Stacks Rating Charts<br />

Use the tables below to determine the correct combination of equipment and circuit breakers for the available fault current.<br />

This chart provides series rating information for the most common applications. For a complete series rating chart please contact<br />

your local sales office.<br />

Available fault current<br />

RMS symmetrical amps at<br />

Meter module<br />

120/240 volts maximum Main Modules a branch circuit breakers<br />

Load center<br />

branch circuit breakers<br />

to 10,000<br />

Series<br />

WB, WB_U, WBM, WBM_U<br />

WEB, WEB_U, WEBM, WEBM_U<br />

WS_U, WES_U, WTB_U,<br />

WET_U, WXB, WXB_U<br />

WXBM, WXBM_U, WBTM,<br />

WBTM_U, BFTM and BFTM_U<br />

Series<br />

WB, WB_U, WBM, WBM_U<br />

WEB, WEB_U, WEBM, WEBM_U<br />

WXB, WXB_U, WXBM,<br />

WXBM_U, WBTM, WBTM_U,<br />

BFTM and BFTM_U<br />

QP, QPH, HQP, HQPH (2 pole, 15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

QPH, HQP, HQPH (2 pole, 15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

3 METER<br />

CENTERS<br />

to 22,000<br />

Series<br />

WS_U, WES_U<br />

WXS<br />

QPH, HQP, HQPH (2 pole, 15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

Series<br />

WTB_U, WET_U<br />

QPH, HQP, HQPH (2 pole, 15–125A)<br />

QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

to 42,000<br />

Series<br />

WB, WB_U, WBM, WBM_U<br />

WEB, WEB_U, WEBM, WEBM_U<br />

WXB, WXB_U, WXBM,<br />

WXBM_U, WBTM, WBTM_U,<br />

BFTM and BFTM_U<br />

Series<br />

WS_U, WES_U<br />

WXS<br />

QPH, HQP, HQPH (2 pole, 15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

QPH, HQP, HQPH (2 pole, 15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

Series<br />

WTB_U, WET_U<br />

HQP, HQPH (2 pole, 15–125A)<br />

QSHH, HQS, HQSH (2 pole, 100–225A)<br />

Series<br />

WB, WB_U, WBM, WBM_U<br />

WEB, WEB_U, WEBM, WEBM_U<br />

WXB, WXB_U<br />

QPH, HQP, HQPH (2 pole, 15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

to 65,000<br />

Series<br />

WS_U, WES_U<br />

WXS<br />

QPH, HQP, HQPH (2 pole, 15–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

Series<br />

WTB_U, WET_U<br />

HQP, HQPH (2 pole, 15–125A)<br />

HQS, HQSH (100–225A)<br />

to 100,000<br />

Series<br />

WB_U, WBM_U, WEB_U,<br />

WEBM_U, WS_U, WES_U,<br />

WXB_U, WXS, WXBM_U,<br />

WBTM_U and BFTM_U<br />

HQPH (2 pole, 100–125A)<br />

QS, QSH, QSHH, HQS, HQSH<br />

(2 pole, 100–225A)<br />

QP, QPH, HQP, QT, QAF, QAFH,<br />

QPF, QPHF, QE, QEH<br />

Series<br />

WTB_U, WET_U<br />

HQPH (2 pole, 100–125A)<br />

HQSH (100–225A)<br />

a Service Entrance Modules:<br />

WB, WEB, WXB, WBT and BFT have 65k AIC breakers factory installed [(JXD2-A, JXD6-A) (LXD6-A) (MXD6) (NXD6) (PXD6) (RXD6)]<br />

WB_U, WEB_U, WXB_U, WBT_U and BFT_U have 100k AIC breakers factory installed [(HJXD6-A) (HLXD6-A) (HMXD6) (HNXD6) (HPXD6) (HRXD6)]<br />

WBM, WEBM, WXBM, WBTM and BFTM have 65k AIC DAS breakers factory installed [(SND6) (SPD6)]<br />

WBM_U, WEBM_U, WXBM_U, WBTM_U and BFTM_U have 100k AIC DAS breakers factory installed [(SHND6) (SHPD6)]<br />

WS_U and WES_U are fused switches (Class T – 300 volt)<br />

WTB_U and WET_U have NO overcurrent protection<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 3-141