Power Mod<br />

Revised on 06/30/19<br />

Applications: WMLZ/ WMLZF – Fusible Residential Lever Bypass Meter Stacks<br />

Flow of Current<br />

3<br />

WMLZ<br />

WMLZ WMLZF<br />

WMLZF WMLZ WSPD<br />

METER<br />

CENTERS<br />

E<br />

E<br />

C<br />

C<br />

E<br />

Main<br />

Horizontal<br />

Bus<br />

A<br />

F<br />

Secondary<br />

Horizontal<br />

Bus<br />

D<br />

D<br />

B<br />

B<br />

D<br />

A Cables land on a tap box and current enters Power Mod line up on the main horizontal Bus.<br />

B Current is directed from the main horizontal bus down onto the WMLZF’s vertical bus and into the<br />

400 amp fuse pull out.<br />

C The current then goes up on the WMLZF’s vertical bus to feed the sockets.<br />

D WMLZ’s must be fed by a secondary horizontal bus from the WMLZF’s<br />

*Additional connections are required between the WMLZ and WMLZF.<br />

E The current then flows up from the secondary horizontal bus and on to the vertical bus to<br />

feed the sockets in the WMLZ’s.<br />

*More than one WMLZ can be fed from 1 WMLZF.<br />

F The main horizontal bus is used as a pass through on the WMLZ’s for any additional modules attached to the line up.<br />

*Quick Connect MUST be used between every module to maintain the line ups Neutral bonding, even if there are no extra modules<br />

attached at the end of the line up.<br />

3-70<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog