12.01.2021 Views

Speedfax 2017

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Power Mod<br />

Revised on 10/31/19<br />

Type WT Feed Thru Tap box<br />

3<br />

Restrictions for 1600-2400amp type WT Power Mod Pull-Thru Tap Boxes:<br />

Type WT feed thru tap boxes cannot be used as service equipment. The feed thru<br />

conductors must have upstream circuit protection. When fed by a Class L fuse, there are<br />

restrictions on the use of additional down-stream horizontal cross-bus connected WTBN,<br />

WET, or WT type Power Mod tap boxes. When another tap box is connected to the same<br />

meter-bank, a type WXB module must be used as protection for the downstream tap<br />

box (placed between the incoming WT tap box and the downstream outgoing tap box).<br />

This restriction does NOT apply if the tap box is fed from a Siemens Sentron or VL series<br />

molded case circuit breaker. Note that the maximum amperage for a Siemens Sentron<br />

circuit breaker is 2,000A. Please note that Siemens type WL circuit breakers CANNOT be<br />

used to feed WT Power Mod tap boxes.<br />

Lug kits not<br />

included.<br />

(2) Lug kits<br />

must be ordered<br />

separately per<br />

module.<br />

Refer to pages<br />

3-129–3-130 for<br />

lug size options.<br />

METER<br />

CENTERS<br />

Not suitable for use as service equipment.<br />

Feed Thru Tap box modules: 1-phase, 120/240V AC<br />

Catalog<br />

number (100k AIC)<br />

Catalog<br />

number (100k AIC)<br />

Blank Endwall<br />

Ampere<br />

rating<br />

Service<br />

feed<br />

Dimensions (inches) KO<br />

Height Width Depth Line side conections Diagram<br />

WT1400PU WT1400PUNH 400<br />

59.25 17.25 8.13 1 set of 2 studs<br />

WT1800PU WT1800PUNH 800 62.25 26.75 11.13 2 sets of 2 studs<br />

WT11200PU WT11200PUNH 1200 68.34 35.19 11.41<br />

WT11600PU WT11600PUNH 1600 OH/UG<br />

67.94 35 14.78<br />

WT12000PU WT12000PUNH 2000<br />

WT12400PU WT12400PUNH 2400 67.94 35 14.78<br />

3 sets of 2 studs<br />

3 sets of 2 studs<br />

Optional 4 sets<br />

of 2 studs <br />

WP-1<br />

WP-2<br />

Feed Thru Tap box modules: 3-phase, 240V AC<br />

Catalog<br />

number (100k AIC)<br />

Catalog<br />

number (100k AIC)<br />

Blank Endwall<br />

Ampere<br />

rating<br />

Service feed<br />

Dimensions (inches) KO<br />

Height Width Depth Line side conections Diagram<br />

WT3400PU WT3400PUNH 400<br />

59.25 17.25 8.13 1 set of 2 studs<br />

WT3800PU WT3800PUNH 800 62.25 26.75 11.13 2 sets of 2 studs<br />

WT31200PU WT31200PUNH 1200 68.34 35.19 11.41<br />

WT31600PU WT31600PUNH 1600 OH/UG<br />

67.94 35 14.78<br />

WT32000PU WT32000PUNH 2000<br />

WT32400PU WT32400PUNH 2400 67.94 35 14.78<br />

3 sets of 2 studs<br />

3 sets of 2 studs<br />

Optional 4 sets<br />

of 2 studs <br />

WP-1<br />

WP-2<br />

Dimensions shown are representative of outside box<br />

dimensions and do not include allowances for mounting<br />

bumps, endwalls, covers, hubs, or hardware<br />

protrusions. Dimensions are subject to change.<br />

Lugs not included. Refer to page 3-129–3-130 for lug<br />

size options. (2) Lug kits must be ordered separately<br />

per module. Refer to page 3-129 – 3-130 for lug<br />

size options.<br />

1200 amp maximum feed per side-must be used as a<br />

center fed main.<br />

Please see restriction note above.<br />

Optional four sets of two studs obtained by installing<br />

bus extension which is provided in all applicable lug<br />

kits.<br />

3-50<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog