12.01.2021 Views

Speedfax 2017

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Power Mod<br />

Revised on 10/31/19<br />

Type WS Standard Switch Mains<br />

Suitable for use as service equipment.<br />

Bonding means may be removed for nonservice<br />

entrance equipment applications.<br />

Lugs not included on<br />

most models.<br />

NEMA 2-stud lugs<br />

must be installed by<br />

user or utility.<br />

Refer to pages 3-129–<br />

3-130 for lug size<br />

options.<br />

METER<br />

CENTERS<br />

3<br />

Fusible switch service entrance modules: 1-phase, 3-wire SN, 120/240V AC f<br />

Catalog number<br />

(100k AIC)<br />

Catalog number<br />

(100k AIC)<br />

Blank Endwall<br />

Rating<br />

amps<br />

Service<br />

feed<br />

Fuse Dimensions (inches) a Line side<br />

type f Height Width Depth connections<br />

Knockout<br />

Diagrams<br />

WMP02U b WMP02UNH 200 OH/UG T 33.00 12.00 13.00 (1) #6 - 250 KCMIL S-0<br />

WS1400CU c WS1400CUNH 400 OH/UG d T 50.13 15.19 16.31 1 set of 2 studs<br />

WS1600CU c WS1600CUNH 600 OH/UG d T 50.13 15.19 16.31<br />

(lugs not included)<br />

S-1<br />

WS1800CU c WS1800CUNH 800 OH/UG d T 50.13 15.19 16.31<br />

2 sets of 2 studs<br />

(lugs not included)<br />

S-2<br />

WS11200BU eg — 1200 UG T 50.06 20.22 16.06 (4) 250- 500 kcmil S-3<br />

Fusible switch service entrance modules: 3-phase, 4-wire WN, 240V AC Max. f<br />

Catalog number<br />

(100k AIC)<br />

Catalog number<br />

(100k AIC)<br />

Blank Endwall<br />

Rating<br />

amps<br />

Service<br />

feed<br />

a Fuse<br />

Dimensions (inches)<br />

Line side<br />

type f Height Width Depth connections<br />

Knockout<br />

Diagrams<br />

WMP024U b WMP024UNH 200 OH/UG T 33.00 12.00 13.00 (1) #6 - 250 KCMIL S-0<br />

WS3400CU c WS3400CUNH 400 OH/UG d T 50.13 15.19 16.31 1 set of 2 studs<br />

WS3600CU c WS3600CUNH 600 OH/UG d T 50.13 15.19 16.31<br />

(lugs not included)<br />

S-1<br />

WS3800CU c WS3800CUNH 800 OH/UG d T 50.13 15.19 16.31<br />

2 sets of 2 studs<br />

(lugs not included)<br />

S-2<br />

WS31200BU eg — 1200 UG T 50.06 20.22 16.06 (4) 250-500 kcmil S-3<br />

a Dimensions shown are representative of outside<br />

box dimensions and do not include allowances for<br />

mounting bumps, endwalls, covers, hubs, or hardware<br />

protrusions. Dimensions are subject to change.<br />

b Additional lead time required. Contact sales office for<br />

details. Fusible pull-out switch.<br />

c Lugs not included. Refer to page 3-129–3-130 for lug size<br />

options. NEMA 2-stud compression lugs must be<br />

installed by user or utility.<br />

d Module is invertible – rotate device to point hub openings<br />

to appropriate feed direction.<br />

e 500 kcmil max wire range size.<br />

f Fuses not included.<br />

g Device uses a molded case switch (looks like a breaker).<br />

Class T fuses must be installed in conjunction with the<br />

molded case switch for proper operation.<br />

Depending on installation details and adjacent product,<br />

a WSP spacer module may be required to provide<br />

enough clearance for hinges/latches. Contact your local<br />

sales person for support<br />

3-34<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog