Current Limiting Circuit Breaker Technology<br />

Selection<br />

Fuseless Current Limiting<br />

Circuit Breakers<br />

The technology of Siemens Sentron ®<br />

fuseless current limiting circuit breakers<br />

was developed to meet the demands of<br />

modern distribution systems. It is<br />

not uncommon for today’s systems to<br />

have prospective short circuit currents<br />

approaching 200,000 amperes. Users<br />

demanded the protection and flexibility<br />

afforded by circuit breakers, without<br />

the nuisance and expense of fuse<br />

replacement.<br />

Underwriters Laboratories, in UL489-<br />

2.4A, defines a fuseless current limiting<br />

circuit breaker as one that “does not<br />

employ a fusible element, and that when<br />

operating within its current-limiting range,<br />

limits the let-through l 2 t to a value less<br />

than the l 2 t of a half-cycle wave of the<br />

symmetrical prospective current.”<br />

l 2 t is an expression which allows<br />

comparison of the energy available as a<br />

result of fault current flow. As used in<br />

current limiting discussions, l 2 t refers to<br />

the energy released between the initiation<br />

of the fault current and the clearing of the<br />

circuit.<br />

Figure 26 relates the “prospective l 2 t” to<br />

the energy allowed by a Sentron current<br />

limiting circuit breaker, or “let-through<br />

l 2 t”. The upper curve represents the<br />

maximum I 2 the circuit can produce,<br />

unaltered by the presence of any<br />

protective device. The lower curve<br />

illustrates the reduction in energy<br />

allowed when Sentron current limiting<br />

circuit breakers are used.<br />

Figure 26. Reduction of l 2 t Let-Through<br />

with Current-Limiting Technology<br />

Figure 27. Current Limitation<br />

Figure 27 illustrates how the Sentron<br />

circuit breaker limits the energy under<br />

fault conditions. The upper curve<br />

illustrates the first half-cycle wave of<br />

prospective fault current. To qualify as<br />

truly current limiting, the circuit breaker<br />

must prevent the current value from<br />

reaching the maximum value that it<br />

would reach if the circuit breaker were<br />

not connected in the circuit.<br />

The Sentron circuit breakers use the<br />

“blow-apart” contact principle to<br />

accomplish current limitation. This<br />

principle is based on the electro-magnetic<br />

repulsion of adjacent conductors which<br />

carry current in opposite directions.<br />

The contact arms are arranged to create<br />

opposing magnetic fields. As fault current<br />

rises, magnetic repulsion forces the<br />

contacts to separate completely. The<br />

higher the fault current, the faster this<br />

“blow-apart” action occurs.<br />

As figure 27 illustrates, the energy letthrough<br />

with the current limiting Sentron<br />

circuit breaker is decreased significantly.<br />

This provides better protection for<br />

downstream equipment, and reduces<br />

damage.<br />

Applications and Ratings<br />

Sentron current limiting circuit breakers<br />

are designed for use in load centers,<br />

power panelboards, distribution<br />

switchboards, secondary unit<br />

substations, and all types of individual<br />

enclosures where the available fault<br />

currents exceed the interrupting ratings<br />

of heavy duty and extra-heavy duty<br />

molded case circuit breakers.<br />

Sentron circuit breakers have ratings of<br />

15 through 1600 amperes, 240 through<br />

600 volts AC, with up to 200,000<br />

symmetrical amperes interrupting rating.<br />

T TECHNICAL<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog T-13