Power Mod<br />

Revised on 06/30/19<br />

Overview of Families<br />

WBT - Feed Thru Tap Box with Horizontal Bus Breaker<br />

Feed thru tap box and breaker module (type WBT) offers<br />

the ability to pull conductors in and out of the enclosure for<br />

rise cable or loop feed applications as well as a main breaker<br />

device utilizing an incoming and out-going thru bus connections<br />

(including incoming lugs). This patented design allows the user to<br />

utilize the WBT family to connect to Siemens Sentron Busway.<br />

Features include:<br />

n Incoming and Outgoing Power Mod thru bus<br />

n Standard compression lug capability<br />

n 65K AIC standard, 100K AIC available for all models<br />

n Broad ampacity ratings up to 1200 Amps<br />

n DAS blue light models available in 1200A<br />

Feed Thru Tap Box with<br />

Breaker quick reference<br />

n 200-1200A breaker rating<br />

n 1200-2400A feed-thru rating<br />

n 1200A horizontal bus rating<br />

n UL Standard #67<br />

n UL file #E27100<br />

n AIC rating (65K and 100K)<br />

n Voltage:<br />

– Three Phase 240V AC max<br />

n NEMA 3R rated<br />

Restrictions for WBT Feed Thru breaker tapbox units:<br />

Type WBT feed thru breaker tap boxes cannot be used as service equipment. The feed thru conductors must<br />

have upstream circuit protection. For feed thru conductor ratings up to 2,000 amps, Siemens Sentron or VL circuit<br />

breakers can be used. For feed thru conductor ratings over 2,000 amps but up to 2,400 amps, use Class L fuses.<br />

Please note that Siemens type WL circuit breakers CANNOT be used as the direct upstream main for these WBT<br />

feed thru breaker tap boxes.<br />

BFT - Main Feed Thru<br />

Main feed thru (type BFT) breaker modules has the ability to<br />

isolate power to side-mounted modules just like any other<br />

Power Mod main breaker module, but also contains feed-through<br />

lugs that can be used to supply and isolate power vertically to<br />

downstream group metering line ups.<br />

Features include:<br />

n Incoming and Outgoing Power Mod thru bus<br />

n Standard compression lug capability<br />

n 65K AIC standard, 100K AIC available for all models<br />

n Main breaker with broad ampacity ratings from<br />

1200A to 2000A<br />

n DAS blue light models available in amperages of 1400-1600A<br />

n For 1200A DAS you must use a 1400A DAS module and have<br />

the trip setting dialed down to 1200A in the field.<br />

WS – Standard Switch Mains<br />

Standard switch modules (type WS) are designed for flexibility,<br />

space savings, and durability.<br />

Features include:<br />

n Standard compression lug capability<br />

n Invertibility: 400-800 Amp devices can be rotated to accommodate<br />

the desired incoming feed direction<br />

n 750 kcmil AL wire options for most models<br />

n 100K AIC standard for all models<br />

n Class T fuse provisions<br />

n Broad ampacity ratings up to 1200 Amps<br />

Main Feed Thru<br />

quick reference<br />

n 1200-2000A module<br />

rating (breaker)<br />

n 1200-2000A feed-thru rating<br />

n 1200A horizontal bus rating<br />

n UL Standard #67, file #E27100<br />

n AIC rating (65K & 100K)<br />

n Voltage: 240V AC max<br />

n Available in single and three phase<br />

n NEMA 1 (Indoor)<br />

n Bottom feed only<br />

n All units come with no hubs<br />

n EUSERC drawing number 347<br />

(EUSERC applies to 1200A unit only)<br />

Standard Switch Mains<br />

quick reference<br />

n 200-1200A module rating<br />

n 1200A horizontal bus rating<br />

n 1200A thru-bus rating<br />

n UL Standard # 98<br />

n<br />

UL file #E25506<br />

n AIC rating (100k AIC)<br />

n Voltage:<br />

– Single phase 120/240V AC max<br />

– Three phase 240V AC max<br />

n NEMA 3R rated<br />

3 METER<br />

CENTERS<br />

WES – Switch-Pullbox Combinations<br />

EUSERC - compliant switch-pullbox combination modules (type<br />

WES) offer EUSERC compatibility, a wider range of lug options,<br />

and extra space for pulling in conductors.<br />

Features include:<br />

n NEMA 2-stud lug mounting pattern<br />

n Broad ampacity ratings up to 1200 Amps<br />

n 750kcmil AL wire options<br />

n 100K AIC standard for all models<br />

n Removable blank bottom endwall<br />

n Class T fuse provisions<br />

n Extra ground lugs in each device<br />

Switch-Pullbox<br />

Combo quick reference<br />

n 400-1200A module rating<br />

n 1200A horizontal bus rating<br />

n UL standard # 98<br />

n UL file # E25506<br />

n AIC Rating (100k AIC)<br />

n Voltage:<br />

– Single phase 120/240V AC max<br />

– Three phase 240V AC max<br />

n NEMA 3R rated<br />

n EUSERC drawing numbers 315, 343,<br />

and 347<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 3-5