For Operation in the Control Cabinet<br />

3RW Soft Starters<br />

Project Planning aids<br />

Main circuit<br />

Control circuit<br />

Possibility 4a: Possibility 4b: Possibility 4:<br />

Inside-delta circuit<br />

Change of direction of rotation for Control by means of PLC<br />

inside-delta circuit<br />

L1<br />

1/N/PE 230 V AC 1) , 50 Hz<br />

F2<br />

+24 V DC<br />

PLC outputs<br />

PLC inputs<br />

M<br />

Start 2)<br />

Reset<br />

PTC type A or<br />

Thermoclick<br />

PE<br />

N<br />

Q11<br />

PE<br />

A1<br />

Motor right<br />

L+ L- IN1 IN2 IN3 IN4<br />

Group error<br />

A2 13 14 23 24 33 34 95 96 98<br />

Switch-on duration No action No action<br />

No action<br />

No action<br />

Trip Reset<br />

T1<br />

+<br />

T2<br />

NSB0_01498b<br />

Soft Starter<br />

Control<br />

1) Permissible values for main and control voltage, see<br />

"Technical specifications".<br />

2) Caution: Risk of restarting!<br />

The start command (e. g. from the PLC) must be reset prior to a reset command<br />

because a new, automatic restart will take place automatically if a<br />

start command is active after the reset command. This applies especially<br />

in case of motor protection tripping.<br />

For safety reasons we recommend incorporating the group error output<br />

(terminals 95 and 96) in the controller.<br />