For Operation in the Control Cabinet<br />

3RW Soft Starters<br />

Project Planning aids<br />

Main circuit<br />

Possibility 3a:<br />

Inline circuit with ramp-down function DC braking 3)<br />

(for device types 3RW44 22 to 3RW44 25)<br />

Control circuit<br />

Possibility 3a:<br />

Control of the DC braking contactor 3)<br />

L1<br />

L2<br />

L3<br />

3/N/PE 400 V AC 1) , 50 Hz<br />

L1<br />

1/N/PE 230 V AC 1) , 50 Hz<br />

Q1<br />

F2<br />

+24 V DC<br />

PLC output<br />

F3<br />

L1 L2 L3<br />

(optional<br />

semiconductor<br />

protection)<br />

M<br />

Start 2)<br />

Reset<br />

PTC type A or<br />

Thermoclick<br />

Q11<br />

T1 T2 T3<br />

Q91<br />

No action<br />

No action<br />

Reset<br />

Soft Starter<br />

Control<br />

M1<br />

PE<br />

Q91<br />

2<br />

U1 V1 W1<br />

M<br />

3~<br />

Q91<br />

NSB0_01501b<br />

Q91<br />

PE<br />

N<br />

Q11<br />

A1<br />

L+ L- IN1 IN2 IN3 IN4<br />

PE<br />

DC braking contactor 3)<br />

96<br />

A2 13 14 23 24 33 34 95 98<br />

Switch-on duration Q91 No action Group error<br />

T1<br />

+<br />

T2<br />

NSB0_01502a<br />

Main circuit<br />

Possibility 3b:<br />

Inline circuit with ramp-down function DC braking 3)<br />

(for device types 3RW44 26 to 3RW44 47)<br />

Control circuit<br />

Possibility 3b:<br />

Control of the DC braking contactor 3)<br />

L1<br />

L2<br />

L3<br />

Q1<br />

3/N/PE 400 V AC 1) , 50 Hz<br />

L1<br />

1/N/PE 230 V AC 1) , 50 Hz<br />

F2<br />

+24 V DC<br />

PLC output<br />

17<br />

CONTROL<br />

PRODUCTS<br />

F3<br />

Q11<br />

L1 L2 L3<br />

T1 T2 T3<br />

(optional<br />

semiconductor<br />

protection)<br />

M<br />

Motor right<br />

PS 1<br />

Start 2)<br />

No action<br />

No action<br />

Reset<br />

Reset<br />

PTC type A or<br />

Thermoclick<br />

M1<br />

PE<br />

Q91 Q92<br />

3 3<br />

U1 V1 W1<br />

M<br />

3~<br />

NSB0_01503b<br />

K4<br />

Q92<br />

Q91<br />

K4<br />

Q91<br />

Q92<br />

PE<br />

Q11 A1 L+ L- IN1 IN2 IN3 IN4<br />

PE<br />

DC braking contactor 3)<br />

96<br />

A2 13 14 23 24 33 34 95 98<br />

Switch-on duration<br />

4)<br />

K4<br />

N<br />

No action<br />

Group error<br />

T1<br />

+<br />

T2<br />

NSB0_01504a<br />

1) Permissible values for main and control voltage, see<br />

"Technical specifications".<br />

2) Caution: Risk of restarting!<br />

The start command (e. g. from the PLC) must be reset prior to a reset command<br />

because a new, automatic restart will take place automatically if a<br />

start command is active after the reset command. This applies especially<br />

in case of motor protection tripping.<br />

For safety reasons we recommend incorporating the group error output<br />

(terminals 95 and 96) in the controller.<br />

3) If the ramp-down function "Combined braking" is selected, no braking contactor<br />

is required.<br />

If the ramp-down function "DC braking" is selected, a braking contactor<br />

must be used in addition. For type see "Fuse Assignment (Inline Circuit)"<br />

on pages 17-238 to 17-240.<br />

For applications with large centrifugal masses (J Load > J Motor ) we recommend<br />

the function "DC braking".<br />

The output 2 must be switched over to "DC braking contactor".<br />

4) Auxiliary relay K4, e. g.:<br />

LZX:RT4A4T30 (230 V AC rated control supply voltage),<br />

LZX:RT4A4S15 (115 V AC rated control supply voltage).<br />

17-292<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog