For Operation in the Control Cabinet<br />

3RW Soft Starters<br />

Project Planning aids<br />

3RW44 connection examples for main and control circuits<br />

Main circuit<br />

Control circuit<br />

Possibility 1a:<br />

Possibility 1:<br />

Inline circuit with motor starter protector and SITOR fuse<br />

Control by pushbutton<br />

(semiconductor protection only)<br />

L1<br />

L2<br />

L3<br />

3/N/PE 400 V AC, 50 Hz<br />

L1<br />

1/N/PE 230 V AC 1) , 50 Hz<br />

Q1<br />

F2<br />

F3<br />

Q11<br />

L1 L2 L3<br />

(optional<br />

semiconductor<br />

protection fuse)<br />

Q11<br />

A1<br />

Stop<br />

S1<br />

2)<br />

Start S2<br />

Motor on right<br />

PS 1<br />

No action<br />

PTC type A<br />

or<br />

Thermoclick<br />

CONTROL<br />

PRODUCTS<br />

17<br />

No action<br />

Reset S3<br />

L+ L- IN1 IN2 IN3 IN4<br />

T1<br />

T2<br />

Soft Starter<br />

Control<br />

M1<br />

PE<br />

T1 T2 T3<br />

U1 V1 W1<br />

M<br />

3~<br />

NSB0_01490b<br />

PE<br />

N<br />

PE<br />

96<br />

A2 13 14 23 24 33 34 95 98<br />

On period<br />

No<br />

action<br />

No<br />

action<br />

Group<br />

error<br />

+<br />

NSB0_01494c<br />

Main circuit<br />

Possibility 1b:<br />

Possibility 1c:<br />

Inline circuit with all-range Inline circuit with line and<br />

protection<br />

SITOR fuse<br />

(line and semiconductor protection) (semiconductor protection only)<br />

1) Permissible values for main and control voltage, see "Technical<br />

specifications".<br />

2) Caution: Risk of restarting!<br />

Because the output is parameterized to "Motor ON", the start command is<br />

automatically active after the reset command and a new, automatic restart<br />

will take place. This applies especially in case of motor protection tripping.<br />

For safety reasons we recommend connecting the group error output (terminals<br />

95/96) in series with the output parameterized to "Motor ON".<br />

17-290<br />