For Operation in the Control Cabinet<br />

3RW Soft Starters<br />

3RW40 for standard applications<br />

Circuit Breaker SCCR<br />

Soft starters<br />

Q11<br />

Type<br />

ToC<br />

1<br />

Rated<br />

current<br />

Circuit Brakers<br />

Thermal Magnetic Instantaneous Trip Fuse<br />

480 V<br />

Type<br />

SCCR<br />

kA<br />

Max.<br />

size<br />

A<br />

600 V<br />

Type<br />

SCCR<br />

kA<br />

Max.<br />

size<br />

A<br />

480 V<br />

Type<br />

SCCR<br />

kA<br />

3RW40 24 11<br />

3RW40 26 23<br />

3RW40 27 29<br />

3RW40 28 34<br />

3RW40 36 42<br />

3RW40 37 58<br />

3RW40 38 62<br />

3RW40 46 73<br />

3RW40 47 98<br />

3RW40 55 117 FD63B 100 150 FD63B 50 150 FXD63A 100 150 FXD63A 50 150 RK5 100 200 J 100 400<br />

3RW40 56 145 JD63B 100 200 JD63B 50 250 FXD63A 100 250 FXD63A 50 250 RK5 100 250 J 100 500<br />

3RW40 73 205 JD63B 100 300 JD63B 50 300 JXD63A 100 300 JXD63A 50 300 RK5 100 250<br />

3RW40 74 248 JD63B 100 400 JD63B 50 400 JXD63A 100 400 JXD63A 50 400 RK5 100 450<br />

3RW40 75 315 LD63B 100 500 LD63B 50 450 JXD63A 100 400 JXD63A 50 400 RK5 100 600<br />

3RW40 76 385 LD63B 100 600 LD63B 50 600 LXD63H 100 600 LXD63H 50 600 L 100 700<br />

Fused version (line protection only)<br />

Max.<br />

size<br />

A<br />

600 V<br />

Type<br />

SCCR<br />

kA<br />

Max.<br />

size<br />

A<br />

600 V<br />

Type<br />

SCCR<br />

kA<br />

Max.<br />

size<br />

A<br />

600 V<br />

Type<br />

SCCR<br />

kA<br />

Max.<br />

size<br />

A<br />

Soft Starter<br />

Control<br />

F1<br />

Q21<br />

Q11<br />

M<br />

3~<br />

NSB0_01904<br />

Soft starters Line protection, maximum Line contactors<br />

Rated current Rated current Size (optional)<br />

ToC<br />

1<br />

Q11 F1 Q21<br />

Type A Type A<br />

Type of coordination "1" 1) : I q = 65 kA at 600 V +5 %<br />

3RW40 24 12.5 3NA3 820-6 50 00 3RT10 24<br />

3RW40 26 25 3NA3 822-6 63 00 3RT10 26<br />

3RW40 27 32 3NA3 824-6 80 00 3RT10 34<br />

3RW40 28 38 3NA3 824-6 80 00 3RT10 35<br />

3RW40 36 45 3NA3 130-6 100 1 3RT10 36<br />

3RW40 37 63 3NA3 132-6 125 1 3RT10 44<br />

3RW40 38 72 3NA3 132-6 125 1 3RT10 45<br />

3RW40 46 80 3NA3 136-6 160 1 3RT10 45<br />

3RW40 47 106 3NA3 136-6 160 1 3RT10 46<br />

3RW40 55 134 3NA3 244-6 250 2 3RT10 55-6A.36<br />

3RW40 56 162 3NA3 244-6 250 2 3RT10 56-6A.36<br />

3RW40 73 230 2 x 3NA3 354-6 2 x 355 3 3RT10 65-6A.36<br />

3RW40 74 280 2 x 3NA3 354-6 2 x 355 3 3RT10 66-6A.36<br />

3RW40 75 356 2 x 3NA3 365-6 2 x 500 3 3RT10 75-6A.36<br />

3RW40 76 432 2 x 3NA3 365-6 2 x 500 3 3RT10 76-6A.36<br />

1) The types of coordination are explained under "3RA1 Fuseless Load Feeders".<br />

The type of coordination "1" refers only to soft starters in combination<br />

with the stipulated protective device (motor starter protector/circuit<br />

breaker/fuse), not to any additional components in the feeder.<br />

17 CONTROL<br />

PRODUCTS<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 17-255