12.01.2021 Views

Speedfax 2017

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

For Operation in the Control Cabinet<br />

3RW Soft Starters<br />

3RW40 for standard applications<br />

Type 3RW40 2., 3RW40 3., 3RW40 4.<br />

Control electronics<br />

Operating indications LEDs DEVICE STATE/BYPASSED/FAILURE OVERLOAD<br />

Off Green Off Off<br />

Start Green Green flashing Off<br />

Bypass Green Green Off<br />

Ramp-down Green Green flashing Off<br />

Alarm signals<br />

I e /Class setting not permissible Green Not relevant Red flashing<br />

Start inhibited/thyristors too hot Yellow flashing Not relevant Off<br />

Error signals<br />

• 24 V: U < 0.75 x U s or U > 1.25 x U s Off Red Off<br />

• 110 ... 230 V: U < 0.75 x U s or U > 1.15 x U s Off Red Off<br />

Non-permissible I e /Class setting<br />

for edge 0 –> 1 on input IN Green Red Red flashing<br />

Motor protection shut-down (overload thermistor) Green Off Red<br />

Thermistor defective (open circuit, short-circuit) Green Off Red flickering<br />

Thermal overloading of the thyristors Yellow Red Off<br />

Missing mains voltage, phase failure, missing load Green Red Off<br />

Device fault Red Red Off<br />

Soft Starter<br />

Control<br />

Type 3RW40 5. and 3RW40 7.<br />

Control electronics<br />

Operating indications LEDs DEVICE STATE/BYPASSED FAILURE OVERLOAD<br />

Off Green Off Off Off<br />

Start Green Green flashing Off Off<br />

Bypass Green Green Off Off<br />

Ramp-down Green Green flashing Off Off<br />

Alarm signals<br />

I e /Class setting not permissible Green Not relevant Not relevant Red flashing<br />

Start inhibited/thyristors too hot Yellow flashing Not relevant Not relevant Off<br />

CONTROL<br />

PRODUCTS<br />

17<br />

Error signals<br />

U < 0.75 x U s or U > 1.15 x U s Off Off Red Off<br />

Non-permissible I e /Class setting<br />

for edge 0 –> 1 on input IN Green Off Red Red flashing<br />

Motor protection shut-down Green Off Off Red<br />

Thermal overloading of the thyristors Yellow Off Red Off<br />

Missing mains voltage, phase failure, missing load Green Off Red Off<br />

Device fault Red Off Red Off<br />

17-248<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog