12.01.2021 Views

Speedfax 2017

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

For Operation in the Control Cabinet<br />

3RW Soft Starters<br />

3RW30 for standard applications<br />

Soft Starter<br />

Control<br />

Type 3RW30 03<br />

Control electronics<br />

Rated values<br />

Rated control supply voltage<br />

V 24 ... 230 AC/DC<br />

• Tolerance<br />

% ± 10<br />

Rated control supply current<br />

mA 25 ... 4<br />

Rated frequency at AC<br />

Hz 50/60<br />

• Tolerance<br />

% ± 10<br />

Starting time s 0.1 ... 20 (adjustable)<br />

Starting voltage % 40 ... 100 (adjustable)<br />

Ramp-down time s 0 ... 20 (adjustable)<br />

Power electronics<br />

Rated operational voltage V AC 200 ... 400<br />

T olerance<br />

% ± 10<br />

Rated frequency Hz 50/60<br />

T olerance<br />

% ±10<br />

Uninterrupted duty (% of I e ) % 100<br />

Minimum load 1) (% of I e );<br />

at 40 °C<br />

% 9<br />

Maximum conductor length between soft starter and motor m 100 2)<br />

Degree of protection acc. to IEC 60529<br />

IP20 (IP00 terminal compartment)<br />

Permissible installation height m 5000<br />

(derating from 1000, see characteristic curves); higher on request<br />

Permissible mounting position<br />

10°<br />

10°<br />

10° 10°<br />

NSB0_01897<br />

Permissible ambient temperature<br />

Operation<br />

°C -25 ... +60; (derating from +40)<br />

Storage<br />

°C -40 ... +80<br />

17<br />

CONTROL<br />

PRODUCTS<br />

Load rating with rated operational current I e<br />

• Acc. to IEC and UL/CSA 1) , for individual mounting, AC-53a<br />

- At 40 °C<br />

A 3<br />

- At 50 °C<br />

A 2.6<br />

- At 60 °C<br />

A 2.2<br />

• Acc. to IEC and UL/CSA 1) , for butt-mounting, AC-53a<br />

- At 40 °C<br />

A 2.6<br />

- At 50 °C<br />

A 2.2<br />

- At 60 °C<br />

A 1.8<br />

Power loss<br />

• In operation after completed starting with uninterrupted rated operational<br />

W 6.5<br />

current (40 °C) approx.<br />

• At utilization of max. switching frequency<br />

W 3<br />

Permissible starts per hour<br />

• For intermittent duty S4, T u = 40 °C, stand-alone installation vertical 1/h 1500<br />

• ON period = 70 %<br />

% I e /s 300/0.2<br />

Conductor cross-sections<br />

Screw terminals<br />

(1 or 2 conductors connectable)<br />

For standard screwdriver<br />

size 2 and Pozidriv 2<br />

Spring-type terminals<br />

• Main conductors<br />

- Solid<br />

mm² 1 x (0.5 ... 4);<br />

2 x (0.5 ... 2.5)<br />

- Finely stranded with end sleeve mm² 1 x (0.5 ... 2.5);<br />

2 x (0.5 ... 1.5)<br />

- Stranded<br />

mm² --<br />

- AWG cables,<br />

AWG 2 x (20 ... 14)<br />

solid or stranded<br />

- Terminal screws M3, PZ2<br />

- Tightening torque NM 0.8 ... 1.2<br />

lb.in 7.1 ... 8.9<br />

• Auxiliary conductors<br />

- Solid<br />

mm² 1 x (0.5 ... 4);<br />

2 x (0.5 ... 2.5)<br />

- Finely stranded with end sleeve mm² 1 x (0.5 ... 2.5); 2 x (0.5 ... 1.5)<br />

- AWG cables,<br />

AWG 2 x (20 ... 14)<br />

solid or stranded<br />

- Terminal screws M3, PZ2<br />

- Tightening torque NM 0.8 ... 1.2<br />

lb.in 7 ... 8.9<br />

Main and auxiliary conductors<br />

• Solid<br />

2<br />

mm 2 x (0.25 ... 1.5)<br />

• Finely stranded with end sleeve mm 2 2 x (0.25 ... 1)<br />

• AWG cables,<br />

mm 2 2 x (24 ... 16)<br />

solid or stranded<br />

1) The rated motor current (specified on the motor's name plate) should at<br />

least amount to the specified percentage of the SIRIUS soft starter unit's<br />

rated operational current I e .<br />

2) If this value is exceeded, problems with line capacities may arise, which<br />

can result in false firing.<br />

17-240<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!