For Operation in the Control Cabinet<br />

3RW Soft Starters<br />

3RW30 for standard applications<br />

Type<br />

3RW30 1.-.BB.4 ... 3RW30 4.-.BB.4<br />

Power electronics<br />

Rated operational voltage V AC 200 ... 480<br />

Tolerance<br />

% -15/+10<br />

Rated frequency Hz 50/60<br />

T olerance<br />

% ±10<br />

Uninterrupted duty at 40 °C (% of I e ) % 115<br />

Minimum load (% of I e ) % 10 (at least 2 A)<br />

Maximum cable length between soft starter and motor m 300<br />

Permissible installation height m 5000<br />

(derating from 1000, see characteristic curves); higher on request<br />

Permissible mounting position<br />

(auxiliary fan not available)<br />

10° 10°<br />

10° 10°<br />

NSB0_01897<br />

Permissible ambient temperature<br />

Operation<br />

°C -25 ... +60; (derating from +40)<br />

Storage<br />

°C -40 ... +80<br />

Degree of protection IP20 for 3RW30 1. and 3RW30 2.;<br />

IP00 for 3RW30 3. and 3RW30 4.<br />

Type 3RW30 13 3RW30 14 3RW30 16 3RW30 17 3RW30 18<br />

Power electronics 40 °C/50 °C/60 °C<br />

Load rating with rated operational current I e<br />

• Acc. to IEC and UL/CSA 1) , for individual mounting at 40/50/60 °C, A 3.6/3.3/3 6.5/6/5.5 9/8/7 12.5/12/11 17.6/17/14<br />

AC-53a<br />

Power loss<br />

• In operation after completed starting with uninterrupted rated operational<br />

W 0.25 0.5 1 2 4<br />

current (40 °C) approx.<br />

• During starting with 300 % I M ( 40 °C)<br />

W 6 13 20 20 29<br />

Permissible rated motor current and starts per hour<br />

for normal starting (Class 10)<br />

2)<br />

- Rated motor current I M , starting time 10 s<br />

A 3.6/3.3/3 6.5/6/5.5 9/8/7 12.5/12/11 17.6/17/14<br />

- Starts per hour 3) 1/h 200/150/70 87/60/50 50 85/70/60 62/46/60<br />

- Rated motor current I<br />

2)<br />

M , starting time 20 s<br />

A 3.6/3.3/3 6.5/6/5.5 9/8/7 12.5/12/11 17.6/17/14<br />

- Starts per hour 3) 1/h 150/100/50 64/46/28 35 62/47/37 45/32/43<br />

1) Measurement at 60 °C according to UL/CSA not required.<br />

3) For intermittent duty S4 with ON period = 30 %, T u = 40 °C, stand-alone<br />

2) With 300 % I M .<br />

installation vertical. The quoted switching frequencies do not apply for<br />

automatic mode.<br />

Type 3RW30 26 3RW30 27 3RW30 28<br />

Power electronics 40 °C/50 °C/60 °C<br />

Load rating with rated operational current I e<br />

• Acc. to IEC and UL/CSA 1) , for individual mounting at 40/50/60 °C, A 25.3/23/21 32.2/29/26 38/34/31<br />

AC-53a<br />

Power loss<br />

• In operation after completed starting with uninterrupted rated operational<br />

W 8 13 19<br />

current (40 °C) approx.<br />

• During starting with 300 % I M ( 40 °C)<br />

W 47 55 64<br />

Permissible rated motor current and starts per hour<br />

for normal starting (Class 10)<br />

- Rated motor current I<br />

2)<br />

M , starting time 10 s<br />

A 25/23/21 32/29/26 38/34/31<br />

- Starts per hour 3) 1/h 23 23 19<br />

2) - Rated motor current I M , starting time 20 s<br />

A 25/23/21 32/29/26 38/34/31<br />

- Starts per hour 3) 1/h 15 16 12<br />

1) Measurement at 60 °C according to UL/CSA not required.<br />

With 300 % I M .<br />

3) For intermittent duty S4 with ON period = 30 %, T u = 40 °C, stand-alone<br />

installation vertical. The quoted switching frequencies do not apply for<br />

automatic mode.<br />

Soft Starter<br />

Control<br />

17 CONTROL<br />

PRODUCTS<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 17-237