Lighting and Heating Control<br />

Electrically Held Lighting Contactors, Class LE<br />

Revised on 03/31/20<br />

Technical Data<br />

Contactor LEN00B003 LEN00B004 LEN00C003 LEN00C004<br />

NEMA & General<br />

Purpose Control<br />

17<br />

CONTROL<br />

PRODUCTS<br />

General technical data:<br />

Finger-safe (main circuit / control circuit) yes / yes yes / yes yes / yes yes / yes<br />

Altitude (m) 2,000 2,000 2,000 2,000<br />

Ambient storage temperature (°C) -55 to 80 -55 to 80 -55 to 80 -55 to 80<br />

Ambient operating temperature (°C) 0 to 40 0 to 40 0 to 40 0 to 40<br />

Humidity (% non-condensing) 10 to 95 10 to 95 10 to 95 10 to 95<br />

Shock resistance at rectangular impulse (g/ms) 6.7 / 5, 4.2 / 10 6.7 / 5, 4.2 / 10 7.5 / 5, 4.7 / 10 7.5 / 5, 4.7 / 10<br />

Shock resistance at sine pulse (g/ms) 10.5 / 5, 6.6 / 10 10.5 / 5, 6.6 / 10 11.8 / 5, 7.4 / 10 11.8 / 5, 7.4 / 10<br />

Mechanical operating cycles as operating time:<br />

of contactor 30,000,000 30,000,000 10,000,000 10,000,000<br />

of contactor with additional aux contacts 10,000,000 10,000,000 10,000,000 10,000,000<br />

Main circuit:<br />

Number of NC / NO main contacts 0NC / 3NO 0NC / 4NO 0NC / 3NO 0NC / 4NO<br />

Typical power loss per conductor (W) 0.7 0.7 0.9 0.9<br />

Off-load operating frequency (cycles per hour) 10,000 10,000 5,000 5,000<br />

Current ratings:<br />

Tungsten (poles per phase)<br />

Ballast (poles per phase)<br />

General and resistive (poles per phase)<br />

Coil ratings:<br />

20A @277V 1p 1ph<br />

20A @480V 2p 1ph<br />

20A @480V 3p 3ph<br />

20A @347V 1p 1ph<br />

20A @600V 2p 1ph<br />

20A @600V 3p 3ph<br />

20A @600V 1p 1ph<br />

20A @600V 2p 1ph<br />

20A @600V 3p 3ph<br />

20A @277V 1p 1ph<br />

20A @480V 2p 1ph<br />

20A @480V 3p 3ph<br />

20A @347V 1p 1ph<br />

20A @600V 2p 1ph<br />

20A @600V 3p 3ph<br />

20A @600V 1p 1ph<br />

20A @600V 2p 1ph<br />

20A @600V 3p 3ph<br />

30A @277V 1p 1ph<br />

30A @480V 2p 1ph<br />

30A @480V 3p 3ph<br />

30A @347V 1p 1ph<br />

30A @600V 2p 1ph<br />

30A @660V 3p 3ph<br />

30A @600V 1p 1ph<br />

30A @600V 2p 1ph<br />

30A @600V 3p 3ph<br />

Nominal voltage 2) 2) 2) 2)<br />

Inrush / sealed power (VA) 31.7 / 4.8 31.7 / 4.8 87 / 9.4 87 / 9.4<br />

Coil voltage tolerance factor 0.8 - 1.1 0.8 - 1.1 0.8 - 1.1 0.8 - 1.1<br />

Internal/standard auxiliary contact:<br />

30A @277V 1p 1ph<br />

30A @480V 2p 1ph<br />

30A @480V 3p 3ph<br />

30A @347V 1p 1ph<br />

30A @600V 2p 1ph<br />

30A @600V 3p 3ph<br />

30A @600V 1p 1ph<br />

30A @600V 2p 1ph<br />

30A @600V 3p 3ph<br />

Number of NC / NO auxiliary contacts 0NC / 1NO NA 1NC / 1NO 1NC / 1NO<br />

Rating A600 / Q600 NA A600 / Q600 A600 / Q600<br />

Installation/mounting/dimensions:<br />

Mounting orientation vertical vertical vertical vertical<br />

Type of mounting: screw / DIN rail yes / yes yes / yes yes / yes yes / yes<br />

Height x Width x Depth (mm) 57.5 x 45 x 73 57.5 x 45 x 73 85 x 45 x 97 85 x 60 x 97<br />

Minimum clearance to sides (mm) 0 0 0 0<br />

Minimum clearance to earthed parts (mm) 6 6 6 6<br />

Connection type / torque for main circuit terminals screw / 7-10 lb in screw / 7-10 lb in screw / 18-22 lb in screw / 18-22 lb in<br />

Connection type / torque for control circuit terminals screw / 7-10 lb in screw / 7-10 lb in screw / 7-10 lb in screw / 7-10 lb in<br />

Solid and stranded conductors for<br />

main contacts (AWG)<br />

Solid and stranded conductors for<br />

control circuit (AWG)<br />

2x(20-16),<br />

2x(18-14), 2x(12)<br />

2x(20-16),<br />

2x(18-14)<br />

2x(20-16),<br />

2x(18-14), 2x(12)<br />

2x(20-16),<br />

2x(18-14)<br />

2x(6-12),<br />

2x(14-8)<br />

2x(20-16),<br />

2x(18-14)<br />

2x(6-12),<br />

2x(14-8)<br />

2x(20-16),<br />

2x(18-14)<br />

Conductor type for main and control circuits 75°C CU 75°C CU 75°C CU 75°C CU<br />

Short circuit current rating of main circuit:<br />

Short circuit current rating 5kA @ 600V 5kA @ 600V 5kA @ 600V 5kA @ 600V<br />

Max fuse / circuit breaker (Amp) 30 / 25 30 / 25 60 / 40 60 / 40<br />

Certificates: cULus cULus cULus cULus<br />

Must use an external (optional) auxiliary contact.<br />

2) Refer to catalog selection tables for coil voltages.<br />

17-84<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog