12.01.2021 Views

Speedfax 2017

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Pump Control Panels<br />

Slim Line NEMA Pump Controller for the Agricultural industry, Class 82<br />

Selection<br />

Class 82 Technical information<br />

General Technical Data:<br />

Weight<br />

Height x Width x Depth<br />

Maximum altitude<br />

Ambient (outside enclosure) storage temperature<br />

Ambient (outside enclosure) operating temperature<br />

Country of origin<br />

Size 1 (Standard Encl.) 23lbs.<br />

Size 1 (Extra Wide Encl.) 47lbs.<br />

Size 2 (Standard Encl.) 47lbs.<br />

Size 1 (Standard Encl.) 26 x 12 x 5in.<br />

Size 1 (Extra Wide Encl.) 35 x 17 x 6in.<br />

Size 2 (Standard Encl.) 35 x 17 x 6in.<br />

6560 ft.<br />

(-30 to 65)°C / (-22 to 149)°F<br />

(-20 to 40)°C / (-4 to 104)°F<br />

Mexico<br />

Horsepower Rating:<br />

See selection table above<br />

See selection table above<br />

Contactor:<br />

Number of NO main contacts 3<br />

Amp rating<br />

32A, 50A<br />

Mechanical operating cycles 10,000,000<br />

NEMA & General<br />

Purpose Control<br />

17<br />

Internal / Standard Auxiliary Contact:<br />

Number of NC / NO auxiliary contacts<br />

NEMA contact rating designation<br />

Optional auxiliary contacts available<br />

Coil:<br />

Voltage<br />

Apparent pull-in / holding power<br />

Normal coil operating limits (% of rated voltage)<br />

Pick-up time / Drop-out time<br />

1NC / 1NO<br />

A600 AC / Q600 DC<br />

Yes<br />

220/230V 50/60Hz, 460V 60Hz, or 110/120V 50/60Hz<br />

81 VA / 10.5 VA<br />

80% - 110% at 60Hz<br />

8-40 / 4-16 msec<br />

CONTROL<br />

PRODUCTS<br />

Overload Relay:<br />

Current range<br />

0.75 - 3.4 or 3 - 12 or 5.5 - 22 or 10 - 40 Amps or 13 - 52 Amps<br />

Trip Class Class 5 / 10 (factory set) / 20 / 30<br />

Trip detection<br />

Overload, phase failure, phase unbalance, ground fault<br />

Phase failure sensitivity<br />

Trip time after phase loss: < 3 sec<br />

Repeat accuracy Within 1%<br />

Reset options<br />

Manual, automatic and remote<br />

External reset<br />

Yes<br />

Test function<br />

Electronics and manual actuation<br />

Conformal coating on printed circuit board<br />

Yes<br />

Number of NC / NO auxiliary contacts<br />

1NC /1NO<br />

Rating of auxiliary contacts<br />

B600 AC / R300 DC<br />

Single contact isolation<br />

600 V<br />

Dual contact isolation<br />

300 V differing polarity / 600 V common polarity<br />

17-72<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog