Reduced Voltage Heavy Duty Starters<br />

2 Step Part Winding with Solid State Overload, Class 36 & 37 Selection<br />

Ordering Information<br />

Field Modification Kits see page 17-102.<br />

Factory Modifications see page 17-114.<br />

Dimensions see page page 17-150.<br />

Wiring Diagrams see page 17-162.<br />

Replacement Parts see page 17-120.<br />

Coil and Control Voltage<br />

The coil voltage will always match the<br />

motor voltage. As standard, a CPT is<br />

supplied and 120V control voltage is<br />

utilized. To change to 120V voltage (CPT<br />

not supplied), change the 9th character<br />

to “F”. To change to 24VAC voltage<br />

(CPT not supplied), change the 9th<br />

character to “J”.<br />

NEMA 4/4X Stainless Steel Enclosures<br />

Motor<br />

Voltage<br />

200<br />

230<br />

460<br />

575<br />

Max<br />

Hp<br />

Overload Relay<br />

NEMA<br />

Size Amp<br />

(1/2 Size) Range<br />

Frame<br />

Size<br />

Non-Combination<br />

Catalog<br />

Number<br />

List<br />

Price $<br />

Combination Non-Fusible<br />

Disconnect<br />

Disc.<br />

Amp Catalog List<br />

Rating Number Price $<br />

Combination Fusible<br />

Disconnect<br />

Fuse Clip<br />

Amp/Volt Catalog<br />

Rating Number<br />

Combination Circit Breaker<br />

Circuit<br />

Breaker Catalog List<br />

Amps Number Price $<br />

7½ 0 5.5–22 A1 36CUDP6WD 60 37CUDP6WDD 60A/250V 37CUDP6WDF 30 37CUDP6WDP<br />

10 1 5.5–22 A1 36DUDP6WD 60 37DUDP6WDD 60A/250V 37DUDP6WDF 50 37DUDP6WDP<br />

15 (1¾) 10–40 A1 36EUEP6WD 100 37EUEP6WDD 100A/250V 37EUEP6WDF 100 37EUEP6WDP<br />

20 2 13–52 B 36FUFP6WD 100 37FUFP6WDD 100A/250V 37FUFP6WDF 100 37FUFP6WDP<br />

30 (2½) 25–100 B 36GUGP6WD 200 37GUGP6WDD 200A/250V 37GUGP6WDF 125 37GUGP6WDP<br />

40 3 25–100 B 36HUGP6WD 200 37HUGP6WDD 200A/250V 37HUGP6WDF 150 37HUGP6WDP<br />

50 (3½) 50–200 B 36IUHP6WD 200 37IUHP6WDD 200A/250V 37IUHP6WDF 250 37IUHP6WDP<br />

75 4 50–200 B 36JUHP6WD 400 37JUHP6WDD 400A/250V 37JUHP6WDF 400 37JUHP6WDP<br />

7½ 0 5.5–22 A1 36CUDP2WG 60 37CUDP2WGD 60A/250V 37CUDP2WGF 30 37CUDP2WGP<br />

10 1 5.5–22 A1 36DUDP2WG 60 37DUDP2WGD 60A/250V 37DUDP2WGF 50 37DUDP2WGP<br />

20 (1½) 10–40 A1 36EUEP2WG 100 37EUEP2WGD 100A/250V 37EUEP2WGF 100 37EUEP2WGP<br />

25 2 13–52 B 36FUFP2WG 100 37FUFP2WGD 100A/250V 37FUFP2WGF 100 37FUFP2WGP<br />

30 (2½) 25–100 B 36GUGP2WG 200 37GUGP2WGD 200A/250V 37GUGP2WGF 100 37GUGP2WGP<br />

50 3 25–100 B 36HUGP2WG 200 37HUGP2WGD 200A/250V 37HUGP2WGF 150 37HUGP2WGP<br />

60 (3½) 50–200 B 36IUHP2WG 200 37IUHP2WGD 200A/250V 37IUHP2WGF 250 37IUHP2WGP<br />

75 4 50–200 B 36JUHP2WG 400 37JUHP2WGD 400A/250V 37JUHP2WGF 250 37JUHP2WGP<br />

10 0 5.5–22 A1 36CUDP4WH 30 37CUDP4WHD 30A/600V 37CUDP4WHF 30 37CUDP4WHP<br />

15 1 5.5–22 A1 36DUDP4WH 60 37DUDP4WHD 60A/600V 37DUDP4WHF 30 37DUDP4WHP<br />

30 (1¾) 10–40 A1 36EUEP4WH 60 37EUEP4WHD 60A/600V 37EUEP4WHF 50 37EUEP4WHP<br />

40 2 13–52 B 36FUFP4WH 100 37FUFP4WHD 100A/600V 37FUFP4WHF 100 37FUFP4WHP<br />

60 (2½) 25–100 B 36GUGP4WH 200 37GUGP4WHD 200A/600V 37GUGP4WHF 100 37GUGP4WHP<br />

75 3 25–100 B 36HUGP4WH 200 37HUGP4WHD 200A/600V 37HUGP4WHF 125 37HUGP4WHP<br />

100 (3½) 50–200 B 36IUHP4WH 200 37IUHP4WHD 200A/600V 37IUHP4WHF 150 37IUHP4WHP<br />

150 4 50–200 B 36JUHP4WH 400 37JUHP4WHD 400A/600V 37JUHP4WHF 250 37JUHP4WHP<br />

10 0 5.5–22 A1 36CUDP5WE 30 37CUDP5WED 30A/600V 37CUDP5WEF 30 37CUDP5WEP<br />

15 1 5.5–22 A1 36DUDP5WE 60 37DUDP5WED 60A/600V 37DUDP5WEF 30 37DUDP5WEP<br />

30 (1¾) 10–40 A1 36EUEP5WE 60 37EUEP5WED 60A/600V 37EUEP5WEF 50 37EUEP5WEP<br />

40 2 13–52 B 36FUFP5WE 60 37FUFP5WED 60A/600V 37FUFP5WEF 50 37FUFP5WEP<br />

60 (2½) 25–100 B 36GUGP5WE 100 37GUGP5WED 100A/600V 37GUGP5WEF 100 37GUGP5WEP<br />

75 3 25–100 B 36HUGP5WE 200 37HUGP5WED 200A/600V 37HUGP5WEF 125 37HUGP5WEP<br />

100 (3½) 50–200 B 36IUHP5WE 400 37IUHP5WED 400A/600V 37IUHP5WEF 150 37IUHP5WEP<br />

150 4 50–200 B 36JUHP5WE 400 37JUHP5WED 400A/600V 37JUHP5WEF 250 37JUHP5WEP<br />

NEMA & General<br />

Purpose Control<br />

17 CONTROL<br />

PRODUCTS<br />

Note: All starter sizes carry one maximum Hp rating (per<br />

the National Electric Code).<br />

Product Category: NEMA<br />

Siemens Industry, Inc. SPEEDFAX Product Catalog 17-41

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!