17.12.2020 Views

API RP 581 - 3rd Ed.2016 - Add.2-2020 - Risk-Based Inspection Methodology

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

RISK-BASED INSPECTION METHODOLOGY, PART 3—CONSEQUENCE OF FAILURE METHODOLOGY 3-113

5.13 Nomenclature

Coefficients C

1

through C41

that provide the metric and U.S conversion factors for the equations are provided

in Annex 3.B. The following lists the nomenclature used in Section 5.

Aburn is the pool fire area based on burning rate, associated with the n th release hole size, m 2 (ft 2 )

pf , n

AIT

is the autoignition temperature of the released fluid, K (°R)

Amax is the maximum pool fire area based on a pool depth of 5 mm (0.0164 ft), associated with the

pf , n

n th release hole size, m 2 (ft 2 )

A is the pool fire surface area, associated with the n th release hole size, m 2 (ft 2 )

pf , n

BP

s

is the boiling point temperature of the stored fluid at normal operating conditions, K (°R)

CA is the final consequence area, m 2 (ft 2 )

f

CA is the component damage consequence area for a BLEVE associated with the rupture case, m 2

bleve

f , cmd

(ft 2 )

CA is the personnel injury consequence area for a BLEVE associated with the rupture case,

bleve

f , inj

m 2 (ft 2 )

CA is the footprint at grade level of the portion of the vapor cloud that exceeds the toxic exposure

cloud

f , n

limit of the toxic component being evaluated, associated with the n th release hole size, m 2 (ft 2 )

CA is the component damage consequence area for a fireball associated with the rupture case, m 2

fball

f , cmd

(ft 2 )

CA is the personnel injury consequence area for a fireball associated with the rupture case, m 2 (ft 2 )

fball

f , inj

CA is the final overall component damage flammable consequence area, m 2 (ft 2 )

flam

f , cmd

CA is the component damage flammable consequence area associated with the n th release hole

flam

f , cmd , n

size, m 2 (ft 2 )

CA is the final overall personnel injury flammable consequence area, m 2 (ft 2 )

flam

f , inj

CA is the personnel injury flammable consequence area associated with the n th release hole size,

flam

f , inj,

n

m 2 (ft 2 )

CA is the component damage consequence area for a flash fire associated with the n th release hole

flash

f , cmd , n

size, m 2 (ft 2 )

CA is the personnel injury consequence area for a flash fire associated with the n th release hole

flash

f , inj,

n

size, m 2 (ft 2 )

Hooray! Your file is uploaded and ready to be published.