Connection of a BC5 measuring cable at a 6V or 12V battery<br />
Connection of BC4 measuring cable at a 2V cell with 2 poles<br />
Connection of a BC4 measuring cable at a 2V cell with 4 or more poles<br />
1.1.2 Connection of the <strong>BACS</strong> Measuring Cables to the <strong>BACS</strong> C Modules<br />
After installing the <strong>BACS</strong> measuring cables, connect the 4 Pole connector with the <strong>BACS</strong> modules. Insert the<br />
connector until you can feel that the lock is closed. Detach the foil of the Velcro underneath of the <strong>BACS</strong><br />
module and the Temperature sensor and fix the <strong>BACS</strong> module on the top of the battery or on the side as<br />
near to the top of the battery as possible. At REV 3 2 foils have to be removed. The smaller one is for the<br />
integrated temperature sensor into the housing, which should be in contact with the surface of the<br />
accumulator.<br />
Copyright of the European Union is effecti ve (Copyright EU) (c) 2012 GENEREX Systems <strong>GmbH</strong>, H amburg, Ger many, All rights reserved<br />