Exact observation<br />

of the battery<br />

temperature up to<br />

12 hours after<br />

discharging<br />

resistance values and the voltages are stable.<br />

Observe battery temperature for up to 12 hours after a<br />

discharge period! The risk of thermal runaways (for VRLA<br />

batteries) is elevated direct after discharges when the<br />

charging process is started. Rising temperatures in<br />

damaged battery cells / blocs can cause fire. The highest<br />

risk of a thermal runaway and subsequent system damages<br />

has to be expected during approx. 12 hours after battery<br />

discharge. React immediately if the battery cell / bloc<br />

temperature rises after discharge phase instead of a slow<br />

decrease or stagnation.<br />

<strong>Safety</strong> <strong>instructions</strong> – for <strong>BACS</strong> configuration and installation<br />

Avoid installations in certain areas<br />

Do not install <strong>BACS</strong> in the following areas:<br />

In rooms which are not protected from water or high humidity, in wet or dusty places<br />

In areas with constantly high concentration of salted or oxidising gases<br />

Near to open flames, flying sparcs or heat sources, as well as in areas with extreme heat or at<br />

places with high variations in temperature.<br />

In areas with high vibrations or mechanical movements.<br />

In areas with high gas concentration or flammable materials.<br />

Monitoring System - Configure and monitor alarms<br />

<strong>BACS</strong> is a monitoring system and should be handled accordingly, assure a correct setting of the<br />

alarm threshold and appropriate reaction in case of alarms!<br />

<strong>BACS</strong> is a tool to increase the durability of the accumulators but its most important function is<br />

monitoring of the battery to avoid breakdowns. It is required to ensure a reaction within a couple<br />

of hours after any alarm. <strong>BACS</strong> is not able to balance battery or charger failures constantly but<br />

provides through its EQUALISATION and alerting functions, an advance warning time which<br />

should be used in any case to avoid fatal damages!<br />

Never mix different <strong>BACS</strong> C Module versions or <strong>BACS</strong> Measuring cabletypes ! You must not use<br />

<strong>BACS</strong> C REV 2 or 3 on the same Batterysystem, nor use <strong>BACS</strong> BC2 or BC5 cables on the same<br />

batterysystem or use BC2 cables with C Modules REV 3. This would damage the modules or lead<br />

to wrong measurings.<br />

For questions and comments refer to:<br />

www.generex.de<br />

support@generex.de<br />

Copyright of the European Union is effecti ve (Copyright EU) (c) 2012 GENEREX Systems <strong>GmbH</strong>, H amburg, Ger many, All rights reserved<br />

TEL +49( 40)22692910 - EMAIL gener ex@generex.de - WEB www.generex.de (This and all other product datasheets ar e available for downl oad.)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!