8. Filled lead-acid batteries contain highly explosive gas (hydrogen/ air<br />
mixture). Never smoke, handle open flames or create sparks near the<br />
batteries. Always avoid electrostatic discharge; wear cotton clothing and<br />
ground yourself if necessary.<br />
9. Wear the appropriate safety clothing and equipment.<br />
For further information refer to the battery makers <strong>instructions</strong> for installation, commissioning and<br />
operating of their battery products.<br />
<strong>Safety</strong> <strong>instructions</strong> – <strong>BACS</strong> safety precautions<br />
Attention<br />
High voltage<br />
warning<br />
Magnetic<br />
emissions<br />
<strong>Installation</strong> by<br />
qualified<br />
personnel only!<br />
Warning!<br />
Check Modules<br />
during<br />
installation and<br />
initial charging<br />
Do not open the <strong>BACS</strong> sensor modules. Do not attach any<br />
kind of objects to the battery or the <strong>BACS</strong> modules itself<br />
apart from the connecting cables! The <strong>BACS</strong> modules and<br />
cables could be live!<br />
Do not apply any magnetic sensitive equipment near the<br />
<strong>BACS</strong> Webmanager, like monitors, disk drives, memory<br />
chips or magnetic tapes.<br />
The <strong>BACS</strong> installation should only be installed by<br />
qualified personnel. <strong>BACS</strong> is to be installed on batteries<br />
where high voltages could cause injuries or even death if<br />
not handled properly!<br />
The <strong>BACS</strong> connection cables (temperature cable, bus<br />
cable, measuring cable) could be live! To avoid short<br />
circuits, do not touch, replace or cut the <strong>BACS</strong> cables,<br />
before having disconnected the system off the batteries!<br />
<strong>BACS</strong> modules must NOT be mounted on a damaged<br />
battery! If a battery is damaged and the internal resistance<br />
is extremely high, the charge current, respectively<br />
discharge current would not flow through the battery but<br />
rather would search for a way with the lowest resistance,<br />
through the <strong>BACS</strong> module. In this case heating could<br />
destroy the <strong>BACS</strong> module. Therefore never use batteries,<br />
which are obviously damaged or show extremely high<br />
internal resistances.<br />
The GENEREX service technician should watch the<br />
<strong>BACS</strong> modules and the initial charge during the<br />
installation. It should be checked, if the <strong>BACS</strong> modules get<br />
very hot. This would be an indication for a damaged<br />
battery or incorrect mounted cables. Do not leave the<br />
installation place, before the <strong>BACS</strong> system has been<br />
completely installed and the battery charge has started for<br />
60 minutes. The system is safe and can be monitored<br />
remote, if the <strong>BACS</strong> system shows normal internal<br />
Copyright of the European Union is effecti ve (Copyright EU) (c) 2012 GENEREX Systems <strong>GmbH</strong>, H amburg, Ger many, All rights reserved<br />