Refrigeration & Air Conditioning Technology 7th Edition

15.07.2019 Views

1212 Section 7 Air-Conditioning (Cooling) CONTROL WIRES FROM INSIDE THE HOUSE DISCONNECT COMPRESSOR CONTACTOR 24 V CONTACTS COIL LOW-PRESSURE CONTROL RC S R C COMMON TERMINAL ON COMPRESSOR COMPRESSOR CONDENSER FAN MOTOR © Cengage Learning 2013 Figure 41.30 The wiring diagram of basic components in a control-and-compressor circuit. compressor is suction-gas-cooled)? Can the start-assist circuit not be working and the compressor not starting? Allow the compressor to cool before restarting it. It is best to fix the unit so that it will not come back on for several hours. The best way to do this is to remove a lowvoltage wire. If the disconnect switch is pulled, by the next day the refrigerant charge may have migrated to the crankcase because there was no crankcase heat. To start the unit within the hour rather than waiting, pull the disconnect switch and run a small amount of water through a hose over the compressor. SAFETY PRECAUTION: The standing water poses a potential electrical hazard. Be sure that all electrical components are protected with plastic or other waterproof covering. Do not come in contact with the water or electrical current when working around live electricity.• It will take about 30 min to cool. Have the gauges and a cylinder of refrigerant connected on the unit because when the compressor is started up by closing the disconnect, it may need refrigerant. If the system has a low charge, taking the time to set up to charge after starting the system may allow the compressor to cut off again from overheating before the gauges are connected. 41.12 COMPRESSOR ELECTRICAL CHECKUP Manufacturers report that a fairly high percentage of compressors returned to them under warranty are actually not defective but were reported by the technician as defective. The technician should use great care when condemning a compressor, as it costs a lot of money in labor and materials to reclaim the refrigerant, ship in a new compressor, and ship the defective compressor back to the manufacturer for in-warranty work. When the compressor is out of warranty, the owner must bear that burden. The technician must be correct with the diagnosis. When a compressor will not start, the problem can be either electrical or mechanical. The electrical portion of the problem is rather easy to prove. When the technician can prove the compressor is electrically sound and it will not start, the only other conclusion would be mechanical. The steps for checking a single-phase compressor electrically are as follows: 1. Check the compressor from winding to ground using either an ohmmeter or a megohmmeter. A megohmmeter will detect much smaller ground circuits and is used on larger equipment exclusively. If there is a circuit showing to ground, remove all wires from the compressor terminals and check just the terminals. If the ground is no longer there, the ground is somewhere in the circuit wiring, not the compressor. If a ground is still indicated, clean the compressor terminal block if there is a possibility that current can leak to ground due to dirt. If there is still a ground, condemn the compressor as grounded. SAFETY PRECAUTION: If a compressor has a large amount of liquid refrigerant in the compressor housing, such as when the crankcase heater has been off for a long period, a circuit to ground may be detected. If the compressor crankcase heat has been off and the compressor housing is cool, it is advisable to let it heat for about 24 hours and check it again. The reason for this condition is probably that the refrigerant has floated up into the motor windings some system contamination that is normally dormant. After the 24-hour heating period, the system should operate correctly. Also, dirt around the motor terminals can cause a slight circuit. If there is a question, clean them with a degreasing solvent and try again.• 2. Check the start winding for correct resistance from common to start.

Unit 41 Troubleshooting 1213 3. Check the run winding for correct resistance from common to run. If the correct resistances are not readily available, make sure that the start winding and run winding have different resistances. The start winding should have much more resistance than the run winding. Either winding can have some shorted turns in the motor. Figure 41.31 shows a start winding with shorted, sometimes called shunted, winding. Figure 41.32 shows a start winding that has an open circuit. 4. Check for continuity from the run to the common terminal. If this circuit is open, the winding thermostat may be open. If the compressor is hot to the touch, let it cool THE MOTOR TERMINALS ARE INSULATED WHERE THEY PASS THROUGH THE COMPRESSOR HOUSING. RUN COMMON START SOME OF THE WINDINGS ARE TOUCHING EACH OTHER AND REDUCING THE RESISTANCE IN THE START WINDING. Figure 41.31 A compressor with a shorted, or shunted, winding. R C S THE START WINDING HAS AN OPEN CIRCUIT. Figure 41.32 A compressor with an open start winding. © Cengage Learning 2013 © Cengage Learning 2013 R C S OPEN CIRCUIT HEAT BE SURE POWER IS OFF. Figure 41.33 Cooling a compressor with water. RUNNING WATER IS BEING APPLIED TO A HOT COMPRESSOR. for several hours or cool it with water, Figure 41.33. SAFETY PRECAUTION: Make sure all power is off and do not stand in water when electrically checking any circuit.• 5. Check the voltage from common to run and from common to start using two different voltmeters while starting the motor. This voltage must be within 10% of the motor’s ratings. For example, many motors are rated at 208/230. The minimum voltage would be 187.2 V (208 0.90 187.2) and the maximum voltage would be 253 V (230 1.10 253). This voltage must be verified as close to the compressor terminals as possible, but do not use the terminals themselves. Follow the wiring back to the first junction, such as the load side of the compressor contactor. It is not unusual for a loose connection to create a low-line-voltage problem at the compressor. If there is any discoloration at the motor terminals, suspect a loose connection. SAFETY PRECAUTION: Never start a compressor with the motor terminal cover box removed. If a motor terminal were to blow out while starting, there is the potential for a high-velocity blowtorch-type of fire. The electrical arc may ignite the escaping oil with the refrigerant, propelling it outward. The box and cover are built to enclose this type of malfunction.• The steps for checking a three-phase compressor electrically are as follows: 1. Check the compressor from all windings to ground using either an ohmmeter or a megohmmeter as described previously in step 1. Pay attention to the Safety Precautions. 2. Check each set of windings from winding to winding— T1 to T2, T1 to T3, and T2 to T3—on a three-lead motor. Some larger motors may be dual motors in the same housing; check both motors. There should be the same resistance across each motor winding on a three-phase motor. There should be no circuit from motor to motor in a dual motor application. © Cengage Learning 2013

Unit 41 Troubleshooting 1213<br />

3. Check the run winding for correct resistance from<br />

common to run. If the correct resistances are not readily<br />

available, make sure that the start winding and run<br />

winding have different resistances. The start winding<br />

should have much more resistance than the run winding.<br />

Either winding can have some shorted turns in the<br />

motor. Figure 41.31 shows a start winding with shorted,<br />

sometimes called shunted, winding. Figure 41.32 shows<br />

a start winding that has an open circuit.<br />

4. Check for continuity from the run to the common terminal.<br />

If this circuit is open, the winding thermostat may<br />

be open. If the compressor is hot to the touch, let it cool<br />

THE MOTOR TERMINALS ARE INSULATED<br />

WHERE THEY PASS THROUGH THE<br />

COMPRESSOR HOUSING.<br />

RUN<br />

COMMON<br />

START<br />

SOME OF THE WINDINGS ARE<br />

TOUCHING EACH OTHER AND<br />

REDUCING THE RESISTANCE<br />

IN THE START WINDING.<br />

Figure 41.31 A compressor with a shorted, or shunted, winding.<br />

R<br />

C<br />

S<br />

THE START WINDING<br />

HAS AN OPEN CIRCUIT.<br />

Figure 41.32 A compressor with an open start winding.<br />

© Cengage Learning 2013<br />

© Cengage Learning 2013<br />

R<br />

C<br />

S<br />

OPEN CIRCUIT<br />

HEAT<br />

BE SURE POWER IS OFF.<br />

Figure 41.33 Cooling a compressor with water.<br />

RUNNING WATER IS<br />

BEING APPLIED TO<br />

A HOT COMPRESSOR.<br />

for several hours or cool it with water, Figure 41.33.<br />

SAFETY PRECAUTION: Make sure all power is off and do<br />

not stand in water when electrically checking any circuit.•<br />

5. Check the voltage from common to run and from<br />

common to start using two different voltmeters while<br />

starting the motor. This voltage must be within 10%<br />

of the motor’s ratings. For ex<strong>amp</strong>le, many motors are<br />

rated at 208/230. The minimum voltage would be<br />

187.2 V (208 0.90 187.2) and the maximum voltage<br />

would be 253 V (230 1.10 253). This voltage<br />

must be verified as close to the compressor terminals<br />

as possible, but do not use the terminals themselves.<br />

Follow the wiring back to the first junction, such as the<br />

load side of the compressor contactor. It is not unusual<br />

for a loose connection to create a low-line-voltage<br />

problem at the compressor. If there is any discoloration<br />

at the motor terminals, suspect a loose connection.<br />

SAFETY PRECAUTION: Never start a compressor<br />

with the motor terminal cover box removed. If a motor terminal<br />

were to blow out while starting, there is the potential<br />

for a high-velocity blowtorch-type of fire. The electrical arc<br />

may ignite the escaping oil with the refrigerant, propelling<br />

it outward. The box and cover are built to enclose this type<br />

of malfunction.•<br />

The steps for checking a three-phase compressor electrically<br />

are as follows:<br />

1. Check the compressor from all windings to ground<br />

using either an ohmmeter or a megohmmeter as described<br />

previously in step 1. Pay attention to the Safety<br />

Precautions.<br />

2. Check each set of windings from winding to winding—<br />

T1 to T2, T1 to T3, and T2 to T3—on a three-lead motor.<br />

Some larger motors may be dual motors in the same<br />

housing; check both motors. There should be the same<br />

resistance across each motor winding on a three-phase<br />

motor. There should be no circuit from motor to motor<br />

in a dual motor application.<br />

© Cengage Learning 2013

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!