06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

FIGURE 2.7.22 Equalizer winding incorporated into the main coil of a regulator.<br />

FIGURE 2.7.21 Tap-changer interruption envelope.<br />

Figure 2.7.21 shows a typical tap-changer interruption envelope. Load current (I L ), tap voltage,<br />

reactor circulating current (I C ), and power factor (PF) are key variables affecting a tap changer’s<br />

interrupting ability and its contact life. A circulating current (I C ), caused by the two contacts being<br />

at different positions (reactor energized with 1 1 / 4% tap voltage), is limited by the reactive impedance<br />

of this circuit. Two opposing requirements must be kept in mind when designing the amount of<br />

reactance for the value of the circulating current. First, the circulating current must not be excessive;<br />

second, the variation of reactance during the switching cycle should not be so large as to introduce<br />

undesirable fluctuations in the line voltage. The reactor has an iron core with gaps in the magnetic<br />

circuit to set this magnetizing circulating current between 25 and 60% of full-load current, thus<br />

providing an equitable compromise between no-load and load conditions. The value of this circulating<br />

current also has a decided effect on switching ability and contact life. The ideal reactor, from<br />

an arcing standpoint, would be one that has a closed magnetic circuit at no-load with an air gap that<br />

would increase in direct proportion to increase in load.<br />

The voltage at the center tap is 5/8%, one-half of the 1 1 / 4% tap voltage of the series winding taps.<br />

Some regulators, depending upon the rating, use an additional winding (called an equalizer winding) in<br />

the bridging reactor circuit. The equalizer winding is a 5/8% voltage winding on the same magnetic<br />

circuit (core) as the shunt and series winding. The equalizer winding is connected into the reactor circuit<br />

opposite in polarity to the tap voltage. This is done so that the reactor is excited at 5/8% of line voltage<br />

on both the symmetrical and bridging positions. Figure 2.7.22 shows an equalizer winding incorporated<br />

into the main coil of a regulator. <br />

Voltage regulators are designed and manufactured in two basic constructions, defined by IEEE standards<br />

as Type A and Type B. Type A step-voltage regulators have the primary circuit (source voltage)<br />

connected directly to the shunt winding of the regulator. The series winding is connected to the load<br />

side of the regulator and, by adjusting taps, changes the output voltage. With Type A construction, the<br />

core excitation varies with the source voltage because the shunt winding is connected across the primary<br />

circuit. A separate voltage transformer is used to provide voltage for the tap-changer and control. The<br />

FIGURE 2.7.23 Voltage regulation on the load side (Type A).<br />

maximum range of regulation of the “raise” side equals the maximum range of regulation of the “lower”<br />

side, with 10% being the minimum amount of regulation. See the schematic diagram in Figure 2.7.23.<br />

Type B step-voltage regulators are constructed so that the primary circuit (source voltage) is applied<br />

by way of taps to the series winding of the regulator, which is connected to the source side of the regulator.<br />

With Type B construction, the core excitation is constant, since the shunt winding is connected across<br />

the regulated circuit. A control winding located on the same core as the series and shunt windings is<br />

used to provide voltage for the tap-changer and control. The maximum range of regulation of the “raise”<br />

side is higher than the maximum range of regulation of the “lower” side, with 10% being the minimum<br />

amount of regulation on the “raise” side. See the schematic diagram in Figure 2.7.24.<br />

Usually the choice of Type A or Type B is that of the supplier. However, the user can specify that an<br />

identical regulator design be provided if the application can anticipate the need to parallel with another<br />

unit in the same substation. Paralleling of regulators that are not of identical design can cause excessive<br />

circulating current between them. This is true even for short-term operation during switching, when the<br />

units are placed on the same numerical tap position and the control function is disabled. Caution: Any<br />

paralleling of step-voltage regulators (as described in this chapter) that may operate, even momentarily,<br />

on differing tap positions requires the inclusion of supplemental system reactance to avoid excessive<br />

circulating current during operation.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!