[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
2.7.4 Theory<br />
A step-voltage regulator is a tapped autotransformer. To understand how a regulator operates, one can<br />
start by comparing it with a two-winding transformer.<br />
Figure 2.7.12 is a basic diagram of a transformer with a 10:1 turns ratio. If the primary winding or<br />
V source has 1000 V applied, the secondary winding or V load will have an output of 100 V (10%). These two<br />
independent windings can be connected so that their voltages aid or oppose one another. A voltmeter<br />
connected across the output terminals measures either the sum of the two voltages or the difference<br />
between them. The transformer becomes an autotransformer with the ability to raise (Figure 2.7.13) or<br />
lower (Figure 2.7.14) the primary or system voltage by 10%. This construction is similar to a “Type A”<br />
single-phase step-voltage regulator, as described later in thissection.<br />
+<br />
VSOURCE = 1000<br />
+<br />
VLOAD= 100<br />
-<br />
-<br />
FIGURE 2.7.15 Tap-changer position indicator.<br />
10 : 1<br />
FIGURE 2.7.12 <strong>Transformer</strong> with 10:1 turns ratio.<br />
+<br />
-<br />
+<br />
VSOURCE = 1000 VLOAD = 1100<br />
-<br />
FIGURE 2.7.13 Step-up autotransformer.<br />
FIGURE 2.7.14 Step-down autotransformer.<br />
+<br />
-<br />
+<br />
VSOURCE = 1000 VLOAD = 900<br />
-<br />
In a voltage regulator, the equivalent of the high-voltage winding in a two-winding transformer would<br />
be referred to as the shunt winding. The low-voltage winding would be referred to as the series winding.<br />
The series winding is connected to the shunt winding in order to boost or buck the applied or primary<br />
voltage approximately 10%. The polarity of its connection to the shunt winding is accomplished by the<br />
use of a reversing switch on the internal motor-driven tap changer. Eight approximately 1 1 / 4 % taps are<br />
added to the series winding to provide small voltage-adjustment increments. To go even further to provide<br />
fine voltage adjustment, such as 16 approximate 5/8% tap steps, a center tapped bridging reactor (preventive<br />
autotransformer) — used in conjunction with two movable contacts on the motorized tap changer<br />
— is utilized. In all, there are 33 positions that include neutral, 16 lower positions (1L, 2L, 3L, 4L, etc.),<br />
and 16 raise positions (1R, 2R, 3R, 4R, etc.). Figure 2.7.15 illustrates a dial that indicates the arrangement<br />
of the tap positions.<br />
It is common practice to have the tap changer located in the same compartment as the core and coil.<br />
Dielectric practices consider the oil and insulation degradation due to the arc by-products. Figure 2.7.16<br />
shows a typical load-break tap changer used in a single-phase step-voltage regulator.<br />
The process of moving from one voltage-regulator tap to the adjacent voltage-regulator tap consists<br />
of closing the circuit at one tap before opening the circuit at the other tap. The movable tap-changer<br />
contacts move through stationary taps alternating in eight bridging and eight nonbridging (symmetrical)<br />
positions. Figure 2.7.17 shows the two movable tap-changer contacts on a symmetrical position, with<br />
the center tap of the reactor at the same potential. This is the case at tap position N (neutral) and all<br />
evenly numbered tap positions.<br />
An asymmetrical position, as shown in Figure 2.7.18, is realized when one tap connection is open<br />
before transferring the load to the adjacent tap. At this juncture, all of the load current flows through<br />
one-half of the reactor, magnetizing the reactor, and the reactance voltage is introduced into the circuit<br />
for about 25 to 30 msec during the tap change.<br />
Figure 2.7.19 shows the movable contacts in a bridging position; voltage change is one-half the 1 1 / 4 %<br />
tap voltage of the series winding because of its center tap and movable contacts located on adjacent<br />
stationary contacts. This is the case at all oddly numbered tap positions.<br />
Voltage phasor relations shown in Figure 2.7.20 represent a tap change. In this figure, S–SL represents<br />
source or unregulated voltage, and sections of the series winding are represented by S–TAP 1 and<br />
TAP 1–TAP 2. In operating the tap changer from TAP 1 to TAP 2, the load or regulated voltage has the<br />
following successive values:<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC